OT/ICS security

Siemens SIMATIC S7-1200 and S7-1500 vulnerabilities: CVE families, fixed firmware, access protection and hardening

Last updated:

Siemens SIMATIC S7-1200 and S7-1500 CPUs are programmed from TIA Portal over S7CommPlus on port 102/tcp and also expose a web server, and Siemens ProductCERT advisories published from August 2019 (SSA-232418) to October 2026 (SSA-591731) show four recurring CVE families: weak protection of the keys and passwords behind that path, crafted packets that stop the CPU, web server flaws, and hardware integrity gaps. The most cited, CVE-2022-38465, lets an attacker recover a family-wide private key. As of 2026-11-19, no S7-1200 or S7-1500 CPU CVE is in CISA's KEV catalog. The defence is current firmware, a TIA Portal V17 or later project, access protection, a disabled web server where unused, and segmentation.

Advisory facts in this guide come from Siemens ProductCERT advisories (SSA numbers) and their machine-readable CSAF files, from CISA's ICS advisories, which republish them, and from NVD. Siemens lists fixes per article number and firmware line, so read the advisory's full product table for your exact CPU before acting on any row below.

Key takeaways

  • Advisory facts in this guide come from Siemens ProductCERT advisories (SSA numbers) and their machine-readable CSAF files, from CISA's ICS advisories, which republish them, and from NVD.
  • An S7-1200 or S7-1500 CPU talks to TIA Portal, HMIs and other PLCs over S7 communication on port 102/tcp, the port named in most of the CPU advisories below.
  • The access levels decide what a client on port 102/tcp can do without a password.
  • CVE-2022-38465 is a key-management flaw that Siemens fixed with both firmware and a new project format.

How do TIA Portal and S7CommPlus reach an S7-1200 or S7-1500 CPU?

An S7-1200 or S7-1500 CPU talks to TIA Portal, HMIs and other PLCs over S7 communication on port 102/tcp, the port named in most of the CPU advisories below. Our S7comm protocol guide covers the wire format, function codes and the difference between classic S7comm and S7CommPlus. The ports a firewall rule has to cover, as the Siemens advisories name them:

Port Use on an S7-1200 or S7-1500 Advisories that name it
102/tcp S7 communication with TIA Portal (PG/PC), HMIs and partner PLCs, including PUT/GET SSA-232418, SSA-434534, SSA-592380, SSA-224824
80/tcp and 443/tcp CPU web server and Web API SSA-224824, SSA-452276, SSA-591731
161/udp SNMP on the CP 1543-1 communication processor SSA-672373
Layer 2, Ethertype 0x8892 PROFINET DCP discovery and configuration SSA-599968

Since TIA Portal V17, the PG/PC and HMI path can run over TLS. Siemens bulletin SSB-898115 says that since TIA Portal V17 and the related CPU firmware, "the PG/PC and HMI communication is protected by TLS V1.3", and that legacy PG/PC and HMI communication is disabled by default in a V17 project but can be switched back on for older HMIs. Siemens' S7-1500 equipment manuals date this "Secure PG/HMI communication" to CPU firmware V2.9 with STEP 7 and WinCC V17. Everything before that, and every project that re-enables the legacy option, relies on the fixed key material behind CVE-2022-38465.

The web server is a second way in. The same equipment manual lists Web API methods for "reading and changing the CPU operating state", and the web server CVEs in the table below run attacker code in a logged-in user's browser and act with that user's rights. The PROFINET interface adds layer-2 denial-of-service paths that the PROFINET guide covers.

What do the access levels and passwords protect?

