Nozomi Networks Labs disclosed five vulnerabilities in 2025 affecting GE Vernova's UR family of substation protection relays (including the N60 Network Relay) and their EnerVista UR Setup configuration software, and two of the five chain together into a real attack path: an attacker who gets a man-in-the-middle position can steal relay credentials over an unauthenticated SSH session, then push unverified, unsigned firmware onto the relay itself.
CVE-2025-27256 (CVSS v3.1 8.3) is the missing-authentication flaw that enables the credential theft; CVE-2025-27257 (CVSS v3.1 6.1) is the missing firmware-signature check that lets the stolen access turn into a firmware takeover. GE Vernova has patched both, alongside three further flaws disclosed the same day (two in EnerVista UR Setup, one in the relay firmware) — but this is not the UR family's first serious CVE round, and that history is itself useful context for anyone deciding how much to trust a patch alone.
Key takeaways
- GE Vernova's UR (Universal Relay) family is a line of protection, control and monitoring relays deployed in electrical substations to detect fault conditions and trip breakers before equipment or personnel are harmed.
- They chain into the research's headline finding.
- Two hit EnerVista UR Setup and one hits the relay firmware.
- Three details from those documents change how you plan the work.
What is the GE Vernova UR relay family, and why does it matter for OT security?
GE Vernova's UR (Universal Relay) family is a line of protection, control and monitoring relays deployed in electrical substations to detect fault conditions and trip breakers before equipment or personnel are harmed. CISA's ICSA-21-075-02 CSAF record lists the models: B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60. The N60 Network Relay, the device Nozomi Networks Labs examined, is one member of that family. EnerVista UR Setup is GE Vernova's Windows tool for configuring a UR relay, reading its status and pushing firmware or settings; it carries three of the five 2025 CVEs, and the relay firmware carries the other two.
A protection relay decides, in milliseconds, whether to trip a breaker. An attacker who can reconfigure one, or replace its firmware, has a different kind of leverage than one sitting on an office laptop.
What do CVE-2025-27256 and CVE-2025-27257 actually let an attacker do?
They chain into the research's headline finding. Per the Nozomi Networks Labs write-up (7 March 2025), EnerVista UR Setup talks to the relay over "a custom protocol built on Modbus" carried inside SSH, and the chain runs like this:
Intercept the sessionCVE-2025-27256 (CVSS v3.1 8.3, CWE-306): EnerVista UR Setup versions 7.0 to 8.60 do not authenticate the SSH server they connect to, so an attacker on the same network can sit in the middle. Nozomi showed the relay credentials an off-the-shelf SSH-MITM tool captured. Log in with the stolen credentialsThe relay sees a valid user. Push modified firmwareCVE-2025-27257 (CVSS v3.1 6.1, CWE-345): per the CVE record, "the firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup," so replaying UR Setup's requests with a modified image gets it installed.
Nozomi's summary: "By executing the MITM attack, an attacker can intercept and acquire valid credentials for the GE Vernova N60 Network Relay. With these credentials, and due to the lack of firmware verification, the attacker can then upload malicious firmware to seize control of the device." Both CVEs score Adjacent Network (AV:A): the attacker needs a foothold on the relay's network segment, not just internet access.
Which component do the other three 2025 CVEs hit?
Two hit EnerVista UR Setup and one hits the relay firmware. All three were published on 10 March 2025 with Nozomi Networks Labs as the CVE numbering authority; the affected versions below are from the CVE records and the matching Nozomi advisories (for example CVE-2025-27253):
| CVE | Component and versions | CVSS v3.1 | CWE | What the record says |
|---|---|---|---|---|
| CVE-2025-27253 | UR relay firmware 7.0 to 8.60 | 6.1 | CWE-15 | Port-forwarding input with no IP/port validation "may allow the attacker to bypass firewall rules or to send malicious traffic in the network." |
| CVE-2025-27254 | EnerVista UR Setup 8.42 | 8.0 | CWE-282 | "The software's startup authentication can be disabled by altering a Windows registry setting that any user can modify." |
| CVE-2025-27255 | EnerVista UR Setup 8.42 | 8.0 | CWE-798 | "The local user database is encrypted using an hardcoded password retrievable by an attacker analyzing the application code." |
CVE-2025-27253 is the one to watch on the network side: Nozomi's write-up says the relay does not check client-supplied data for the SSH port-forwarding channel, so it can be made to "redirect the received network traffic to an arbitrary target," a firewall bypass that lives inside the relay itself. The two Setup flaws need local access to a workstation running UR Setup 8.42.
