**CVE-2020-10664** is a NULL pointer dereference in the IGMP component of Wind River VxWorks 6.8.3, published by NVD on 2020-04-27 with a CVSS v3.1 score of 7.5 (network denial of service). GE Vernova's notice GES-2025-005 lists it for UR protection relay firmware with IEC 61850 order codes and fixes it in UR firmware 8.70.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
1.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-10664 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Wind River VxWorks | cpe:2.3:o:windriver:vxworks:6.8.3:*:*:*:*:*:*:* | NVD: 6.8.3 (IPNET CVE patches created in 2019) |
| GE Vernova UR relay firmware (IEC 61850 order codes) | — | 7.43 to 7.46, 7.64 to 7.66, and 7.82 up to 8.62; fixed in UR firmware 8.70 (per GE Vernova GES-2025-005) |
What does this mean for affected devices?
NVD's description reads: "The IGMP component in VxWorks 6.8.3 IPNET CVE patches created in 2019 has a NULL Pointer Dereference" (NVD). NVD scores it 7.5 under CVSS v3.1 with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H: network reachable, no privileges, no user interaction, and the impact is availability only. NVD records CWE-476 and a single CPE, VxWorks 6.8.3. The CVE record itself was filed by MITRE with vendor and product "n/a", so the NVD CPE is the only product data in the record, and it does not name any device that ships this VxWorks build.
The device angle comes from GE Vernova. Its security notice GES-2025-005 (initial release 14 December 2025, revised 22 January 2026) states that "the UR firmware is affected by the underlying Wind River VxWorks Real-Time Operating System (RTOS)" and lists CVE-2020-10664 for "UR firmware with IEC61850 order codes", versions 7.43 to 7.46, 7.64 to 7.66, and 7.82 and higher up to 8.62. GE Vernova explains where IGMP matters on a relay: it "is used by UR IEDs in Routable GOOSE (R-GOOSE) applications for managing the membership of the UR relays in a specific multicast group." It adds that "if the R-GOOSE feature is not used by a UR user, this vulnerability will not impact their IED."
GE Vernova handled the flaw in two steps. First, "the R-GOOSE subscription capability was removed in EnerVista Setup version 8.6x." Then, in version 8.70, "the CVE is fixed by applying a patch provided by WindRiver and the R-GOOSE subscription capability was restored in EnerVista Setup version 8.7x." The notice recommends UR firmware 8.70, released in November 2025, and EnerVista UR Setup 8.70 or greater; UR Setup is backward compatible, so the workstation can move first. At publication GE Vernova had no reports of attacks exploiting the vulnerabilities in the notice.
CVE-2020-10664 is not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.014, percentile 72.5, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).
For a UR fleet, the check is the order code, the firmware version and whether R-GOOSE is in use; a relay inside the listed ranges that subscribes to R-GOOSE should go to firmware 8.70. A CPE-only scanner will not connect this CVE to a UR relay, because NVD's configuration names VxWorks 6.8.3 and no GE product. Our GE Vernova UR relay guide covers GES-2025-005 alongside the 2025 Nozomi Networks CVEs, and the IEC 61850 security guide explains GOOSE and R-GOOSE traffic. CVE-2020-28895 is the second VxWorks flaw fixed in the same UR firmware 8.70 release, and the embedded TCP/IP stack guide covers other IPnet flaws.
Evidence
- IGMP component in VxWorks 6.8.3 IPNET CVE patches created in 2019 has a NULL pointer dereference; NVD Primary CVSS v3.1 7.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), v2 5.0; CWE-476; CPE VxWorks 6.8.3; published 2020-04-27. — NVD
- UR firmware is affected via Wind River VxWorks; CVE-2020-10664 affects UR firmware with IEC 61850 order codes 7.43-7.46, 7.64-7.66, 7.82 up to 8.62; IGMP used for R-GOOSE; no impact if R-GOOSE is not used; R-GOOSE subscription removed in Setup 8.6x and restored in 8.7x; fixed in UR firmware 8.70 (released November 2025); no reported attacks at publication. — GE Vernova Security Notice GES-2025-005: UR IED and EnerVista UR Setup vulnerabilities fixed in version 8.70 (PDF)
- Not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). — CISA KEV
- EPSS 0.01377 (percentile 72.5), dataset 2026-11-16, read 2026-11-16. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which GE Vernova UR relays does CVE-2020-10664 affect?
GE Vernova lists UR firmware with IEC 61850 order codes at versions 7.43 to 7.46, 7.64 to 7.66, and 7.82 and higher up to 8.62 (per GE Vernova GES-2025-005).
Is a UR relay that does not use R-GOOSE exposed?
No, according to GE Vernova: IGMP is used for R-GOOSE multicast membership, and "if the R-GOOSE feature is not used by a UR user, this vulnerability will not impact their IED" (per GE Vernova GES-2025-005).
Why does NVD list only VxWorks for CVE-2020-10664?
The CVE record was filed by MITRE with no vendor or product, and NVD's configuration names only Wind River VxWorks 6.8.3; the UR relay link comes from GE Vernova's own notice (per NVD and GE Vernova GES-2025-005).
Is CVE-2020-10664 in the CISA KEV catalog?
No, as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.014, percentile 72.5, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).