The access levels decide what a client on port 102/tcp can do without a password. Siemens' application example User Management & Access Control with TIA Portal V19 (V1.0, July 2024) describes the legacy scheme as passwords "for the different access levels in the 'Protection & Security' area of the PLC's properties":

Access level What a client can do without the password
Full access (no protection) Read and change the hardware configuration and blocks, download, run test functions, change RUN/STOP, update firmware
Read access Upload the hardware configuration and blocks; HMI access and diagnostics
HMI access Only HMI access and diagnostics; tags can be read and written from an HMI
No access (complete protection) Nothing without a password; in the V19 configuration, PUT/GET communication is disabled

The same document points out the weakness of the scheme: access protection "was therefore related to groups that had the appropriate passwords - not to individual users", so legacy access control "did not authenticate the user". From TIA Portal V19 and S7-1500 firmware 3.1, User Management and Access Control (UMAC) assigns rights to named users, and Siemens' security-by-default settings for firmware 3.1 include a password for confidential PLC configuration data, only secure PG/PC and HMI communication, and PUT/GET disabled. Legacy access control is disabled by default.

Two CVEs show that a password is only as strong as the way it is stored and checked. CVE-2022-38465 exposes the access-level passwords: SSB-898115 lists them among the confidential configuration data an attacker could extract once the global key is known. CVE-2021-37172, in SSA-830194, affected S7-1200 firmware V4.5.0 only: the CPU failed "to authenticate against configured passwords when provisioned using TIA Portal V13", letting an attacker download arbitrary programs. The fix is V4.5.1.

What is CVE-2022-38465, the hard-coded global private key?

CVE-2022-38465 is a key-management flaw that Siemens fixed with both firmware and a new project format. SSA-568427 says the CPUs "protect the built-in global private key in a way that cannot be considered sufficient any longer" and that an attacker could "discover the private key of a CPU product family by an offline attack against a single CPU of the family". SSB-898115 explains the history: when Siemens introduced asymmetric cryptography with TIA Portal V12 in early 2013, it chose "an approach based on fixed key material" because practical key management for control systems did not exist.

With the key, SSB-898115 describes two attacks. The first extracts confidential configuration data from a TIA Portal project or a CPU memory card: keys and passwords for HTTPS, OPC UA and secure Open User Communication, and the access-level passwords. The second is a man-in-the-middle attack on legacy PG/PC and HMI communication, where an attacker "could read, modify, and selectively forward data". Siemens scores it CVSS v3.1 9.3 with a local attack vector; NVD scores it 7.8. CISA republished it as ICSA-22-286-04.

The fix has three parts, and the third is the one most often missed:

  1. FirmwareS7-1200 V4.5.0 or later; S7-1500 V2.9.2 or later; S7-1500 Software Controller V21.9 or later; S7-PLCSIM Advanced V4.0 or later.
  2. ProjectMigrate the project to TIA Portal V17 or later, update the hardware configuration to the new CPU version and download it. SSB-898115: "an update of the firmware on the device is not sufficient."
  3. ConfigurationSet the CPU to "Only allow secure PG/PC and HMI communication" and set a password for confidential configuration data. Siemens lists no fix for the ET 200SP Open Controller CPU 1515SP PC.

Which CVE families appear in Siemens advisories for S7-1200 and S7-1500?

The table lists the CPU CVEs most likely to come up when an S7-1200 or S7-1500 is matched against Siemens and CISA advisories. Scores are Siemens' CVSS v3.1 from the advisory; fixed versions are from the Siemens CSAF file. Where Siemens fixes several S7-1500 firmware lines, all are listed.