Which advisories and fixed versions followed in 2025 and 2026?
Three primary documents matter, and only one of them is a CISA advisory:
| Date | Document | Covers | Fixed in |
|---|---|---|---|
| 7 Mar 2025 | Nozomi Labs advisories + GE Vernova notice | CVE-2025-27253…27257 | "Latest released version" of UR Setup and UR firmware |
| 22 Jan 2026 | GE Vernova GES-2025-005 | Firmware: CVE-2020-10664 (VxWorks IGMP, 7.5), CVE-2020-28895 (VxWorks calloc, 7.3); UR Setup: zip-slip and DLL hijacking (Dragos) | UR firmware 8.70 (released November 2025), UR Setup 8.70 |
| 17 Feb 2026 | CISA ICSA-26-048-03 | CVE-2026-1762 (DLL hijacking, CWE-427, 7.8) and CVE-2026-1763 (path traversal, CWE-35, 3.3) in UR Setup before 8.70 | UR Setup 8.70 |
Three details from those documents change how you plan the work. First, the GE Vernova link that the 2025 CVE records cite redirects to a login-gated resource library, so the public trail for the Nozomi CVEs is the CVE records and Nozomi's advisories; no CISA advisory for them appears in CISA's CSAF repository. Second, GES-2025-005 narrows the firmware ranges: CVE-2020-10664 applies only to firmware with IEC 61850 order codes at 7.43–7.46, 7.64–7.66, or 7.82 up to 8.62, and only matters if R-GOOSE is used, while CVE-2020-28895 spans 7.00 to 8.62. Third, the same scoring flaw gets different numbers: GE Vernova scores the DLL hijack 4.6 and the zip-slip 2.9 with a physical attack vector, while CISA's CSAF scores them 7.8 and 3.3. The two sources also disagree on which ID is which: GE Vernova's own CVE records on cve.org give CVE-2026-1762 as "Directory Traversal" ("File Manipulation", CWE-23, 2.9) and CVE-2026-1763 as "DLL Hijacking" (4.6), while CISA's CSAF file on GitHub maps CVE-2026-1762 to DLL hijacking (CWE-427, 7.8) and CVE-2026-1763 to path traversal (CWE-35, 3.3). Record both and decide on your own exposure.
GES-2025-005 also states that "UR IEDs version 8.60 and higher validate the firmware file before upgrading." The CVE-2025-27257 record still lists firmware up to 8.60 as affected, so treat 8.70 as the target for both components.
Is there a patch, and what does GE Vernova recommend?
Yes: move EnerVista UR Setup and UR firmware to 8.70 or later. In March 2025 Nozomi advised updating "the EnerVista UR software to the latest 8.60 version" and the N60 firmware "to the newest available release"; GES-2025-005 now recommends firmware 8.70 and UR Setup "8.70 or greater," and notes that UR Setup is backward compatible, so the workstation can be upgraded before the relays.
Both GE Vernova documents add the same compensating controls. GE Vernova's statement in Nozomi's write-up lists "placing the UR inside an electronic security perimeter, deploying and maintaining access controls, robust network monitoring and Intrusion Detection, network segmentation and firewalls." None of the 2025 CVEs is exploitable from the open internet without a foothold, which is what NERC CIP-005's electronic security perimeter is built to deny.
Is 2025 the first time the UR relay family has had serious vulnerabilities disclosed?
