CVE-2020-15782 is a memory protection bypass in Siemens SIMATIC S7-1200 and S7-1500 CPUs: a remote attacker with access to port 102/tcp could write data and code into protected memory or read sensitive data. NVD scores it 9.8; Siemens scores it 8.1. Siemens SSA-434534 fixes it in S7-1200 V4.5.0 and S7-1500 V2.9.2.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
5.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-15782 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| SIMATIC S7-1200 CPU family (incl. SIPLUS variants) | cpe:2.3:o:siemens:s7-1200_cpu_firmware:*:*:*:*:*:*:*:* | All versions before V4.5.0; fixed in V4.5.0 (Siemens SSA-434534) |
| SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) | cpe:2.3:o:siemens:s7-1500_cpu_firmware:*:*:*:*:*:*:*:* | All versions before V2.9.2; fixed in V2.9.2 (Siemens SSA-434534) |
| SIMATIC Drive Controller family | cpe:2.3:o:siemens:simatic_driver_controller_firmware:*:*:*:*:*:*:*:* | All versions before V2.9.2; fixed in V2.9.2 (Siemens SSA-434534) |
| SIMATIC S7-1500 Software Controller | cpe:2.3:a:siemens:simatic_s7-1500__software_controller:*:*:*:*:*:*:*:* | All versions before V21.9; fixed in V21.9 (Siemens SSA-434534). NVD's CPE has no version limit |
| SIMATIC ET 200SP Open Controller CPU 1515SP PC2 and CPU 1515SP PC (incl. SIPLUS variants) | cpe:2.3:o:siemens:et_200sp_open_controller_firmware:*:*:*:*:*:*:*:* | CPU 1515SP PC2 before V21.9 (fixed in V21.9); CPU 1515SP PC all versions, no fix, mitigations only as of 2026-11-19 (Siemens SSA-434534) |
| SIMATIC S7-PLCSIM Advanced | cpe:2.3:a:siemens:simatic_s7-plcsim_advanced:*:*:*:*:*:*:*:* | All versions before V4.0; fixed in V4.0 (Siemens SSA-434534) |
| SINUMERIK MC and SINUMERIK ONE | — | All versions before V6.15; fixed in V6.15 (Siemens SSA-434536) |
| SINAMICS PERFECT HARMONY GH180 drives (6SR5 with options A84, A85, E06, W41 with X30; 6SR4 with option W41 with X30) | — | Drives manufactured before 2021-08-13; later drives contain a corrected S7-1500 or S7-1200 CPU (Siemens SSA-434535) |
What does this mean for affected devices?
NVD carries the Siemens description: affected devices "are vulnerable to a memory protection bypass through a specific operation. A remote unauthenticated attacker with network access to port 102/tcp could potentially write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks." NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H); CISA's ADP container on the CVE record gives the same 9.8. NVD assigns no CWE of its own and lists Siemens' CWE-119. The record was published on 2021-05-28 by the Siemens CNA (NVD, CVE record).
Why does Siemens score it 8.1 and NVD 9.8?
Siemens ProductCERT SSA-434534 scores CVE-2020-15782 at CVSS v3.1 8.1 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C). The only base-metric difference is attack complexity: Siemens rates it high, NVD low. CISA's ICSA-21-152-01 CSAF reuses the Siemens 8.1 vector and CWE-119. Use the Siemens score when you rank against other Siemens advisories and the NVD score when your tooling is keyed to NVD.
What can an attacker do to the PLC?
Claroty Team82, credited by Siemens (Tal Keren), describes the flaw as a bypass of the sandbox in which S7-1200 and S7-1500 user code runs. Claroty used it to gain read and write memory access that it says would be "difficult to detect and remove", and to write and run native shellcode in protected memory areas. Claroty notes the attack needs network access to the PLC and PLC download rights, and applies to PLCs with disabled access protection. In its 2021 write-up Claroty stated it was not aware of public exploitation.
Which products and firmware versions are affected?
| Product (Siemens wording) | Affected | Fixed |
|---|---|---|
| SIMATIC S7-1200 CPU family (incl. SIPLUS) | before V4.5.0 | V4.5.0 |
| SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS) | before V2.9.2 | V2.9.2 |
| SIMATIC Drive Controller family | before V2.9.2 | V2.9.2 |
| SIMATIC S7-1500 Software Controller | before V21.9 | V21.9 |
| SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS) | before V21.9 | V21.9 |
| SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS) | all versions | no fix, mitigations only |
| SIMATIC S7-PLCSIM Advanced | before V4.0 | V4.0 |
| SINUMERIK MC and SINUMERIK ONE | before V6.15 | V6.15 (SSA-434536) |
| SINAMICS PERFECT HARMONY GH180 (several 6SR5 and 6SR4 models) | manufactured before 2021-08-13 | later drives ship a corrected CPU (SSA-434535) |
NVD's CPE configuration has no version limit for the S7-1500 Software Controller or the ET 200SP Open Controller, so a scanner keyed to NVD also flags fixed units, and it does not cover the SINUMERIK and SINAMICS products.
How do you fix or mitigate it?
Update to the fixed version for each product. Where that is not possible, SSA-434534 lists password protection for S7 communication, blocking client connections with the ENDIS_PW instruction or the S7-1500 display, keeping PLCs off untrusted networks, and moving to TIA Portal V17 with TLS and individual certificates between PLC, HMI and PG/PC. SSA-434536 adds limiting 102/tcp to trusted users and systems. Our S7comm security guide covers port 102/tcp controls, the S7-1200/S7-1500 vulnerability guide ranks this CVE against the rest of the family, and the memory corruption fix guide covers the CWE-119 class. The same 102/tcp path carries CVE-2019-10929 and CVE-2019-10943; S7-1200 CPUs before V4.5.0 are also hit by CVE-2020-28400.
