CVE-2019-10929 is a weakness in the integrity protection of S7 traffic on port 102/tcp: an attacker in a man-in-the-middle position could modify traffic to Siemens S7-1200 and S7-1500 CPUs and related products. NVD scores it 5.9; Siemens scores it 3.7 (CWE-327). Siemens fixes the CPUs in S7-1200 V4.4.0 and S7-1500 V2.8.1.
Vulnerability summary
CVSS base score
5.9
Medium severity
EPSS score (FIRST)
1.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-10929 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| SIMATIC S7-1200 CPU family (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-1200_cpu_1214c_firmware:*:*:*:*:*:*:*:* | All versions before V4.4.0; fixed in V4.4.0 (Siemens SSA-232418). NVD's CPE ends at 4.0 inclusive |
| SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-1500_cpu_1511c_firmware:*:*:*:*:*:*:*:* | All versions before V2.8.1; fixed in V2.8.1 (Siemens SSA-232418). NVD's CPE has no version limit |
| SIMATIC S7-1500 Software Controller; SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_et_200sp_open_controller_cpu_1515sp_pc2_firmware:*:*:*:*:*:*:*:* | All versions before V20.8; fixed in V20.8 (Siemens SSA-232418) |
| SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_et_200sp_open_controller_cpu_1515sp_pc_firmware:*:*:*:*:*:*:*:* | All versions; no fix as of 2026-11-19 (Siemens SSA-232418) |
| SIMATIC S7-PLCSIM Advanced | cpe:2.3:a:siemens:simatic_s7-plcsim_advanced:*:*:*:*:*:*:*:* | All versions before V3.0; fixed in V3.0 (Siemens SSA-232418) |
| SIMATIC STEP 7, WinCC, WinCC Runtime Advanced and WinCC Runtime Professional (TIA Portal) | cpe:2.3:a:siemens:simatic_step_7:*:*:*:*:*:*:*:* | All versions before V16; fixed in V16 (Siemens SSA-273799) |
| SIMATIC WinCC OA | cpe:2.3:a:siemens:simatic_wincc_open_architecture:*:*:*:*:*:*:*:* | All versions before V3.16 P013; fixed in V3.16 P013 (Siemens SSA-273799) |
| SIMATIC NET PC Software V14 and V15 | cpe:2.3:a:siemens:simatic_net_pc:*:*:*:*:*:*:*:* | V14 before V14 SP1 Update 14 (fixed in V14 SP1 Update 14); V15 all versions, no fix as of 2026-11-19 (Siemens SSA-273799) |
| TIM 1531 IRC (incl. SIPLUS NET variants) | cpe:2.3:o:siemens:simatic_tim_1531_irc_firmware:*:*:*:*:*:*:*:* | All versions before V2.1; fixed in V2.1 (Siemens SSA-273799) |
| SIMATIC CP 1626 (6GK1162-6AA01) and SIMATIC HMI Panel (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_hmi_panel_firmware:*:*:*:*:*:*:*:* | All versions; no fix as of 2026-11-19 (Siemens SSA-273799) |
What does this mean for affected devices?
NVD carries the Siemens description: affected devices "contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices." NVD's Primary score is CVSS v3.1 5.9 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N) with the placeholder NVD-CWE-Other; the Siemens CNA classes it CWE-327 (use of a broken or risky cryptographic algorithm). The record was published on 2019-08-13 (NVD, CVE record).
How severe is it, and why do the scores differ?
Siemens ProductCERT scores CVE-2019-10929 at CVSS v3.1 3.7 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:L/A:N/E:U/RL:O/RC:C) in both SSA-232418 and SSA-273799. NVD rates the integrity impact high instead of low, which lifts the base score to 5.9. Both agree that the attacker has to sit in the path between engineering station or HMI and the CPU, which is why attack complexity is high. CISA's ICSA-19-344-06 and ICSA-19-344-04 CSAF files use 3.7.