CVE Siemens (CISA) advisory CPUs Issue CVSS v3.1 Fix or main mitigation
CVE-2019-10929 SSA-232418 (ICSA-19-344-06) S7-1200, S7-1500 Integrity protection on 102/tcp can be bypassed by a man in the middle, CWE-327 3.7 S7-1200 V4.4.0; S7-1500 V2.8.1
CVE-2019-10943 SSA-232418 (ICSA-19-344-06) S7-1200, S7-1500, all versions Running code can differ from the source stored on the CPU, CWE-353 5.3 No fix for current firmware; password protection for S7 communication
CVE-2020-15782 SSA-434534 (ICSA-21-152-01) S7-1200, S7-1500 Memory protection bypass over 102/tcp; write data and code to protected memory, CWE-119 8.1 S7-1200 V4.5.0; S7-1500 V2.9.2
CVE-2021-37172 SSA-830194 (ICSA-21-222-09) S7-1200 V4.5.0 Passwords not enforced when provisioned with TIA Portal V13, CWE-287 8.1 V4.5.1
CVE-2022-38465 SSA-568427 (ICSA-22-286-04) S7-1200, S7-1500 Global private key insufficiently protected, CWE-522 9.3 S7-1200 V4.5.0; S7-1500 V2.9.2; plus TIA Portal V17 project
CVE-2022-38773 SSA-482757 S7-1500 No immutable hardware root of trust; boot image can be replaced with physical access, CWE-1326 4.6 No fix for listed CPUs; restrict physical access
CVE-2023-46156 SSA-592380 (ICSA-23-348-09) S7-1500 Crafted packets on 102/tcp cause a denial of service; restart needed, CWE-416 7.5 V3.1.0 (some CPUs V3.1.2); no fix for earlier hardware
CVE-2024-47100 SSA-717113 (ICSA-25-021-02) S7-1200 Web interface CSRF can change the CPU mode, CWE-352 7.1 V4.7
CVE-2024-46887 SSA-054046 S7-1500 Unauthenticated read of cycle-time and communication-load data via the web server, CWE-288 5.3 V2.9.8; V3.1.4
CVE-2025-24811 SSA-224824 (ICSA-25-044-01) S7-1200 Crafted packets on 80/tcp cause an unauthenticated denial of service, CWE-404 7.5 V4.7
CVE-2025-40943 SSA-452276 (ICSA-26-071-04) S7-1500 Crafted trace file runs code in a user's browser session, CWE-95 9.6 V2.9.9; V3.1.6; V4.1.2; no fix for some earlier hardware
CVE-2026-25786 SSA-688146 (ICSA-26-134-15) S7-1500 Stored XSS via the PLC/station name on the web server, CWE-79 9.1 V2.9.9; V3.1.6; V4.1.6; no fix for some earlier hardware
CVE-2026-63350 SSA-591731 (ICSA-26-295-14) S7-1500 Crafted trace file runs JavaScript in a user's browser session, CWE-95 9.6 No fix available; disable the web server or restrict 80/tcp and 443/tcp

Attacks on the S7 communication path

CVE-2019-10929, CVE-2019-10943 and CVE-2020-15782 all sit on port 102/tcp. For CVE-2020-15782, SSA-434534 says a "remote unauthenticated attacker with network access to port 102/tcp could potentially write arbitrary data and code to protected memory areas". Siemens scores it 8.1; NVD scores it 9.8. CVE-2019-10943 is the one with no fix in current firmware: SSA-232418 lists every S7-1200 and S7-1500 version as affected and says an engineer who reads the program back "can receive different source code that is not actually running on the device". The mitigation Siemens gives for all three is password protection for S7 communication.

Denial of service

Several CPU CVEs need no password and stop the controller. For CVE-2023-46156, SSA-592380 says crafted packets to port 102/tcp cause a denial of service, and "a restart is needed to restore normal operations". The fix depends on hardware: current S7-1500 article numbers get V3.1.0, while Siemens lists no fix for 48 earlier article numbers, such as the CPU 1511-1 PN 6ES7511-1AK02-0AB0, and recommends limiting port 102/tcp to trusted systems. For the S7-1200, SSA-224824 fixes CVE-2025-24811, crafted packets to the web server on port 80/tcp, and CVE-2025-24812 on port 102/tcp, in V4.7. PROFINET adds two more: CVE-2019-10936 affects S7-1200 below V4.4.0 and S7-1500 below V2.0, and CVE-2020-28400, a DCP reset flood, affects S7-1200 below V4.5.0.

