CVE-2020-28400 is a PROFINET DCP denial-of-service flaw in Siemens devices: a large number of DCP reset packets from an unauthenticated attacker knocks out S7-1200 CPUs, SCALANCE switches, RUGGEDCOM routers and SIMOCODE pro V devices. NVD scores it 7.5. Siemens SSA-599968 lists 356 entries; nine have no fix and rely on blocking DCP.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
1.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-28400 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC S7-1200 CPUs | — | before V4.5.0 (Siemens SSA-599968) |
| Siemens SCALANCE X-200, X-200IRT, X-300, XB/XC/XF/XP-200, XM-400 and XR-500 switches | cpe:2.3:o:siemens:scalance_x204-2_firmware:*:*:*:*:*:*:*:* | X-300 before V4.1.4; XB/XC/XF-200BA/XP-200 before V4.3; X-200 before V5.2.5; X-200IRT before V5.5.0; XR-500 and XM-400 before V6.3.1 (SSA-599968) |
| Siemens RUGGEDCOM RM1224, SCALANCE M-800 and S615 | cpe:2.3:o:siemens:ruggedcom_rm1224_firmware:*:*:*:*:*:*:*:* | before V6.4 (SSA-599968) |
| Siemens SCALANCE W-700 and W1700 | — | W-700 IEEE 802.11n before V6.4.0; W1748/W1788 M12 before V3.0.0 (SSA-599968) |
| Siemens SIMOCODE pro V, SIMATIC MV540/550/560, CM 1542-1, CFU PA/DIQ, EK-ERTEC 200P, PROFINET Driver | — | SIMOCODE pro V PN before V2.1.3, EIP before V1.1.3; MV540/MV550/MV560 and CM 1542-1 before V3.0; CFU before V2.0.0; EK-ERTEC 200P before V4.7; PROFINET Driver before V2.3 (SSA-599968) |
| Siemens CP 1604, CP 1616, CP 1626, IE/PB-LINK, DK-16xx PN IO, PLB, SOFTNET-IE PNIO, DK/EK-ERTEC 200 kits | — | no fix; mitigation only (9 entries, SSA-599968) |
What does this mean for affected devices?
CVE-2020-28400 is the largest of the Siemens PROFINET denial-of-service disclosures. NVD's description: "Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a denial of service condition. The vulnerability can be triggered if a large amount of DCP reset packets are sent to the device." NVD scores it 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, with CWE-770 (allocation of resources without limits or throttling) (NVD). Siemens adds a CVSS v4.0 score of 8.7.
Siemens ProductCERT SSA-599968 was first published on 2021-07-13. Revision 10 of 2026-04-14 added a fix for the SCALANCE W-700 IEEE 802.11n family and expanded the S7-1200 CPU list. Its CSAF file lists 356 product entries, and CISA's ICSA-21-194-03, at revision 12 of 2026-04-16, carries the same 356 (CSAF). Fixed versions include:
- SIMATIC S7-1200 CPUs (1211C to 1217C, incl. F and SIPLUS variants): V4.5.0; the S7-1200 CPU V4 family entry: V4.5.
- SCALANCE X-300 (incl. X302-7 EEC): V4.1.4. XB-200, XC-200, XF-200BA, XP-200: V4.3. X-200: V5.2.5. X-200IRT: V5.5.0. XR-500 (XR524-8C, XR526-8C, XR528-6M, XR552-12M) and XM-400 (XM408, XM416): V6.3.1.
- RUGGEDCOM RM1224, SCALANCE M-800 and S615: V6.4. SCALANCE W-700 IEEE 802.11n: V6.4.0. SCALANCE W1748/W1788 M12: V3.0.0.
- SIMOCODE pro V PN: V2.1.3; SIMOCODE pro V EIP: V1.1.3. SIMATIC MV540, MV550 and MV560 and CM 1542-1: V3.0. CFU PA and CFU DIQ: V2.0.0. EK-ERTEC 200P: V4.7. PROFINET Driver: V2.3.
Nine entries have no fix: the DK Standard Ethernet Controller and EK-ERTEC 200 development kits, SIMATIC CP 1604, CP 1616 and CP 1626, SIMATIC IE/PB-LINK, SIMATIC NET DK-16xx PN IO, the SIMATIC Power Line Booster PLB base module and SOFTNET-IE PNIO. For all 356 entries Siemens recommends to "Block incoming Profinet Discovery and Configuration Protocol (DCP) packets (Ethertype 0x8892, Frame-ID: 0xfefe) from untrusted networks" and to disable PROFINET where it is optional and unused.
Our PROFINET protocol security guide uses this CVE as its main example. DCP has no authentication, but this bug is a throttling failure, so a PROFINET Security Class does not close it; only the vendor firmware does. The guide's monitoring rule for this pattern is a flood of DCP frames to one device. The other Siemens DCP pages are CVE-2017-2680 and CVE-2018-4843, and Cisco's PROFINET DCP flaw on Industrial Ethernet switches is CVE-2017-12235. For throttling as a design rule, see our input-handling fix guide.
CVE-2020-28400 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.01856, the 79.5th percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).
Evidence
- Large amount of DCP reset packets triggers DoS; unauthenticated; CVSS 3.1 7.5 Primary; CWE-770. — NVD
- SSA-599968 first published 2021-07-13; revision 10 of 2026-04-14 added SCALANCE W-700 fix and expanded S7-1200 list; CVSS v4.0 8.7; fixed versions listed; block DCP (Ethertype 0x8892, Frame-ID 0xfefe); disable PROFINET where optional. — Siemens ProductCERT SSA-599968
- 356 product entries, 9 with no fix (CSAF). — Siemens ProductCERT SSA-599968 (CSAF)
- ICSA-21-194-03 revision 12 of 2026-04-16 lists 356 entries, 9 without a fix. — CISA ICSA-21-194-03 (CSAF)
- Not in the KEV catalog as of 2026-11-17 (catalog version 2026.11.13). — CISA KEV
- EPSS 0.01856 (79.5th percentile), dataset 2026-11-16, read 2026-11-17. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
How is CVE-2020-28400 triggered?
By sending a large amount of PROFINET DCP reset packets to an affected device. No authentication is needed, and the device does not limit the resources it spends on them (CWE-770, per NVD and Siemens SSA-599968).
Which Siemens products have no fix for CVE-2020-28400?
Nine entries: SIMATIC CP 1604, CP 1616 and CP 1626, IE/PB-LINK, NET DK-16xx PN IO, Power Line Booster PLB base module, SOFTNET-IE PNIO and the DK Standard Ethernet Controller and EK-ERTEC 200 kits (per SSA-599968).
What does Siemens recommend while patching?
Block incoming DCP packets (Ethertype 0x8892, Frame-ID 0xfefe) from untrusted networks and disable PROFINET on products where it is optional and unused (per SSA-599968).
Is CVE-2020-28400 in the CISA KEV catalog?
No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.01856, the 79.5th percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?