**CVE-2021-27430** is a hard-coded credentials flaw in the GE UR protection relay bootloader, versions 7.00 to 7.02: the binary contains unused hard-coded credentials, and someone with physical access can interrupt the boot sequence by rebooting the relay. NVD scores it 6.8 (physical access), while CISA's advisory ICSA-21-075-02 scores it 8.4.
Vulnerability summary
CVSS base score
6.8
Medium severity
EPSS score (FIRST)
0.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-27430 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| GE UR bootloader binary | cpe:2.3:a:ge:ur_bootloader_binary:7.00:*:*:*:*:*:*:* | 7.00, 7.01 and 7.02 (per NVD) |
| GE UR relay family firmware (B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60) | — | Below 8.10; GE recommends UR firmware 8.10 or greater (per CISA ICSA-21-075-02) |
What does this mean for affected devices?
NVD's description reads: "GE UR bootloader binary Version 7.00, 7.01 and 7.02 included unused hardcoded credentials. Additionally, a user with physical access to the UR IED can interrupt the boot sequence by rebooting the UR" (NVD). NVD and CISA both record CWE-798 (use of hard-coded credentials), and NVD's CPEs name the UR bootloader binary at 7.00, 7.01 and 7.02. NVD published the record on 2022-03-23.
The two scores differ only in attack vector. NVD's own CVSS v3.1 score is 6.8 with vector CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, physical access, which matches the description's "user with physical access to the UR IED". CISA scored it 8.4 with AV:L, local access, and CISA's CSAF record carries an SSVC note dated 2026-04-15 of exploitation none and automatable no. For a relay in a locked substation cabinet, the physical vector is the realistic one: the attacker has to stand at the device and power-cycle it, which a protection engineer would see as a relay outage.
CISA published these findings as ICSA-21-075-02, "GE UR Family", on 2021-03-16 and reissued it as Update A on 2026-04-16 to revise the content into its current format (CSAF). The advisory lists ten CVEs and names the affected products: UR B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60, each at firmware below 8.10. It credits SCADA-X, DOE's Cyber Testing for Resilient Industrial Control Systems (CyTRICS) program, Verve Industrial and VuMetric. GE's remedy is to "update their UR devices to UR firmware Version 8.10 or greater", with details in GE publication GES-2021-004, which sits behind a login. GE also recommends "placing UR IED inside the control system network security perimeter" with access controls and intrusion detection, and CISA notes that no known public exploitation specifically targeting these vulnerabilities had been reported to it.
CVE-2021-27430 is not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.0025, percentile 16.3, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).
Firmware 8.10 clears the 2021 advisory, but later UR notices raise the target. GE Vernova's GES-2025-005 fixes two VxWorks flaws in UR firmware up to 8.62 and recommends firmware 8.70, so a relay moved off a pre-8.10 build should go to 8.70. Physical controls matter more for this CVE than for the network ones: lock relay panels, log cabinet access, and alarm on unexpected relay restarts. Our GE Vernova UR relay guide covers this advisory with the later UR notices, and the hard-coded credentials fix guide covers removing build-time secrets from boot code. CVE-2021-27426 and CVE-2021-27428 are two more CVEs from the same advisory.
Evidence
- UR bootloader binary 7.00, 7.01 and 7.02 included unused hard-coded credentials; physical access can interrupt boot by rebooting; NVD Primary CVSS v3.1 6.8 (AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), v2 4.6; CISA secondary 8.4 (AV:L); CWE-798; CPEs ur_bootloader_binary 7.00/7.01/7.02; published 2022-03-23. — NVD
- ICSA-21-075-02 initial 2021-03-16, Update A 2026-04-16; affected UR B30 ... T60 < 8.10; CVSS 8.4 (AV:L); CWE-798; SSVC E:N/A:N 2026-04-15; fix UR firmware 8.10 or greater (GES-2021-004, login required); credits SCADA-X, CyTRICS, Verve Industrial, VuMetric; no known public exploitation reported to CISA. — CISA ICSA-21-075-02 (Update A): GE UR Family (CSAF)
- UR firmware up to 8.62 affected by two VxWorks CVEs; GE Vernova recommends UR firmware 8.70. — GE Vernova Security Notice GES-2025-005: UR IED and EnerVista UR Setup vulnerabilities fixed in version 8.70 (PDF)
- Not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). — CISA KEV
- EPSS 0.00249 (percentile 16.3), dataset 2026-11-16, read 2026-11-16. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Why do NVD and CISA give CVE-2021-27430 different scores?
NVD scores it 6.8 with a physical attack vector (AV:P), CISA 8.4 with a local vector (AV:L); the other metrics match (per NVD and CISA ICSA-21-075-02).
Which bootloader versions contain the hard-coded credentials?
GE UR bootloader binary versions 7.00, 7.01 and 7.02 (per NVD).
What does GE recommend for CVE-2021-27430?
Updating UR devices to firmware 8.10 or greater and placing the UR IED inside the control system network security perimeter with access controls and monitoring (per CISA ICSA-21-075-02).
Is CVE-2021-27430 in the CISA KEV catalog?
No, as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.0025, percentile 16.3, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?