The web server

The web server is the fastest-growing family. Since 2024, Siemens has published an information leak (SSA-054046), an open redirect (CVE-2024-46886, SSA-876787), a CSRF that can change the S7-1200 CPU mode, and a run of script injections through trace files and names that appear on web pages. In the trace-file cases the attacker has to persuade a user with the "Read diagnostics" right to import a crafted file; SSA-452276 says the code could then "trigger PLC operations via the webserver that the legitimate user is authorized to perform". The October 2026 advisory SSA-591731 adds eight more CVEs, from CVE-2026-63350 to CVE-2026-63357, and as of its first version (13 October 2026) Siemens lists no fix for any affected product. Its first mitigation: "Disable the webserver if not required on the affected systems."

Hardware and modules

CVE-2022-38773 in SSA-482757 is different in kind: the S7-1500 has no immutable root of trust in hardware, so "an attacker with physical access to the device could use this to replace the boot image". Siemens lists no fix and recommends restricting physical access. Communication processors carry their own CVEs: the S7-1500 CP 1543-1 has the only KEV entry in this family, CVE-2016-8562, covered in the next section.

How do you read the firmware version and match it to a fix?

Siemens writes S7 fixes against an article number and a firmware line, so the inventory needs both. In recent CSAF files the product names are article-number level, such as "SIMATIC S7-1500 CPU 1511-1 PN (6ES7511-1AK01-0AB0)" with a version range like "<2.9.8".

  1. Read the CPUSiemens' S7-1500 equipment manuals say the CPU display "provides information on order numbers, firmware version and serial numbers of all connected modules". TIA Portal's online diagnostics shows the same for a connected CPU, and the hardware configuration in the project records the version that was configured.
  2. Identify the firmware lineS7-1500 fixes come in parallel lines: CVE-2025-40943 is fixed in V2.9.9 for older article numbers, and in V3.1.6 or V4.1.2 for others. A CPU on V3.1.5 needs V3.1.6 or later, not V2.9.9. The S7-1200 has a single V4.x line, with V4.7 as the current fix level for SSA-224824 and SSA-717113.
  3. Check for hardware with no fixCVE-2023-46156, CVE-2025-40943 and CVE-2026-25786 list earlier article numbers with no fix at all. For those CPUs, the mitigation is the network, or replacement hardware.
  4. Record the TIA Portal version and project settingsCVE-2022-38465 is closed only if the project is V17 or later and legacy PG/PC and HMI communication is off; CVE-2021-37172 depends on the TIA Portal version used for provisioning.

A passive capture helps with which hosts talk to the PLCs, not with versions. CISA's ICSNPP-S7COMM Zeek parser logs S7comm, S7comm-plus and COTP, including the IDs of system status list (SZL) reads in s7comm_read_szl.log; it does not log a firmware version field.

NVD data for these CVEs is uneven. As of 2026-11-19, NVD has its own (Primary) score for the older CVEs, while CVE-2023-46156 carries only the Siemens score, CVE-2024-46887, CVE-2024-47100 and CVE-2025-24811 are Deferred, and CVE-2025-40943, CVE-2026-25786 and CVE-2026-63350 are Awaiting Analysis. A CPE-only scanner misses most of the newer entries, so match against the Siemens or CISA CSAF product tree as well.

How should KEV and EPSS weigh on S7-1200 and S7-1500 findings?

As of 2026-11-19, the CISA KEV catalog (version 2026.11.18, 1,786 entries) has no S7-1200 or S7-1500 CPU entry. Its two Siemens entries are a Siemens Software Center flaw and CVE-2016-8562, the S7-1500 communication processor CP 1543-1, added on 2022-03-03. SSA-672373 says SNMP variables on port 161/udp "which should be read-only" could be written, which "could reduce the availability or cause a denial-of-service"; the fix is CP 1543-1 V2.0.28. Siemens scores it 5.3, NVD 7.5.

