Honeywell's Experion PKS distributed control system, its C300, C200E and ACE controllers, ControlEdge PLCs and RTUs, Experion LX and PlantCruise, and older Excel Web building controllers have published flaws in five main families: memory corruption in the Control Data Access (CDA) layer and server messaging, hard-coded or exposed credentials, missing authentication on firmware and diagnostics functions, file read and write through path traversal, and weak web session handling. The newest set, CISA's ICSA-25-205-03, rates CVE-2025-2523 at 9.4 and is fixed in R520.2 TCU9 Hot Fix 1 or R530 TCU3 Hot Fix 1. None is in CISA's KEV catalog as of 2026-11-22.
Key takeaways
- The CVE record for CVE-2022-30317 calls Experion LX a distributed control system (DCS) that uses the CDA EpicMo protocol for device diagnostics and maintenance.
- Neither CISA's advisories nor Honeywell's public pages give a port for CDA itself, so confirm ports from the Experion Network and Security Planning Guide that Honeywell points customers to, or from a capture.
- CISA's ICSA-25-205-03 was published on 24 July 2025 and updated on 4 August 2025 (Update A, researcher names added).
- CISA's ICSA-24-116-04 of 25 April 2024 lists 16 CVEs reported by Claroty and Armis.
Where do Honeywell Experion and ControlEdge sit in OT networks?
CISA lists the deployment sectors for Honeywell's process products per advisory: chemical, critical manufacturing, energy, healthcare and public health, and water and wastewater for the 2025 Experion PKS advisory, and chemical, critical manufacturing, energy and water and wastewater for the 2024 one. The product names that appear in CISA advisories and Honeywell CVE records fall into four groups:
| Group | Products named in advisories and CVE records | Typical place in the network |
|---|---|---|
| Experion PKS servers and stations | Experion Server and Console Station (CISA's names), Direct Station and Engineering Station (NVD's CPE names), HMIWeb Browser on older releases | Supervisory level: Windows hosts that run the HMI, history and engineering tools and talk to controllers through CDA |
| Experion controllers and I/O | C300 (PCNT02, PCNT05, C300PM), C200 and C200E, ACE (Application Control Environment), Unit Operations Controller (UOC) and vUOC, FIM4 and FIM8, CN100, HCA | Control level: process controllers and interface modules below the servers |
| Other Experion platforms | Experion LX, PlantCruise by Experion, Safety Manager and Safety Manager SC (in the 2024 advisory) | Same layers in smaller DCS installations and safety systems |
| PLC, RTU and building controllers | ControlEdge PLC and RTU; Excel Web XL1000 and XL Web II controllers, also sold as FALCON in the Centraline partner channel | Remote sites, skids and building automation |
The CVE record for CVE-2022-30317 calls Experion LX a distributed control system (DCS) that uses the CDA EpicMo protocol for device diagnostics and maintenance. That is the pattern across the family: one engineering and server layer, built on Windows, that reaches many controllers over a protocol designed for a trusted control network. Safety Manager is in scope of the 2024 advisory but its safety-specific issues belong with the IEC 61511 safety instrumented systems guide. Honeywell's Niagara-based building products have their own advisories and are covered in the Niagara Fox protocol guide.
How are Experion controllers and ControlEdge devices managed?