No — 2025 is at least the second round. ICSA-21-075-02 (March 2021) lists ten CVEs against UR firmware before 8.10, credited to SCADA-X, DOE's CyTRICS program, Verve Industrial and VuMetric, with GE's fix in firmware 8.10 (GES-2021-004). It includes CVE-2021-27426 (factory mode on the "Basic" security variant, 9.8) and CVE-2021-27430 (unused hard-coded bootloader credentials in versions 7.00–7.02, 8.4). Before that, ICSA-18-046-02 (February 2018) covered the D60 Line Distance Relay, one of the UR models: firmware 7.11 and prior has multiple stack-based buffer overflows that may allow remote code execution (CVE-2018-5475, 9.8 per CISA and NVD), found by Kirill Nesterov of Kaspersky.
One 2021 entry reads like an early version of the 2025 finding. CVE-2021-27428 (9.8) says the UR Setup tool "validates the authenticity and integrity of firmware file before uploading the UR IED," and that "an illegitimate user could upgrade firmware without appropriate privileges." Four years later, CVE-2025-27257 again found signature checking enforced only in the client. A third round followed in early 2026 with GES-2025-005 and ICSA-26-048-03. A recurring pattern like that is what MITRE ATT&CK for ICS and IEC 62351 assume about fielded relays: plan for the next advisory, not only the current one.
Where does OT network monitoring fit?
It is a compensating control for the gap these CVEs expose, not a fix. A relay that cannot refuse a modified image leaves the network as the place to notice a firmware push or a man-in-the-middle. Nozomi's own write-up notes that intrusion detection "can help decrease" the chain's likelihood by spotting techniques "like ARP poisoning." Nozomi, which found the CVEs, also sells Guardian, which learns "a baseline of normal behavior patterns" and flags deviations. Monitoring does not remove a missing SSH host-key check or a hard-coded password; those need the 8.70 updates.
What does a fleet exposure check look like? (worked example)
Synthetic example, not a real site. A utility exports relay and workstation versions from its asset register and checks them against the documents above:
| Asset (synthetic) | Component and version | 2025 Nozomi CVEs | GES-2025-005 / ICSA-26-048-03 | Action |
|---|---|---|---|---|
| Relay A, N60, IEC 61850 order code | Firmware 7.82 | CVE-2025-27253, -27257 | CVE-2020-10664 (if R-GOOSE used), CVE-2020-28895 | Upgrade to 8.70 |
| Relay B, L90 | Firmware 8.62 | Outside 7.0–8.60 | CVE-2020-28895 | Upgrade to 8.70 |
| Relay C, F60 | Firmware 7.02 | CVE-2025-27253, -27257 | CVE-2020-28895; also ICSA-21-075-02 (< 8.10) | Upgrade to 8.70, check bootloader |
| Relay D, T60 | Firmware 8.70 | None | None | Keep, record evidence |
| Workstation 1 | UR Setup 8.42 | CVE-2025-27254, -27255, -27256 | CVE-2026-1762, -1763 | Upgrade to 8.70 first |
| Workstation 2 | UR Setup 8.60 | CVE-2025-27256 | CVE-2026-1762, -1763 | Upgrade to 8.70 |
The order matters: the workstations come first, because UR Setup is backward compatible and is the tool that will carry the new firmware to each relay.
What is a workable starting point?
Inventory every UR relay and every workstation running EnerVista UR Setup, with model, order code, firmware and UR Setup version. Every range above depends on these values. Upgrade EnerVista UR Setup to 8.70 or later first, then schedule relay firmware 8.70 through your normal outage and protection-testing process. Confirm every UR relay sits inside an electronic security perimeter— per NERC CIP-005 for BES Cyber Assets, or an equivalent zone in the Purdue model. Restrict who can reach the relay's SSH serviceto named engineering workstations, since the 2025 chain and CVE-2025-27253 both ride that channel. Put firmware changes under change management, the way NERC CIP-010 requires for in-scope assets, and compare firmware versions after every maintenance visit. Subscribe to the CVE IDs and vendor names, not only to CISA: GE Vernova's own notices and Nozomi's CVE records came out before, or without, a CISA advisory.
What are the common pitfalls?
- Relying on NVD CPE matching. As of 14 November 2026 all five 2025 CVE records sit at NVD status "Deferred" with no CPE configuration, so a CPE-only scanner will not link them to a UR asset (see the NVD backlog guide).
- Patching relays and forgetting the workstation. Three of the five 2025 CVEs and both 2026 CVEs live in EnerVista UR Setup.