What does a man in the middle gain on 102/tcp?
Port 102/tcp carries S7 communication between TIA Portal, HMIs and the CPU. Because of a weakness in the calculation that protects message integrity, an attacker who can intercept that traffic could modify it in transit. SSA-232418 credits researchers from the Technion and Tel Aviv University. Claroty Team82 links SSA-232418 to the Rogue7 research, in which a rogue engineering station masqueraded as TIA Portal and injected messages, and says Siemens "partially resolved this issue and provided mitigations".
Which products and versions are affected?
| Product (Siemens wording) | Affected | Fixed |
|---|---|---|
| SIMATIC S7-1200 CPU family (incl. SIPLUS) | before V4.4.0 | V4.4.0 |
| SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS) | before V2.8.1 | V2.8.1 |
| SIMATIC S7-1500 Software Controller; ET 200SP Open Controller CPU 1515SP PC2 | before V20.8 | V20.8 |
| SIMATIC ET 200SP Open Controller CPU 1515SP PC | all versions | no fix |
| SIMATIC S7-PLCSIM Advanced | before V3.0 | V3.0 |
| STEP 7, WinCC, WinCC Runtime Advanced and Professional (TIA Portal) | before V16 | V16 |
| SIMATIC WinCC OA | before V3.16 P013 | V3.16 P013 |
| SIMATIC NET PC Software V14 | before V14 SP1 Update 14 | V14 SP1 Update 14 |
| TIM 1531 IRC (incl. SIPLUS NET) | before V2.1 | V2.1 |
| SIMATIC CP 1626, SIMATIC HMI Panel (incl. SIPLUS), NET PC Software V15 | all versions | no fix |
The CPU rows come from SSA-232418 V1.4 (2022-08-09), the rest from SSA-273799 V1.3 (2022-04-12). NVD's CPE for the S7-1200 stops at firmware 4.0 inclusive, so it misses V4.1 to V4.3.x, and it lists S7-1500 CPU 1511C, 1512C and 1518 firmware without a version limit.
How do you fix or mitigate it?
Update both ends of the link: CPU firmware and the TIA Portal, WinCC or NET PC software that talks to it. For the CPU 1515SP PC, which has no fix, SSA-232418 lists password protection for S7 communication; for CP 1626, HMI Panels and NET PC Software V15, SSA-273799 gives only the general advice to protect network access. Either way, keep 102/tcp inside the cell so nobody can get into the path. Our S7comm security guide, the S7-1200/S7-1500 vulnerability guide and the weak cryptography fix guide cover this. SSA-232418 also lists CVE-2019-10943; CVE-2020-15782 uses the same port, and CVE-2019-10936 is a PROFINET flaw in S7-1500 CPUs.
CVE-2019-10929 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.00978, the 62.9th percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-19): status Modified; published 2019-08-13; NVD Primary CVSS v3.1 5.9 CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N, v2 4.3; CWE NVD-CWE-Other (NVD), CWE-327 (Siemens); CPE: S7-1200 CPU 1211C to 1217C firmware up to and including 4.0, S7-1500 CPU 1511C/1512C/1518 firmware without version limit, STEP 7 and WinCC before 16, NET PC before 16, TIM 1531 IRC before 2.1; references SSA-232418, SSA-273799, ICSA-19-344-04. — NVD
- Siemens SSA-232418 V1.4 (published 2019-08-13, updated 2022-08-09), read 2026-11-19: CVE-2019-10929 message protection bypass on 102/tcp by a man in the middle; CVSS v3.1 3.7 CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:L/A:N/E:U/RL:O/RC:C; CWE-327; fixes S7-1200 V4.4.0, S7-1500 V2.8.1, S7-1500 Software Controller and CPU 1515SP PC2 V20.8, S7-PLCSIM Advanced V3.0; CPU 1515SP PC all versions with no fix; mitigation password protection for S7 communication; credits Technion and Tel Aviv University researchers. — Siemens ProductCERT SSA-232418