The latest FIRST EPSS scores, dated 2026-11-18, were:

CVE EPSS Percentile
CVE-2020-15782 0.052 0.926
CVE-2016-8562 0.036 0.897
CVE-2019-10936 0.021 0.818
CVE-2020-28400 0.019 0.796
CVE-2023-46156 0.012 0.699
CVE-2019-10929 0.010 0.629
CVE-2019-10943 0.010 0.620
CVE-2021-37172 0.009 0.610
CVE-2025-24811 0.006 0.514
CVE-2025-40943 0.005 0.465
CVE-2026-25786 0.004 0.315
CVE-2026-63350 0.003 0.273
CVE-2022-38465 0.002 0.154

EPSS is low across the family, so rank by reachability and consequence. A CPU whose port 102/tcp or web server is reachable from outside its cell comes first, then unauthenticated denial of service on a running line, then the key and password issues that let one stolen project unlock others. Our KEV and EPSS prioritization guide explains the method.

How do you harden an S7-1200 or S7-1500 per Siemens guidance?

The steps below are the ones Siemens gives in the advisories above and in its Operational Guidelines (Version 2.2.1, April 2024), in the order that covers the most CVEs.

  1. Update firmware and the project togetherApply the fixed version for each CPU's article number and firmware line, then migrate the project to TIA Portal V17 or later and download it. SSB-898115 is explicit that firmware alone does not close CVE-2022-38465. See our IEC 62443-2-3 patch management guide for scheduling updates on a running plant.
  2. Allow only secure PG/PC and HMI communicationLeave legacy communication off unless an HMI below V17 still needs it, and set a password for confidential configuration data.
  3. Set access protectionUse the strongest access level the HMIs allow, or UMAC with named users from TIA Portal V19 and S7-1500 firmware 3.1. SSA-434534 and SSA-232418 both list "password protection for S7 communication" as the mitigation, and SSA-434534 adds the ENDIS_PW instruction or the S7-1500 display, which block remote client connections "even when the client can provide the correct password".
  4. Leave PUT/GET offIt reopens classic, unauthenticated S7comm on the same CPU, as the S7comm guide explains.
  5. Disable the web server where it is not usedSSA-452276 and SSA-591731 give this as the first mitigation, with access to 80/tcp and 443/tcp restricted to trusted systems where it is needed. Limit the "Read diagnostics" and "firmware update" rights to trained staff, and import only trusted trace files.
  6. Segment the cellThe Operational Guidelines describe a "cell protection concept" that segments production into protected cells, separates production and office networks, and routes access through a demilitarized zone. Restrict 102/tcp to the HMIs and engineering stations that need it, as SSA-592380 advises; the Purdue model guide shows the zone layout.
  7. Deactivate unused interfaces and change default passwordsThe Operational Guidelines list unused USB and Ethernet/PROFINET ports among the interfaces to deactivate, and say that predefined default passwords "must be changed during system commissioning". Where PROFINET is optional and unused, SSA-599968 recommends disabling it.
  8. Protect the project files and memory cardsSSA-568427 tells users to protect access to the TIA Portal project and the CPU, including memory cards, and SSA-482757 adds physical access control.

What does an S7 triage of one machine line look like? (worked example)

Synthetic example. The line, article numbers in use and firmware versions are invented for illustration; the CVEs and fixed versions come from the Siemens advisories above.

A filling line has an S7-1500 CPU 1511-1 PN (6ES7511-1AK02-0AB0) on V2.8.3 with its web server enabled, an S7-1200 CPU on V4.4.0 in a separate cell, and a TIA Portal V16 project.

Device Finding Action
S7-1500 CPU 1511-1 PN, 6ES7511-1AK02-0AB0, V2.8.3 Below V2.9.2 (CVE-2020-15782, CVE-2022-38465); article number listed with no fix for CVE-2023-46156; web server CVEs apply Update to the current V2.9.x release; migrate to TIA Portal V17 or later and allow only secure PG/PC and HMI communication; disable the web server; plan replacement hardware for CVE-2023-46156
S7-1200 CPU, V4.4.0 Below V4.5.0 (CVE-2020-15782, CVE-2022-38465, CVE-2020-28400) and V4.7 (CVE-2024-47100, CVE-2025-24811) Update to V4.7 or later, skipping V4.5.0 (CVE-2021-37172); set access protection
TIA Portal V16 project Legacy PG/PC and HMI communication only; confidential data protected by the global key Migrate the project and download it to both CPUs

What are the common pitfalls?

