GE Vernova UR relay vulnerabilities: the 2025 CVE chain, explained

Last updated:

Key takeaways

  • A protection relay sits at one of the most consequence-heavy points in a power grid: it is the device deciding, in milliseconds, whether to trip a breaker to prevent equipment damage or a wider outage.
  • These two chain together into the research's headline finding.
  • No — it is at least the second round in four years.
  • Inventory every UR-family relay and every workstation running EnerVista UR Setup.

Nozomi Networks Labs disclosed five vulnerabilities in 2025 affecting GE Vernova's UR family of substation protection relays (including the N60 Network Relay) and their EnerVista UR Setup configuration software, and two of the five chain together into a real attack path: an attacker who gets a man-in-the-middle position can steal relay credentials over an unauthenticated SSH session, then push unverified, unsigned firmware onto the relay itself. CVE-2025-27256 (CVSS v3.1 8.3) is the missing-authentication flaw that enables the credential theft; CVE-2025-27257 (CVSS v3.1 6.1) is the missing firmware-signature check that lets the stolen access turn into a firmware takeover. GE Vernova has patched both, alongside three further EnerVista UR Setup flaws disclosed the same day — but this is not the UR family's first serious CVE round, and that history is itself useful context for anyone deciding how much to trust a patch alone.

This guide draws directly on NVD's own published records for all five 2025 CVEs, Nozomi Networks Labs' original disclosure write-up, and CISA's 2021 ICSA-21-075-02 advisory for the UR family's prior CVE history — each fetched and read for this guide, not paraphrased from a secondary summary.

What is the GE Vernova UR relay family, and why does it matter for OT security?

GE Vernova's UR (Universal Relay) family is a line of protection, control and monitoring relays deployed in electrical substations to detect fault conditions and trip breakers before equipment or personnel are harmed — CISA's ICSA-21-075-02 advisory names the family's models directly: B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60. The N60 Network Relay, the device Nozomi Networks Labs examined in its 2025 research, is one member of that family. EnerVista UR Setup is GE Vernova's Windows client software for configuring a UR relay, reading its status, and pushing firmware or configuration changes — the single piece of software responsible for four of the five 2025 CVEs, with the relay's own onboard firmware responsible for the fifth.

A protection relay sits at one of the most consequence-heavy points in a power grid: it is the device deciding, in milliseconds, whether to trip a breaker to prevent equipment damage or a wider outage. That is also exactly why an attacker who can reconfigure one, or replace its firmware outright, has a materially different kind of leverage than an attacker on a typical IT endpoint.

What do CVE-2025-27256 and CVE-2025-27257 actually let an attacker do?

These two chain together into the research's headline finding. NVD's record for CVE-2025-27256 (CVSS v3.1 8.3, CWE-306 Missing Authentication for Critical Function) describes "a missing SSH server authentication" in EnerVista UR Setup versions 7.0 through 8.60 that "allows Authentication Bypass" — concretely, "an attacker may perform a man-in-the-middle attack on the network in order to steal credentials or forge malicious traffic." NVD's record for CVE-2025-27257 (CVSS v3.1 6.1, CWE-345 Insufficient Verification of Data Authenticity) describes the second half of the chain: "an authenticated user" can "install a modified firmware" because "the firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup" and not on the N60 relay itself.

Nozomi Networks Labs' own write-up states the combined effect in plain terms: "By executing the MITM attack, an attacker can intercept and acquire valid credentials for the GE Vernova N60 Network Relay. With these credentials, and due to the lack of firmware verification, the attacker can then upload malicious firmware to seize control of the device." Neither step alone requires the attacker to already hold valid relay credentials — the missing SSH authentication is what gets them the credentials in the first place.