- Taking one CVSS score as fact. GE Vernova and CISA score the same 2026 flaws differently.
- Assuming "8.60 is the fix." It was the advice in March 2025; 8.70 is the version that clears every document listed here.
- Treating a monitored network as patched. Detection reduces likelihood; it does not change the firmware.
SoftWSP matches an uploaded component list against NVD, CISA KEV, FIRST EPSS and CISA CSAF ICS advisories, so ICSA-26-048-03 shows up against an EnerVista UR Setup row, while the five 2025 CVEs need a watchlist on the CVE IDs or on the GE Vernova product names because NVD has no CPE data for them. Its OT Snapshot reads a mirror-port capture and lists which hosts open SSH sessions to which relays; it does not read the Modbus inside the SSH tunnel or the relay's firmware version. Each report is an AI-drafted, cited draft that an engineer reviews: see OT Snapshot. For relay protocols on the same bus, see the IEC 61850 security guide and NIST SP 800-82's OT security guidance.
This guide summarizes the CVE and NVD records for CVE-2025-27253 to CVE-2025-27257, Nozomi Networks Labs' write-up and advisories, GE Vernova's GES-2025-005 notice, and CISA's CSAF records for ICSA-26-048-03 and ICSA-21-075-02, each fetched on 14 November 2026. It is not a substitute for GE Vernova's current notices or an engineer's assessment of a specific substation.
Put this guide to work
Frequently asked questions
What is the GE Vernova UR relay family, and what does EnerVista UR Setup do?
GE Vernova's UR (Universal Relay) family is a line of protection, control and monitoring relays for electrical substations, sold under model names including the B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60 — CISA's own ICSA-21-075-02 advisory lists exactly this set as "advanced protection and control relays." The N60 Network Relay, the specific device examined in Nozomi Networks Labs' 2025 research, is one member of that family, built to protect substation equipment by tripping breakers when it detects a fault condition. EnerVista UR Setup is GE Vernova's own Windows client software for configuring a UR relay, monitoring its status and pushing firmware or configuration updates to it — NVD's own advisory text for this research describes it plainly as the vulnerable component in three of the five 2025 CVEs, with the relay's onboard firmware carrying the other two.
What do CVE-2025-27256 and CVE-2025-27257 actually let an attacker do?
They chain together into a credential-theft-to-malicious-firmware attack. NVD's record for CVE-2025-27256 (CVSS v3.1 8.3, CWE-306 Missing Authentication for Critical Function) describes "a missing SSH server authentication" in EnerVista UR Setup (versions 7.0 through 8.60, per the CVE record) that "allows Authentication Bypass," so that "an attacker may perform a man-in-the-middle attack on the network" — Nozomi's own advisory adds that the aim is "to steal credentials or forge malicious traffic." NVD's record for CVE-2025-27257 (CVSS v3.1 6.1, CWE-345 Insufficient Verification of Data Authenticity) describes the second half: "Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware," because "the firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup," not on the relay itself. Nozomi Networks Labs' own write-up states the combined effect directly: "By executing the MITM attack, an attacker can intercept and acquire valid credentials for the GE Vernova N60 Network Relay. With these credentials, and due to the lack of firmware verification, the attacker can then upload malicious firmware to seize control of the device."
What are the other three 2025 CVEs, and are they as serious?
Two affect EnerVista UR Setup and one, CVE-2025-27253, affects UR relay firmware 7.0 to 8.60; the CVE records rate the two Setup flaws High. CVE-2025-27254 (CVSS v3.1 8.0, CWE-282 Improper Ownership Management) is an authentication bypass where, per NVD, "the software's startup authentication can be disabled by altering a Windows registry setting that any user can modify" — no special privileges needed, since the registry key itself isn't locked down. CVE-2025-27255 (CVSS v3.1 8.0, CWE-798 Use of Hard-coded Credentials) is a privilege-escalation flaw where, per NVD, "the local user database is encrypted using an hardcoded password retrievable by an attacker analyzing the application code" — meaning every installation shares the same decryption key. CVE-2025-27253 (CVSS v3.1 6.1, CWE-15 External Control of System or Configuration Setting) lets an attacker "establish a TCP connection through a port forwarding" because of inadequate IP address and port validation, which NVD notes "may allow the attacker to bypass firewall rules or to send malicious traffic in the network." All five were published by NVD on 10 March 2025 and credited to Nozomi Networks Labs' responsible disclosure.