  • Updating firmware but not the project. CVE-2022-38465 stays open until a V17 or later project is downloaded with legacy communication off.
  • Matching on family instead of article number. SSA-592380 fixes some S7-1500 CPUs and leaves earlier hardware of the same model without a fix.
  • Leaving the web server on because it was on. It carries more CVEs than any other S7-1500 function, and SSA-591731 has no fix.
  • Treating access-level passwords as user authentication. They are shared group passwords, and CVE-2022-38465 lets an attacker extract them from a project.
  • Trusting what the engineering station reads back. CVE-2019-10943 means the uploaded source may not be what runs.
  • Relying on NVD CPE matching. As of 2026-11-19, the newer CVEs have no NVD analysis.

For other controller families, see the Rockwell Logix guide and the CODESYS runtime guide, and map attacker techniques with MITRE ATT&CK for ICS.

AI-assisted analysis: what SoftWSP actually runs

SoftWSP identifies components and versions from a firmware image or a component list, and matches them against NVD, CISA KEV, FIRST EPSS and CISA's ICS advisories with deterministic code. AI then writes the plain-language summary, citing the component, version and record behind each finding, and an engineer reviews every report before it is sent.

For an S7 system, the useful input is each CPU's article number and firmware version, each communication processor, and the TIA Portal version. The OT Snapshot reads Zeek and ICSNPP logs from a mirror-port capture at connection level: which hosts talk S7comm or S7comm-plus to which PLCs, on which ports, and which remote-access sessions exist. It does not read the PLC's firmware, access level, web server setting or project, so those come from the asset list and TIA Portal and are judged in the engineer review. For a whole machine line, see the machine builder report.

This guide draws on Siemens ProductCERT advisories SSA-232418, SSA-434534, SSA-830194, SSA-568427, SSA-482757, SSA-592380, SSA-717113, SSA-054046, SSA-876787, SSA-224824, SSA-452276, SSA-688146, SSA-591731, SSA-473245, SSA-599968 and SSA-672373 and bulletin SSB-898115 with their CSAF files, CISA ICS advisories, Siemens' Operational Guidelines 2.2.1, the UMAC application example for TIA Portal V19, an S7-1500 equipment manual, NVD records, CISA's ICSNPP-S7COMM documentation, CISA's KEV catalog version 2026.11.18 and FIRST EPSS data dated 2026-11-18, all read on 2026-11-19.

Put this guide to work

Frequently asked questions

Is any S7-1200 or S7-1500 CPU vulnerability in CISA's KEV catalog?

No CPU entry, but one module entry. As of 2026-11-19, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.18, 1,786 entries) has two Siemens entries, and neither names an S7-1200 or S7-1500 CPU. One of them, CVE-2016-8562, is the SIMATIC CP 1543-1, a communication processor for the S7-1500. Siemens advisory SSA-672373 says SNMP variables on port 161/udp that should be read-only could be written, which could cause a denial of service; the fix is CP 1543-1 firmware V2.0.28. CISA added it to KEV on 2022-03-03. For the CPUs themselves, rank findings by reachability of port 102/tcp and the web server, then by score.

What is CVE-2022-38465, the S7-1200 and S7-1500 global private key issue?

Siemens advisory SSA-568427 (11 October 2022) says S7-1200 and S7-1500 CPUs protect a built-in global private key in a way that "cannot be considered sufficient any longer". An attacker who recovers the key by an offline attack on a single CPU of a family can extract confidential configuration data from projects protected by that key, including access-level passwords, or attack legacy PG/PC and HMI communication. Siemens scores it CVSS v3.1 9.3; NVD scores it 7.8. The fix is S7-1200 firmware V4.5.0 or S7-1500 V2.9.2 or later together with a TIA Portal V17 or later project that is migrated and downloaded again. Siemens bulletin SSB-898115 stresses that a firmware update alone is not sufficient.