The management and data paths that the advisories name are the attack paths:
| Path | Products | What the sources say |
|---|---|---|
| Control Data Access (CDA) | Experion PKS servers and controllers, OneWireless WDM | The component with five of the six 2025 CVEs; Honeywell's CVE-2023-5405 record names a "CDA Server process" |
| CDA EpicMo diagnostics | Experion LX controllers | No authentication; the CVE record for CVE-2022-30317, quoting Forescout, gives TCP port 55565 |
| SSH | ControlEdge PLC and RTU | Root login permitted with a hard-coded credential; the CVE record for CVE-2022-30318 gives TCP port 22 |
| eNAP Server service | Experion PKS client tools | Used for firmware uploads to Series-C devices; a crafted packet stops it (CVE-2016-8344) |
| Controller file system | C200, C200E, C300, ACE; Experion controllers and SMSC S300 | File upload, file read and file write flaws in 2021 and 2024 |
| Web and FTP interfaces | Excel Web XL1000 and XL Web II | FTP directory traversal and web URLs that disclose passwords |
Neither CISA's advisories nor Honeywell's public pages give a port for CDA itself, so confirm ports from the Experion Network and Security Planning Guide that Honeywell points customers to, or from a capture. The two port numbers above come from the CVE records, which quote Forescout's OT:ICEFALL research, not from CISA's text. Whatever the port, the BOD 23-02 guide on internet-exposed management interfaces explains how to check exposure from outside instead of trusting the firewall configuration.
What are the 2025 Control Data Access vulnerabilities?
CISA's ICSA-25-205-03 was published on 24 July 2025 and updated on 4 August 2025 (Update A, researcher names added). It credits Demid Uzenkov and Kirill Kutaev of Positive Technologies and says exploitation could result in information exposure, denial of service or remote code execution.
| CVE | Flaw, per CISA and Honeywell | CWE | Score (CVSS v3.1, CISA and Honeywell) |
|---|---|---|---|
| CVE-2025-2520 | Uninitialized variable in the common Epic Platform Analyzer (EPA) communications; uninitialized pointer dereference, denial of service | CWE-457 | 7.5 |
| CVE-2025-2521 | CDA buffer overread from improper index validation, remote code execution | CWE-119 | 8.6 |
| CVE-2025-2522 | CDA buffer reuse that may cause incorrect system behavior | CWE-226 | 6.5 |
| CVE-2025-2523 | CDA integer underflow during subtraction, remote code execution | CWE-191 | 9.4 |
| CVE-2025-3946 | CDA wrong handler, incorrect handling of packets, remote code execution | CWE-430 | 8.2 |
| CVE-2025-3947 | CDA integer underflow, denial of service | CWE-191 | 8.2 |
CISA lists Experion PKS before R520.2 TCU9 Hot Fix 1 and before R530 TCU3 Hot Fix 1 as affected and recommends those updates. Honeywell's CVE records are more specific: they name the C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM and C200E, give the affected releases as 520.1 through 520.2 TCU9 and 530 through 530 TCU3, and write the second fix as 530.1 TCU3 HF1. As of 2026-11-22, NVD lists all six as Deferred, so the only scores are Honeywell's and CISA's.
Four of the six (CVE-2025-2521, -2522, -2523 and -3946) also affect the OneWireless Wireless Device Manager. CISA's ICSA-25-247-01 lists WDM before R322.5 and R331.1 as affected and recommends those releases; the CVE records give 322.1 through 322.4 and 330.1 through 330.3. A plant that updates Experion but not the WDM keeps the same CDA bugs on its wireless gateway. The memory corruption guide explains why integer underflows and overreads in message parsers so often end in code execution.
Honeywell's product security page lists public security notices with their CISA advisory numbers, and says customers of Honeywell Process Solutions products must log in to read the full Security Notifications. Its public table did not list ICSA-25-205-03 when checked on 2026-11-22, although it lists the 2023 and 2024 Experion advisories, so search CISA's advisories as well as Honeywell's page.
What did the 2024 Experion controller and server advisory cover?
CISA's ICSA-24-116-04 of 25 April 2024 lists 16 CVEs reported by Claroty and Armis. Honeywell's product security page calls it "Experion Controller and SMSC S300 Modification Vulnerabilities", rated Critical. The affected releases are Experion PKS before R510.2 HF14, R511.5 TCU4 HF4, R520.1 TCU5 and R520.2 TCU4 HF2; Experion LX and PlantCruise before R511.5 TCU4 HF4, R520.1 TCU5 and R520.2 TCU4 HF2; Safety Manager R15x and R16x up to R162.10; and Safety Manager SC R210.X, R211.1, R211.2 and R212.1. CISA's remediation is to upgrade to the version in Honeywell's Security Notice or CVE record.