CVE-2020-15782 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.05184, the 92.6th percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-19): status Modified; published 2021-05-28; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, Secondary 9.8 from CISA ADP, v2 7.5; CWE-119 from Siemens only; CPE: s7-1200_cpu_firmware before 4.5.0, s7-1500_cpu_firmware and simatic_driver_controller_firmware before 2.9.2, simatic_s7-plcsim_advanced before 4.0, simatic_s7-1500__software_controller and et_200sp_open_controller_firmware without version limit; references SSA-434534, SSA-434535, SSA-434536. — NVD
- Siemens SSA-434534 V1.1 (published 2021-05-28, updated 2021-09-14), read 2026-11-19: memory protection bypass, remote unauthenticated attacker with network access to 102/tcp could write arbitrary data and code to protected memory areas or read sensitive data; CVSS v3.1 8.1 CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C; CWE-119; fixes: Drive Controller V2.9.2, CPU 1515SP PC2 V21.9, S7-1200 V4.5.0, S7-1500 V2.9.2, S7-1500 Software Controller V21.9, S7-PLCSIM Advanced V4.0; CPU 1515SP PC all versions, mitigations only; mitigations: password protection for S7 communication, ENDIS_PW, S7-1500 display access protection, defense in depth, TIA Portal V17 with TLS; credits Tal Keren (Claroty). — Siemens ProductCERT SSA-434534
- Siemens SSA-434536 V1.1 (updated 2021-09-14), read 2026-11-19: SINUMERIK MC and SINUMERIK ONE before V6.15 affected, fixed in V6.15; mitigation: limit access to 102/tcp to trusted users and systems; CVSS v3.1 8.1. — Siemens ProductCERT SSA-434536
- Siemens SSA-434535 V1.1 (updated 2021-09-14), read 2026-11-19: SINAMICS PERFECT HARMONY GH180 drives manufactured before 2021-08-13 affected; drives manufactured on or after 2021-08-13 contain a corrected S7-1500 or S7-1200 CPU; mitigations: protect the CPU access protection password, keep the drive internal network unconnected externally. — Siemens ProductCERT SSA-434535
- CISA ICSA-21-152-01 CSAF (Update A, current release 2025-05-06), read 2026-11-19: CVE-2020-15782, CWE-119, CVSS v3.1 8.1 with the Siemens vector; same product list, fixed versions and mitigations as SSA-434534. — CISA CSAF ICSA-21-152-01
- Claroty Team82 write-up, read 2026-11-19: CVE-2020-15782 bypasses the PLC sandbox on S7-1200 and S7-1500 to gain read/write memory access and run native shellcode in protected memory; attack needs network access and PLC download rights and applies to PLCs with disabled access protection; Claroty not aware of public exploitation at publication. — Claroty Team82
- CVE record (checked 2026-11-19): state PUBLISHED, CNA Siemens, published 2021-05-28; CNA CWE-119, no CNA CVSS metric; CISA ADP CVSS v3.1 9.8. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-19. — CISA KEV
- EPSS 0.05184, percentile 0.92621, dataset 2026-11-18, read 2026-11-19. — FIRST EPSS

Related advisories
Sources
- NVD
- Siemens ProductCERT SSA-434534: Memory Protection Bypass Vulnerability in SIMATIC S7-1200 and S7-1500 CPU Families
- Siemens ProductCERT SSA-434536: Memory Protection Bypass Vulnerability in SINUMERIK ONE and SINUMERIK MC
- Siemens ProductCERT SSA-434535: Memory Protection Bypass Vulnerability in SINAMICS PERFECT HARMONY GH180 Drives
- CISA CSAF: ICSA-21-152-01 Siemens SIMATIC S7-1200 and S7-1500 CPU Families (machine-readable advisory)
- Claroty Team82: The Race to Native Code Execution in PLCs
- CVE.org record CVE-2020-15782 (CNA: Siemens)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Which firmware fixes CVE-2020-15782?
S7-1200 CPU family V4.5.0, S7-1500 CPU family and Drive Controller V2.9.2, S7-1500 Software Controller and ET 200SP Open Controller CPU 1515SP PC2 V21.9, and S7-PLCSIM Advanced V4.0. The ET 200SP Open Controller CPU 1515SP PC has no fix as of 2026-11-19 (per Siemens SSA-434534).
Why do NVD and Siemens give different scores for CVE-2020-15782?
NVD rates attack complexity low and arrives at 9.8; Siemens rates it high and arrives at 8.1. All other base metrics match: network vector, no privileges, no user interaction, high impact on confidentiality, integrity and availability (per NVD and Siemens SSA-434534).
What can I do on CPUs that cannot be updated right away?
Set password protection for S7 communication, block remote client connections with the ENDIS_PW instruction or the S7-1500 display, keep the PLC off untrusted networks, and move to TIA Portal V17 with TLS between PLC, HMI and PG/PC (per Siemens SSA-434534).
Does CVE-2020-15782 let an attacker hide code on the PLC?
Claroty used it to escape the PLC sandbox and write native shellcode into protected memory, access it describes as difficult to detect and remove. Claroty says the attack needs network access and PLC download rights and applies to PLCs with disabled access protection (per Claroty Team82).
Questions about this page?