What are the access levels on an S7-1200 or S7-1500 CPU?

The CPU's legacy access control has four levels, set by password in the Protection & Security area of the CPU properties in TIA Portal: Full access (no protection), Read access, HMI access, and No access (complete protection). Siemens' application example for TIA Portal V19 describes HMI access as allowing only HMI access and diagnostics, and Read access as allowing an upload of the hardware configuration and blocks without a password. From TIA Portal V19 and S7-1500 firmware 3.1, User Management and Access Control (UMAC) replaces the shared passwords with named users, and legacy access control is disabled by default. When legacy access is set to No access (complete protection), PUT/GET communication is disabled.

How do I find the firmware version of an S7-1500 or S7-1200 CPU?

Read the article number (6ES7...) and the firmware version together, because Siemens writes fixes per article number and firmware line. Siemens' S7-1500 equipment manuals say the CPU display shows the order numbers, firmware version and serial number of all connected modules; TIA Portal's online diagnostics shows the same values for a connected CPU. Compare the result with the Siemens advisory: for CVE-2023-46156, SSA-592380 fixes many S7-1500 CPUs in V3.1.0 but lists no fix for earlier hardware such as the CPU 1511-1 PN 6ES7511-1AK02-0AB0. A passive network capture can show which hosts talk S7comm or S7CommPlus to the CPU, but it does not give you the firmware version.

Can SoftWSP tell me whether my S7 controllers are affected?

SoftWSP matches the components and versions it is given against NVD, CISA KEV, FIRST EPSS and CISA's ICS advisories, and AI writes a summary that cites the record behind each finding; an engineer reviews it before delivery. For an S7 system the useful input is each CPU's article number and firmware version, each communication processor, and the TIA Portal version. Its passive OT Snapshot reads Zeek and ICSNPP logs at connection level, which shows which hosts reach the PLCs on port 102/tcp; it does not read the PLC's firmware, access level or project, so those come from the asset list or TIA Portal.