The other three 2025 CVEs: port-forwarding, a registry flag, and a shared password

The remaining three CVEs, all published by NVD on the same day (10 March 2025) and all credited to Nozomi Networks Labs' responsible disclosure, affect EnerVista UR Setup rather than the relay's own firmware:

CVE CVSS v3.1 CWE What NVD says it does
CVE-2025-27254 8.0 CWE-282 (Improper Ownership Management) "The software's startup authentication can be disabled by altering a Windows registry setting that any user can modify."
CVE-2025-27255 8.0 CWE-798 (Use of Hard-coded Credentials) "The local user database is encrypted using an hardcoded password retrievable by an attacker analyzing the application code."
CVE-2025-27253 6.1 CWE-15 (External Control of System or Configuration Setting) Inadequate IP/port validation on a port-forwarding feature "may allow the attacker to bypass firewall rules or to send malicious traffic in the network."

Two of the three (CVE-2025-27254, CVE-2025-27255) score High, not Medium — a shared, hardcoded decryption key and a user-editable registry flag guarding "startup authentication" are both the kind of design choice that defeats the software's own access control with no privileged access required to exploit, only local access to a machine running EnerVista UR Setup.

Is there a patch, and what does GE Vernova recommend?

Yes. Nozomi Networks Labs' advisory states the remediation directly: "Update the EnerVista UR software to the latest 8.60 version and ensure that the N60 firmware is also upgraded to the newest available release" — check GE Vernova's own current advisory for the latest shipping version before acting, since UR Setup has had further releases since. Beyond patching, Nozomi's write-up recommends the standard compensating controls for any protection relay on a substation network: "Placing the UR inside an electronic security perimeter, deploying and maintaining access controls, robust network monitoring and Intrusion Detection, network segmentation and firewalls." Every one of the five 2025 CVEs assumes the attacker already has network access to the relay's management plane or local access to a workstation running EnerVista UR Setup — none is exploitable from the open internet with no foothold at all, which is exactly what NERC CIP-005's electronic security perimeter requirement is built to deny in the first place.

Is 2025 the first time the UR relay family has had serious vulnerabilities disclosed?

No — it is at least the second round in four years. CISA's ICSA-21-075-02, filed in 2021, covers nine separate CVEs against the same UR family, including CVE-2021-27426 (Insecure Default Variable Initialization) at CVSS v3 9.8 — the practical ceiling of the scale — and CVE-2021-27430 (Use of Hard-coded Credentials) at 8.4. That advisory credits its findings to "SCADA-X, DOE's Cyber Testing for Resilient Industrial Control Systems (CyTRICS) program, Verve Industrial, and VuMetric" and states that the UR bootloader binary shipped with "unused hardcoded credentials" through firmware version 7.02, plus a separate finding that "a user with physical access to the UR IED can interrupt the boot sequence by rebooting the UR." Two independent CVE rounds against the same relay family, four years apart, found by four different research groups the second time around (Nozomi, versus SCADA-X/DOE CyTRICS/Verve/VuMetric the first time), is the kind of recurring pattern MITRE ATT&CK for ICS and IEC 62351's power-systems communications security guidance both assume will keep happening in fielded protection relays — which is why the relevant question for an asset owner is less "has this specific CVE been patched" and more "is this device inside an electronic security perimeter with change management that would catch an unauthorized firmware push."

Where does AI-based OT network monitoring actually fit here?

It is worth naming plainly, without overclaiming: Nozomi Networks, the firm that found and disclosed these five CVEs, also sells commercial OT network-monitoring sensors built around exactly the compensating control its own advisory recommends. Nozomi's own Guardian product page describes the mechanism as passively learning "a baseline of normal behavior patterns" from traffic and device interactions, then continuously monitoring "for deviations from the baseline to detect anomalous traffic, unusual process values and threats." That is a real, commercially available technique — behavioral baselining of OT protocol traffic, not a vague "AI will catch it" claim — and it is a genuinely useful compensating control for exactly the gap these CVEs expose: a relay with no firmware-signature enforcement of its own has no way to refuse a malicious update, so the practical defense shifts to the network layer, watching for the kind of unusual engineering-workstation-to-relay traffic a firmware push or credential-harvesting MITM would generate. It does not, on its own, fix a missing SSH authentication check or a hardcoded password — those still need the vendor patch.