Is there a patch, and what does GE Vernova recommend in the meantime?
Yes. Nozomi Networks Labs' advisory states the fix directly: "Update the EnerVista UR software to the latest 8.60 version and ensure that the N60 firmware is also upgraded to the newest available release" — NVD's reference links point to GE Vernova's own vendor advisory for the authoritative current version, since UR Setup has since moved past 8.60 in subsequent releases addressing unrelated issues. Beyond patching, GE Vernova's statement quoted in Nozomi's write-up recommends standard compensating controls for any IED on this bus: "Placing the UR inside an electronic security perimeter, deploying and maintaining access controls, robust network monitoring and Intrusion Detection, network segmentation and firewalls." None of the five 2025 CVEs requires an unauthenticated remote attacker starting from the open internet — every path assumes the attacker already has network access to the relay's management interface, which is exactly the access an electronic security perimeter is built to deny.
Is 2025 the first time GE's UR relay family has had serious vulnerabilities disclosed?
No. CISA's ICSA-21-075-02, filed four years earlier, covers ten CVEs against the same UR family — including CVE-2021-27426 (Insecure Default Variable Initialization) at CVSS v3 9.8, the maximum practical severity, and CVE-2021-27430 (Use of Hard-coded Credentials) at 8.4. That advisory credits the findings to "SCADA-X, DOE's Cyber Testing for Resilient Industrial Control Systems (CyTRICS) program, Verve Industrial, and VuMetric" and states a UR bootloader binary shipped with "unused hardcoded credentials" through firmware version 7.02. Two independent rounds of CVE disclosures against the same relay family, four years apart and from different researchers (four groups in 2021, Nozomi Networks Labs in 2025), is the kind of repeat pattern that argues for standing compensating controls rather than a one-time patch-and-move-on response.
Sources
- NVD: CVE-2025-27256 — CVSS v3.1 8.3, CWE-306, missing SSH authentication in GE Vernova EnerVista UR Setup
- NVD: CVE-2025-27257 — CVSS v3.1 6.1, CWE-345, client-side-only firmware signature verification on GE Vernova UR IED family devices
- NVD: CVE-2025-27254 — CVSS v3.1 8.0, CWE-282, registry-based startup authentication bypass in EnerVista UR Setup
- NVD: CVE-2025-27255 — CVSS v3.1 8.0, CWE-798, hard-coded local-database decryption password in EnerVista UR Setup
- NVD: CVE-2025-27253 — CVSS v3.1 6.1, CWE-15, unvalidated port-forwarding configuration in GE Vernova UR IED family devices
- Nozomi Networks Labs: "Securing the Grid: Understanding the Cybersecurity Risks of the GE N60 Network Relay" (original disclosure write-up)
- CISA: ICS Advisory ICSA-21-075-02 — GE UR family (9 CVEs, 2021, including CVSS 9.8 CVE-2021-27426)
- Nozomi Networks: Guardian product page (passive network baselining and anomaly detection, industry context for AI-based OT monitoring)
- GE Vernova: Security Notice GES-2025-005 — UR IED and EnerVista UR Setup vulnerabilities fixed in version 8.70 (22 January 2026)
- CISA CSAF: ICSA-26-048-03 — GE Vernova Enervista UR Setup, CVE-2026-1762 and CVE-2026-1763, fixed in 8.70 (17 February 2026)
- CISA CSAF: ICSA-21-075-02 (Update A) — GE UR family, ten CVEs, fixed in UR firmware 8.10
- Nozomi Networks Labs: advisory CVE-2025-27253 — UR IED firmware 7.0 to 8.60, port-forwarding input validation
- Nozomi Networks Labs: advisory CVE-2025-27256 — EnerVista UR Setup 7.0 to 8.60, missing SSH server authentication
- NVD: CVE-2026-1762 — DLL hijacking in GE Vernova EnerVista UR Setup installer