- Siemens SSA-273799 V1.3 (published 2019-12-10, updated 2022-04-12), read 2026-11-19: CVE-2019-10929, CVSS v3.1 3.7, CWE-327; CP 1626, HMI Panel and NET PC Software V15 all versions with no fix; NET PC Software V14 fixed in V14 SP1 Update 14; STEP 7, WinCC, WinCC Runtime Advanced/Professional (TIA Portal) fixed in V16; WinCC OA fixed in V3.16 P013; TIM 1531 IRC fixed in V2.1. — Siemens ProductCERT SSA-273799
- CISA ICSA-19-344-06 CSAF (Update B, 2020-03-10), read 2026-11-19: CVE-2019-10929 CWE-327, CVSS v3.0 3.7, S7-1200/S7-1500 CPU families and related products. — CISA CSAF ICSA-19-344-06
- CISA ICSA-19-344-04 CSAF (Update C, current release 2025-05-06), read 2026-11-19: CVE-2019-10929 CWE-327, CVSS v3.1 3.7; product list and fixes match SSA-273799. — CISA CSAF ICSA-19-344-04
- Claroty Team82, read 2026-11-19: describes the Rogue7 attack (rogue engineering station masquerading as TIA Portal and injecting messages) and states Siemens partially resolved it and provided mitigations, as documented in SSA-232418. — Claroty Team82
- CVE record (checked 2026-11-19): state PUBLISHED, CNA Siemens, published 2019-08-13; CNA CWE-327, no CNA CVSS metric; references SSA-232418, SSA-273799, ICSA-19-344-04. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-19. — CISA KEV
- EPSS 0.00978, percentile 0.62861, dataset 2026-11-18, read 2026-11-19. — FIRST EPSS

Related advisories
Sources
- NVD
- Siemens ProductCERT SSA-232418: Vulnerabilities in SIMATIC S7-1200 and SIMATIC S7-1500 CPU Families
- Siemens ProductCERT SSA-273799: Message Integrity Protection Bypass Vulnerability in SIMATIC Products
- CISA CSAF: ICSA-19-344-06 Siemens SIMATIC S7-1200 and S7-1500 CPU Families (machine-readable advisory)
- CISA CSAF: ICSA-19-344-04 Siemens SIMATIC Products (machine-readable advisory)
- Claroty Team82: The Race to Native Code Execution in PLCs (Rogue7 and SSA-232418 background)
- CVE.org record CVE-2019-10929 (CNA: Siemens)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Which firmware fixes CVE-2019-10929 on S7 CPUs?
S7-1200 CPU family V4.4.0, S7-1500 CPU family V2.8.1, S7-1500 Software Controller and ET 200SP Open Controller CPU 1515SP PC2 V20.8, and S7-PLCSIM Advanced V3.0. The CPU 1515SP PC has no fix as of 2026-11-19 (per Siemens SSA-232418).
Is updating the CPU enough?
No. The flaw also affects the software at the other end of the link: STEP 7, WinCC and WinCC Runtime (TIA Portal) before V16, WinCC OA before V3.16 P013, NET PC Software and TIM 1531 IRC. CP 1626, HMI Panels and NET PC Software V15 have no fix (per Siemens SSA-273799).
Why is the Siemens score lower than the NVD score?
Siemens rates the integrity impact low and scores 3.7; NVD rates it high and scores 5.9. Both rate attack complexity high because the attacker must be in a man-in-the-middle position on 102/tcp (per NVD and Siemens SSA-232418).
How do I reduce the risk where no fix exists?
For the CPU 1515SP PC, apply password protection for S7 communication (per Siemens SSA-232418). For CP 1626, HMI Panels and NET PC Software V15, Siemens SSA-273799 gives only the general recommendation to protect network access. In both cases keep port 102/tcp traffic inside a protected cell so that no untrusted host can sit between the engineering station or HMI and the CPU.
Questions about this page?