A workable starting point

  1. Inventory every UR-family relay and every workstation running EnerVista UR SetupBoth the 2025 and 2021 CVE rounds affect specific firmware and software version ranges; you cannot assess exposure without knowing exactly which relay models, firmware revisions and EnerVista UR Setup versions are in use.
  2. Patch EnerVista UR Setup and relay firmware to GE Vernova's current recommended versions, not just "the latest version as of this guide" — check GE Vernova's own current advisory, since the vendor has continued to ship releases past the versions discussed here.
  3. Confirm every UR relay sits inside an electronic security perimeter, per NERC CIP-005 if the device is a BES Cyber Asset, or an equivalent segmented zone otherwise — none of the five 2025 CVEs is remotely exploitable from the open internet, so a genuine network boundary closes off the realistic attack path even before patching.
  4. Pair patching with change management that would flag an unauthorized firmware push, the way NERC CIP-010 requires for in-scope assets — the 2025 chain's entire point is that the relay itself cannot tell a legitimate update from a malicious one.
  5. Treat a network-monitoring layer as a compensating control, not a substitute for the patch— passive behavioral baselining of the kind discussed above can flag the unusual traffic an exploitation attempt generates, but it does not close the underlying authentication or signature-verification gap.

SoftWSP's OT Snapshot builds a passive, factual picture of what is actually talking to a substation's protection relays from a mirror port, without touching production traffic — a starting point for scoping exposure to this CVE chain before deciding on segmentation, patching order or change-management changes: see OT Snapshot. For the broader network-architecture question of where a protection relay should sit relative to the rest of a substation's systems, see the Purdue Model for OT/ICS network architecture and NIST SP 800-82's OT security guidance.

This guide summarizes NVD's published records for CVE-2025-27253 through CVE-2025-27257, Nozomi Networks Labs' original disclosure write-up, and CISA's ICSA-21-075-02 advisory for the UR family's 2021 CVE history, each fetched directly for this guide on 6 November 2026. It is not a substitute for GE Vernova's current advisory, NVD's current CVE records, or an engineer's assessment of a specific deployment, and does not constitute security advice.

Sources

  1. NVD: CVE-2025-27256 — CVSS v3.1 8.3, CWE-306, missing SSH authentication in GE Vernova EnerVista UR Setup
  2. NVD: CVE-2025-27257 — CVSS v3.1 6.1, CWE-345, client-side-only firmware signature verification on GE Vernova UR IED family devices
  3. NVD: CVE-2025-27254 — CVSS v3.1 8.0, CWE-282, registry-based startup authentication bypass in EnerVista UR Setup
  4. NVD: CVE-2025-27255 — CVSS v3.1 8.0, CWE-798, hard-coded local-database decryption password in EnerVista UR Setup
  5. NVD: CVE-2025-27253 — CVSS v3.1 6.1, CWE-15, unvalidated port-forwarding configuration in GE Vernova UR IED family devices
  6. Nozomi Networks Labs: "Securing the Grid: Understanding the Cybersecurity Risks of the GE N60 Network Relay" (original disclosure write-up)
  7. CISA: ICS Advisory ICSA-21-075-02 — GE UR family (9 CVEs, 2021, including CVSS 9.8 CVE-2021-27426)
  8. Nozomi Networks: Guardian product page (passive network baselining and anomaly detection, industry context for AI-based OT monitoring)

Frequently asked questions

What is the GE Vernova UR relay family, and what does EnerVista UR Setup do?

GE Vernova's UR (Universal Relay) family is a line of protection, control and monitoring relays for electrical substations, sold under model names including the B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60 — CISA's own ICSA-21-075-02 advisory lists exactly this set as "advanced protection and control relays." The N60 Network Relay, the specific device examined in Nozomi Networks Labs' 2025 research, is one member of that family, built to protect substation equipment by tripping breakers when it detects a fault condition. EnerVista UR Setup is GE Vernova's own Windows client software for configuring a UR relay, monitoring its status and pushing firmware or configuration updates to it — NVD's own advisory text for this research describes it plainly as the vulnerable component in four of the five 2025 CVEs, with the relay's onboard firmware carrying the fifth.

