Security Advisory

CVE-2019-10936: Siemens PROFINET UDP Flood DoS

Last updated:
  • CVE-2019-10936

CVE-2019-10936 is a denial-of-service flaw in Siemens PROFINET devices: large amounts of specially crafted UDP packets let an unauthenticated remote attacker knock S7 CPUs, ET 200 IO modules and SINAMICS drives offline. NVD scores it 7.5. Siemens SSA-473245 lists 120 entries, and 46 of them, including S7-1500 CPU hardware, have no fix.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

2.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-10936 · Source: NVD

Affected components

ComponentCPEVersion range
Siemens SIMATIC S7-1200 CPU familycpe:2.3:o:siemens:simatic_s7-1200_cpu_firmware:*:*:*:*:*:*:*:*before V4.4.0 (Siemens SSA-473245)
Siemens SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS)cpe:2.3:o:siemens:simatic_s7-1500_cpu_firmware:*:*:*:*:*:*:*:*all versions; no fix, mitigation only (SSA-473245); Software Controller fixed in V2.0
Siemens SIMATIC S7-300, S7-400 and S7-410 CPUs—S7-300 PN/DP before V3.2.17 (314C-2 before V3.3.17); S7-400 PN/DP V7 before V7.0.3; S7-400 H V6 before V6.0.9; S7-410 V8 before V8.2.2; S7-400 PN/DP V6 and below no fix (SSA-473245)
Siemens ET 200MP, ET 200SP, ET 200M, ET 200S, ET 200AL and ET200ecoPN IO modules—IM 155-5 PN HF before V4.4.0; IM 155-6 PN HF before V4.2.2; ST, BA, ET 200M/S/AL and ET200ecoPN no fix (SSA-473245)
Siemens SINAMICS drives and SINUMERIK CNC—G120 V4.7 PN before V4.7 SP10 HF5; S120 V4.7 before V5.2 HF4; SINUMERIK 828D before V4.8 SP5, 840D sl before V4.8 SP6; S110 and SM120 no fix (SSA-473245)

What does this mean for affected devices?

CVE-2019-10936 is a UDP flood weakness in Siemens PROFINET devices. NVD's description is short: "Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a denial of service condition." NVD's own analysis gives CVSS v3.1 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, with CWE-400. The API types that v3.1 entry as Secondary; NVD's Primary metric is CVSS v2 5.0 (NVD). Siemens gives the same 7.5 and, in its CSAF file, the temporal metric E:P (proof-of-concept exploit code).

Siemens ProductCERT SSA-473245 was first published on 2019-10-08 and reached revision 18 on 2024-07-09. It lists 120 product entries; CISA's copy, ICSA-19-283-02, carries the same 120 (CSAF). Fixed versions include:

  • SIMATIC S7-1200 CPU family: V4.4.0. S7-1500 Software Controller and ET 200SP Open Controller CPU 1515SP PC: V2.0.
  • SIMATIC S7-300 PN/DP CPUs: V3.2.17 (CPU 314C-2 PN/DP: V3.3.17). S7-400 PN/DP V7 CPUs: V7.0.3. S7-400 H V6: V6.0.9. S7-410 V8: V8.2.2.
  • ET 200MP IM 155-5 PN HF: V4.4.0. ET 200SP IM 155-6 PN HF: V4.2.2. PN/PN Coupler: V4.2.1.
  • SINAMICS G120 V4.7 PN: V4.7 SP10 HF5. SINAMICS S120 V4.7: V5.2 HF4. SINUMERIK 828D: V4.8 SP5; 840D sl: V4.8 SP6.

The gap is large: 46 of the 120 entries have no fix. They include the SIMATIC S7-1500 CPU family hardware (incl. related ET200 CPUs and SIPLUS), the S7-400 PN/DP V6 and below CPUs, the ET 200SP IM 155-6 PN ST and BA and ET 200MP IM 155-5 PN ST interface modules with their SIPLUS variants, ET 200M, ET 200S, ET 200AL and ET200ecoPN, the HMI Comfort, Comfort Outdoor and KTP Mobile Panels, SINAMICS S110 and SM120, and the DK Standard Ethernet Controller and EK-ERTEC 200 development kits. NVD's CPE configuration still gives S7-1500 CPU firmware before 2.0 as the affected range, which differs from Siemens' current list, so check hardware CPUs against the SSA rather than the CPE. For all entries Siemens recommends to "Restrict network access to affected devices."

Our PROFINET protocol security guide groups this CVE with the DCP findings CVE-2020-28400 and CVE-2018-4843: its fix is vendor firmware, not a PROFINET Security Class. Because so many entries depend on network controls, rate-limit and filter UDP at the cell boundary as our Purdue model guide describes. For resource exhaustion as a class, see the input-handling fix guide.

CVE-2019-10936 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.02065, the 81.7th percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Resource exhaustion. Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.

Evidence

  • Improper handling of large amounts of crafted UDP packets; NVD CVSS 3.1 7.5 (typed Secondary) and Primary CVSS v2 5.0; CWE-400; CPE s7-1500_cpu firmware before 2.0. — NVD
  • SSA-473245 published 2019-10-08, revision 18 of 2024-07-09; 120 entries, 46 with no fix including S7-1500 CPU family; fixed versions listed; mitigation restrict network access. — Siemens ProductCERT SSA-473245
  • CVSS 3.1 vector with E:P/RL:O/RC:C temporal metrics. — Siemens ProductCERT SSA-473245 (CSAF)
  • ICSA-19-283-02 revision 18 lists 120 entries, 46 without a fix. — CISA ICSA-19-283-02 (CSAF)
  • Not in the KEV catalog as of 2026-11-17 (catalog version 2026.11.13). — CISA KEV
  • EPSS 0.02065 (81.7th percentile), dataset 2026-11-16, read 2026-11-17. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-473245: Denial of Service Vulnerability in Profinet Devices
  3. Siemens ProductCERT SSA-473245 (CSAF)
  4. CISA ICSA-19-283-02: Siemens PROFINET Devices (CSAF)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Is CVE-2019-10936 a DCP flaw?

No. It is triggered by large amounts of specially crafted UDP packets, not DCP frames, so it travels over IP and NVD scores the attack vector as network (per NVD and Siemens SSA-473245).

Is the SIMATIC S7-1500 CPU fixed for CVE-2019-10936?

The S7-1500 Software Controller is fixed in V2.0, but Siemens lists the S7-1500 CPU family hardware (incl. related ET200 CPUs and SIPLUS) among the 46 entries with no fix (per SSA-473245, revision 18).

What does Siemens recommend where no fix exists?

Restrict network access to the affected devices. That is Siemens' mitigation for all 120 entries in SSA-473245, and CISA's ICSA-19-283-02 carries the same advice.

Is CVE-2019-10936 in the CISA KEV catalog?

No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.02065, the 81.7th percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).