CVE-2022-38773 is a hardware design flaw in Siemens SIMATIC S7-1500 CPUs: they have no immutable root of trust in hardware, so the integrity of the code cannot be checked at boot, and an attacker with physical access could replace the boot image and run arbitrary code. NVD scores it 6.8, Siemens 4.6 (CWE-1326). Firmware does not fix it; new hardware versions do.
Vulnerability summary
CVSS base score
6.8
Medium severity
EPSS score (FIRST)
0.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-38773 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| SIMATIC S7-1500 CPUs (1510SP to 1518, incl. F, T, TF, R, H, MFP and ODK variants), ET 200pro CPUs 1513PRO/1516PRO and SIPLUS variants: listed article numbers | cpe:2.3:o:siemens:simatic_s7-1500_cpu_1511-1_pn_firmware:-:*:*:*:*:*:*:* | All versions of the listed hardware article numbers (for example 6ES7511-1AK02-0AB0); no fix for these, mitigation only (Siemens SSA-482757) |
| SIMATIC Drive Controller CPU 1504D TF (6ES7615-4DF10-0AB0) and CPU 1507D TF (6ES7615-7DF10-0AB0) | cpe:2.3:o:siemens:simatic_drive_controller_cpu_1504d_tf_firmware:-:*:*:*:*:*:*:* | All versions; no fix, mitigation only (Siemens SSA-482757) |
| New S7-1500 hardware versions with secure boot (for example CPU 1511-1 PN 6ES7511-1AL03-0AB0, CPU 1516-3 PN/DP 6ES7516-3AP03-0AB0, CPU 1518-3 PN 6ES7518-3AT10-0AB0) | — | Not affected: Siemens lists 38 new hardware article numbers that contain a secure boot mechanism resolving the flaw (SSA-482757, Additional Information) |
What does this mean for affected devices?
NVD carries the Siemens description: "Affected devices do not contain an Immutable Root of Trust in Hardware. With this the integrity of the code executed on the device can not be validated during load-time. An attacker with physical access to the device could use this to replace the boot image of the device and execute arbitrary code." NVD's Primary score is CVSS v3.1 6.8 (CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) with the placeholder NVD-CWE-Other; the Siemens CNA classes it CWE-1326 (missing immutable root of trust in hardware). The record was published on 2023-01-10 (NVD, CVE record).
Why do NVD and Siemens score it differently?
Siemens ProductCERT scores CVE-2022-38773 at CVSS v3.1 4.6 (CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N/E:P/RL:T/RC:C) in SSA-482757 and in the CVE record. Both agree that the attacker needs physical access. Siemens counts only the integrity impact; NVD rates confidentiality, integrity and availability all high, in line with the description's outcome that the attacker could "execute arbitrary code". CISA's ICSA-23-012-08 (last updated 2025-01-14) repeats the Siemens 4.6.
Which CPUs are affected, and is there a fix?
The flaw is in the hardware, so no firmware update removes it. SSA-482757 lists 123 affected entries: S7-1500 CPUs from the 1510SP-1 PN to the 1518-4 PN/DP (including F, T, TF, R, H, MFP and ODK models), the ET 200pro CPUs 1513PRO and 1516PRO, the Drive Controller CPU 1504D TF and 1507D TF, and SIPLUS variants such as SIPLUS ET 200SP, each by hardware article number. For all of them Siemens states that it currently intends no fix.
Instead, Siemens has released new hardware versions "that contain a new secure boot mechanism that resolves the vulnerability". The advisory names 38 of them. For some CPU types, the old and the new article number side by side:
| CPU | Affected article number (example) | New hardware version with secure boot |
|---|---|---|
| CPU 1511-1 PN | 6ES7511-1AK02-0AB0 | 6ES7511-1AL03-0AB0 |
| CPU 1513-1 PN | 6ES7513-1AL02-0AB0 | 6ES7513-1AM03-0AB0 |
| CPU 1515-2 PN | 6ES7515-2AM02-0AB0 | 6ES7515-2AN03-0AB0 |
| CPU 1516-3 PN/DP | 6ES7516-3AN02-0AB0 | 6ES7516-3AP03-0AB0 |
Siemens says it is working on new hardware versions for the remaining PLC types. The advisory was published on 2023-01-10 and updated five times up to 2025-01-14, each time adding new hardware versions. NVD's CPE entries name 70 CPU firmware products with the version - (no version), so a CPE match cannot tell old and new hardware apart; compare the hardware article number with the lists in SSA-482757.
How do you mitigate it?
Siemens' mitigation is to restrict physical access to trusted personnel, for example by placing the devices in locked control cabinets. When you plan replacements, order the new article numbers. The same S7-1500 family has network-reachable flaws that matter more for most plants, such as the program integrity issue CVE-2019-10943 and the global private key CVE-2022-38465. Our S7-1200/S7-1500 vulnerability guide covers the whole family.
CVE-2022-38773 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00305, the 23.9th percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-21): status Modified; published 2023-01-10; NVD Primary CVSS v3.1 6.8 CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; Siemens Secondary 4.6; CWE NVD-CWE-Other (NVD), CWE-1326 (Siemens); 70 CPE entries for S7-1500, ET 200SP, Drive Controller and SIPLUS CPU firmware, version "-". — NVD
- Siemens SSA-482757 V1.5 (published 2023-01-10, updated 2025-01-14), CSAF and HTML read 2026-11-21: CVE-2022-38773 missing immutable root of trust in hardware, CWE-1326, CVSS v3.1 4.6 CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N/E:P/RL:T/RC:C; 123 affected entries by article number; remediation: no fix intended for the listed products; mitigation: restrict physical access, e.g. locked control cabinets; Additional Information lists 38 new hardware versions with a new secure boot mechanism that resolves the vulnerability; Siemens working on new hardware for remaining PLC types. — Siemens ProductCERT SSA-482757
- CISA ICSA-23-012-08 CSAF (current release 2025-01-14), read 2026-11-21: CVE-2022-38773 CWE-1326, CVSS v3.1 4.6; Siemens S7-1500 CPU devices. — CISA CSAF ICSA-23-012-08
- CVE record (checked 2026-11-21): state PUBLISHED, CNA Siemens, published 2023-01-10; CNA CVSS v3.1 4.6, CWE-1326. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21. — CISA KEV
- EPSS 0.00305, percentile 0.23905, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Can a firmware update fix CVE-2022-38773?
No. Siemens describes it as a hardware flaw and states for all listed article numbers that no fix is intended. It is resolved only in new hardware versions with a secure boot mechanism, such as CPU 1511-1 PN 6ES7511-1AL03-0AB0 (per Siemens SSA-482757).
How do I know whether my CPU is affected?
Compare the hardware article number of the CPU with the lists in SSA-482757: the affected list has 123 entries and the Additional Information section names 38 new article numbers with secure boot. NVD's CPE data does not separate hardware versions.
Can it be exploited over the network?
Siemens and NVD both score the attack vector as physical: the attacker needs physical access to the device to replace the boot image. Siemens recommends restricting physical access to trusted personnel, for example with locked control cabinets.
Why is the NVD score higher than the Siemens score?
Siemens rates only the integrity impact (4.6); NVD also rates confidentiality and availability high (6.8). Both scores assume physical access; the Siemens description says the attacker could execute arbitrary code.
Questions about this page?