What do CVE-2025-27256 and CVE-2025-27257 actually let an attacker do?

They chain together into a credential-theft-to-malicious-firmware attack. NVD's record for CVE-2025-27256 (CVSS v3.1 8.3, CWE-306 Missing Authentication for Critical Function) describes "a missing SSH server authentication" in EnerVista UR Setup versions 7.0 through 8.60 that "allows Authentication Bypass," meaning "an attacker may perform a man-in-the-middle attack on the network in order to steal credentials or forge malicious traffic." NVD's record for CVE-2025-27257 (CVSS v3.1 6.1, CWE-345 Insufficient Verification of Data Authenticity) describes the second half: "Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware," because "the firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup," not on the relay itself. Nozomi Networks Labs' own write-up states the combined effect directly: "By executing the MITM attack, an attacker can intercept and acquire valid credentials for the GE Vernova N60 Network Relay. With these credentials, and due to the lack of firmware verification, the attacker can then upload malicious firmware to seize control of the device."

What are the other three 2025 CVEs, and are they as serious?

All three affect EnerVista UR Setup rather than the relay firmware, and NVD rates two of them High. CVE-2025-27254 (CVSS v3.1 8.0, CWE-282 Improper Ownership Management) is an authentication bypass where, per NVD, "the software's startup authentication can be disabled by altering a Windows registry setting that any user can modify" — no special privileges needed, since the registry key itself isn't locked down. CVE-2025-27255 (CVSS v3.1 8.0, CWE-798 Use of Hard-coded Credentials) is a privilege-escalation flaw where, per NVD, "the local user database is encrypted using an hardcoded password retrievable by an attacker analyzing the application code" — meaning every installation shares the same decryption key. CVE-2025-27253 (CVSS v3.1 6.1, CWE-15 External Control of System or Configuration Setting) lets an attacker "establish a TCP connection through a port forwarding" because of inadequate IP address and port validation, which NVD notes "may allow the attacker to bypass firewall rules or to send malicious traffic in the network." All five were published by NVD on 10 March 2025 and credited to Nozomi Networks Labs' responsible disclosure.

Is there a patch, and what does GE Vernova recommend in the meantime?

Yes. Nozomi Networks Labs' advisory states the fix directly: "Update the EnerVista UR software to the latest 8.60 version and ensure that the N60 firmware is also upgraded to the newest available release" — NVD's reference links point to GE Vernova's own vendor advisory for the authoritative current version, since UR Setup has since moved past 8.60 in subsequent releases addressing unrelated issues. Beyond patching, Nozomi's write-up recommends standard compensating controls for any IED on this bus: "Placing the UR inside an electronic security perimeter, deploying and maintaining access controls, robust network monitoring and Intrusion Detection, network segmentation and firewalls." None of the five 2025 CVEs requires an unauthenticated remote attacker starting from the open internet — every path assumes the attacker already has network access to the relay's management interface, which is exactly the access an electronic security perimeter is built to deny.

Is 2025 the first time GE's UR relay family has had serious vulnerabilities disclosed?

No. CISA's ICSA-21-075-02, filed four years earlier, covers nine separate CVEs against the same UR family — including CVE-2021-27426 (Insecure Default Variable Initialization) at CVSS v3 9.8, the maximum practical severity, and CVE-2021-27430 (Use of Hard-coded Credentials) at 8.4. That advisory credits the findings to "SCADA-X, DOE's Cyber Testing for Resilient Industrial Control Systems (CyTRICS) program, Verve Industrial, and VuMetric" and states a UR bootloader binary shipped with "unused hardcoded credentials" through firmware version 7.02. Two independent rounds of CVE disclosures against the same relay family, four years apart, by four different research groups the second time, is the kind of repeat pattern that argues for standing compensating controls rather than a one-time patch-and-move-on response.

In this cluster

GE Vernova UR relay vulnerabilities: the 2025 CVE chain, explained