Sources

  1. Siemens ProductCERT SSA-568427: Weak Key Protection Vulnerability in SIMATIC S7-1200 and S7-1500 CPU Families (CVE-2022-38465)
  2. Siemens ProductCERT SSB-898115: Remarks Regarding SSA-568427 (11 October 2022)
  3. Siemens ProductCERT SSA-434534: Memory Protection Bypass Vulnerability in SIMATIC S7-1200 and S7-1500 CPU Families (CVE-2020-15782)
  4. Siemens ProductCERT SSA-232418: Vulnerabilities in SIMATIC S7-1200 and SIMATIC S7-1500 CPU Families (CVE-2019-10929, CVE-2019-10943)
  5. Siemens ProductCERT SSA-830194: Missing Authentication Vulnerability in S7-1200 Devices (CVE-2021-37172)
  6. Siemens ProductCERT SSA-592380: Denial of Service Vulnerability in SIMATIC S7-1500 CPUs and related products (CVE-2023-46156)
  7. Siemens ProductCERT SSA-224824: Denial of Service Vulnerabilities in SIMATIC S7-1200 CPU Family Before V4.7 (CVE-2025-24811, CVE-2025-24812)
  8. Siemens ProductCERT SSA-717113: Cross-Site Request Forgery (CSRF) Vulnerability in SIMATIC S7-1200 CPUs before V4.7 (CVE-2024-47100)
  9. Siemens ProductCERT SSA-054046: Unauthenticated Information Disclosure in Web Server of SIMATIC S7-1500 CPUs (CVE-2024-46887)
  10. Siemens ProductCERT SSA-876787: Open Redirect Vulnerability in SIMATIC S7-1500 and S7-1200 CPUs (CVE-2024-46886)
  11. Siemens ProductCERT SSA-452276: Eval Injection Vulnerability in SIMATIC S7-1500 (CVE-2025-40943)
  12. Siemens ProductCERT SSA-688146: Multiple Cross-Site Scripting Vulnerabilities in SIMATIC S7 PLCs Web Server (CVE-2026-25786, CVE-2026-25787, CVE-2026-25789)
  13. Siemens ProductCERT SSA-591731: Multiple Vulnerabilities in SIMATIC S7 PLCs Web Server (CVE-2026-63350 to CVE-2026-63357)
  14. Siemens ProductCERT SSA-482757: Missing Immutable Root of Trust in S7-1500 CPU devices (CVE-2022-38773)
  15. Siemens ProductCERT SSA-473245: Denial of Service Vulnerability in Profinet Devices (CVE-2019-10936)
  16. Siemens ProductCERT SSA-599968: Denial of Service Vulnerability in Profinet Devices (CVE-2020-28400)
  17. Siemens ProductCERT SSA-672373: Vulnerabilities in CP 1543-1 before V2.0.28 (CVE-2016-8562)
  18. Siemens: Cybersecurity for Industry, Operational Guidelines, Version 2.2.1 (April 2024)
  19. Siemens Industry Online Support: User Management & Access Control with TIA Portal V19, application example 109973173, V1.0 (07/2024)
  20. CISA CSAF: ICSA-22-286-04 Siemens SIMATIC S7-1200 and S7-1500 CPU Families (CVE-2022-38465)
  21. CISA CSAF: ICSA-21-152-01 Siemens SIMATIC S7-1200 and S7-1500 CPU Families (Update A), CVE-2020-15782
  22. CISA CSAF: ICSA-23-348-09 Siemens SIMATIC S7-1500 CPU family, CVE-2023-46156
  23. CISA CSAF: ICSA-25-044-01 Siemens SIMATIC S7-1200 CPU Family, CVE-2025-24811 and CVE-2025-24812
  24. CISA CSAF: ICSA-26-295-14 Siemens SIMATIC S7 PLCs Web Server (CVE-2026-63350 to CVE-2026-63357)
  25. NVD: CVE-2022-38465
  26. NVD: CVE-2020-15782
  27. NVD: CVE-2016-8562
  28. CISA ICSNPP-S7COMM: Zeek parser for S7comm, S7comm-plus and COTP
  29. CISA Known Exploited Vulnerabilities catalog
  30. FIRST: Exploit Prediction Scoring System (EPSS)
Was this guide helpful?

In this cluster

Sparkplug B protocol security: what MQTT's SCADA layer protects, and what it doesn'tSparkplug B's own specification calls its security chapter 'guidance only' and 'non-normative' — authentication, encryption and access control are left entirely to the MQTT broker. What that means for Birth/Death certificates, sequence numbers, a real Ignition vulnerability, and the AI analytics increasingly built on top of Sparkplug data.TriStation protocol security: the protocol TRITON/TRISIS exploitedTriStation is the proprietary protocol Schneider Electric's Triconex safety controllers speak with no built-in authentication. What CISA's HatMan report and the 2017 TRITON/TRISIS attack actually found, and the keyswitch and network controls that remain the only defense.TSA Pipeline Security Directives: what covered operators must doWhat TSA's two pipeline cybersecurity directive series actually require: 24/7 coordinators and incident reporting under SD-01, and the Cybersecurity Implementation/Incident Response/Assessment Plans under SD-02C, SD-02D and SD-02E, with effective dates.UDS (ISO 14229) security: the protocol that can reflash an ECU, and what guards itUDS — ISO 14229, run over ISO 15765-2 CAN transport — is the service set a dealer tool uses to read trouble codes and reflash ECU firmware. Its SecurityAccess (0x27) seed-key gate has a documented history of weak OEM implementations. What the Jeep Cherokee research actually found about it, what a 2024 academic paper demonstrated on a real truck, and what NHTSA recommends.