Security Advisory

CVE-2021-37172: S7-1200 V4.5.0 Password Bypass

Last updated:
  • CVE-2021-37172

CVE-2021-37172 is an authentication flaw in Siemens SIMATIC S7-1200 CPUs on firmware V4.5.0: if the CPU was provisioned with TIA Portal V13, it does not check the configured passwords, so an attacker can download arbitrary programs to the PLC. NVD scores it 7.5, Siemens 8.1. Siemens fixes it in firmware V4.5.1.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

0.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2021-37172 · Source: NVD

Affected components

ComponentCPEVersion range
Siemens SIMATIC S7-1200 CPU family (incl. SIPLUS variants)cpe:2.3:o:siemens:simatic_s7-1200_cpu_firmware:4.5.0:*:*:*:*:*:*:*V4.5.0 only; fixed in V4.5.1 (Siemens SSA-830194)
Siemens SIMATIC STEP 7 (TIA Portal) V13 used for provisioningcpe:2.3:a:siemens:simatic_step_7_\(tia_portal\):*:*:*:*:*:*:*:*NVD CPE: up to and including 13.0. Siemens: the flaw does not occur when TIA Portal V13 SP1 or later was used to provision the CPU

What does this mean for affected devices?

NVD carries the Siemens description: "Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N); both NVD and Siemens class it CWE-287 (improper authentication). The record was published on 2021-08-10 (NVD, CVE record).

Which S7-1200 CPUs are affected?

Siemens ProductCERT SSA-830194 (V1.1, 2021-09-14) limits the flaw to one firmware release: the SIMATIC S7-1200 CPU family, including SIPLUS variants, on V4.5.0. Two conditions must both hold: the CPU runs V4.5.0, and its configuration was provisioned with TIA Portal V13 (without SP1). Version 1.1 of the advisory clarified that an attacker using TIA Portal V13 or later, not only V17 or later, could exploit it. CISA republished it as ICSA-21-222-09. The researcher credited is Gao Jian.

Why is the Siemens score higher than NVD's?

Siemens scores it 8.1 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C): it rates attack complexity high, because of the provisioning precondition, but counts confidentiality, integrity and availability as high, since a downloaded program controls the whole PLC. NVD rates complexity low and only integrity high, which gives 7.5. Either way, a program download from an unauthenticated engineering client is full control of the process.

How do you fix or mitigate it?

Product Affected Fix
SIMATIC S7-1200 CPU family (incl. SIPLUS) V4.5.0 V4.5.1 or later

Siemens' specific workaround is to use TIA Portal V13 SP1 or any later version before provisioning S7-1200 V4.5.0 devices. Record which TIA Portal version created each project, since the risk depends on it, and skip V4.5.0 when you plan firmware updates. Beyond that, Siemens advises protecting network access to the CPU, which in practice means keeping S7 traffic on 102/tcp inside the cell.

Our S7-1200 and S7-1500 vulnerability guide covers this CVE among the access-protection issues, and the authentication bypass fix guide covers the class. Related S7-1200 pages are CVE-2019-10943, CVE-2020-15782 and CVE-2022-38465.

CVE-2021-37172 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.00922, the 61.1st percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD (read 2026-11-20): status Modified; published 2021-08-10; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N, v2 5.0; CWE-287 (NVD and Siemens); CPE S7-1200 CPU firmware 4.5.0 with CPU 1211C to 1217C and STEP 7 (TIA Portal) up to and including 13.0; reference SSA-830194. — NVD
  • Siemens SSA-830194 V1.1 (published 2021-08-10, updated 2021-09-14), read 2026-11-20: S7-1200 CPU family (incl. SIPLUS) V4.5.0 fails to authenticate against configured passwords when provisioned with TIA Portal V13; update to V4.5.1 or later; workaround: use TIA Portal V13 SP1 or later before provisioning; CVSS v3.1 8.1 CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C; CWE-287; credits Gao Jian; V1.1 clarified TIA Portal V13 or later (not only V17 or later). — Siemens ProductCERT SSA-830194
  • CISA ICSA-21-222-09 CSAF (Siemens SIMATIC S7-1200, Update A, current release 2025-05-06), read 2026-11-20: CVE-2021-37172 CWE-287, CVSS v3.1 8.1. — CISA CSAF ICSA-21-222-09
  • CVE record (checked 2026-11-20): state PUBLISHED, CNA Siemens, published 2021-08-10; CNA CWE-287; affected S7-1200 CPU family (incl. SIPLUS variants) V4.5.0. — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries, released 2026-11-18), checked 2026-11-20. — CISA KEV
  • EPSS 0.00922, percentile 0.61073, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-830194: Missing Authentication Vulnerability in S7-1200 Devices
  3. CISA CSAF: ICSA-21-222-09 Siemens SIMATIC S7-1200 (machine-readable advisory)
  4. CVE.org record CVE-2021-37172 (CNA: Siemens)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Is my S7-1200 affected by CVE-2021-37172?

Only if it runs firmware V4.5.0 and was provisioned with TIA Portal V13. Siemens SSA-830194 says the flaw does not occur when TIA Portal V13 SP1 or any later version was used to provision the CPU, and other firmware versions are not listed.

Which firmware fixes it?

S7-1200 firmware V4.5.1 or later, per Siemens SSA-830194. When planning updates from older firmware, go past V4.5.0 rather than stopping on it.

What can an attacker do with it?

Bypass the configured password and download arbitrary programs to the PLC using TIA Portal V13 or later, according to Siemens. A downloaded program controls the outputs of the CPU, so the impact is control of the process the PLC runs.

Why do NVD and Siemens give different scores?

Siemens scores 8.1 with high attack complexity and high impact on confidentiality, integrity and availability. NVD scores 7.5 with low complexity and integrity impact only. Both agree that no privileges or user interaction are needed.