The controller-side CVEs:
| CVE | Flaw, per CISA | CISA score | Other scores |
|---|---|---|---|
| CVE-2023-5389 | Modify files on Experion controllers or SMSC S300, which could lead to a malicious application being run | 9.1 | NVD 7.5 |
| CVE-2023-5390 | Read files from Experion controllers or SMSC S300 (absolute path traversal) | 5.3 | NVD 5.3 |
| CVE-2023-5407 | Stack-based overflow in the Experion controller, ControlEdge PLC, Safety Manager or SMSC S300; denial of service or remote code execution | 7.4 | Honeywell 5.9 |
| CVE-2023-5392 | C300 analysis feature returns more memory over the network than required | 7.5 | Honeywell 7.5 |
The server and station CVEs are all memory-safety or message-handling bugs triggered by crafted messages. CISA scores CVE-2023-5395, -5397, -5400, -5401, -5403 and -5404 (stack and heap overflows, pointer overwrite and hostname manipulation) at 8.1; CVE-2023-5393 at 8.1 and CVE-2023-5394 and -5396 at 7.4 (stack overflows in hostname handling); CVE-2023-5406 at 5.9 (an out-of-bounds write that a crafted message from a controller can trigger on the server); CVE-2023-5398 at 5.9 (heap corruption from a list of IPs); and CVE-2023-5405 at 5.3 (a CDA Server process memory leak). Honeywell's own scores differ on three of these: 7.4 for CVE-2023-5393, 5.9 for CVE-2023-5405 and 5.9 for CVE-2023-5407.
Two discrepancies matter for asset matching. Honeywell's CVE records for CVE-2023-5389 and CVE-2023-5390 name the ControlEdge VirtualUOC and ControlEdge UOC, while CISA's text names Experion controllers and the SMSC S300; NVD's configuration follows the CVE record and lists only UOC and vUOC firmware. And all but two of the 16 are Deferred in NVD as of 2026-11-22, with no CPE configuration, so a scanner that relies on CPE matching will miss most of the advisory.
What did the 2023 Experion R520.2 advisory fix?
CISA's ICSA-23-194-06 of 13 July 2023 covers nine CVEs reported by Armis in Experion PKS, LX and PlantCruise before R520.2, with Honeywell's notice SN2023-06-22. CISA's fix is R520.2 for all three platforms, and it also asks users to keep Experion backup files in a location with access limited to authorized users.
| CVE | Flaw, per CISA | CISA score (CVSS v3.0) | NVD score (CVSS v3.1) |
|---|---|---|---|
| CVE-2023-23585 | Heap overflow in Experion Server or Console Station during a configuration operation | 9.8 | 7.5 |
| CVE-2023-25078 | Stack overflow in Experion Server or Console Station; denial of service or remote code execution | 9.8 | 7.5 |
| CVE-2023-22435 | Incorrect comparison in Experion Server; denial of service | 9.8 | 7.5 |
| CVE-2023-24474 | Heap overflow in Experion Server; denial of service | 9.8 | 7.5 |
| CVE-2023-25948 | C300 leaks configuration data when an error is generated | 9.8 | 7.5 |
| CVE-2023-24480 | C300 stack overflow when decoding a message from the server | 9.8 | 7.5 |
| CVE-2023-25770 | C300 buffer overflow when an error is generated | 9.8 | 7.5 |
| CVE-2023-26597 | C300 buffer overflow in message handling; denial of service | 7.5 | 7.5 |
| CVE-2023-25178 | C300 may be loaded with malicious firmware, enabling remote code execution | 7.5 | 9.8 |
CISA's 9.8 for most entries is much higher than NVD's analysis, and CVE-2023-25178 runs the other way, so record both scores. NVD's C300 configuration lists firmware 501.1 through 501.6 HF8, 510.1 through 510.2 HF12, 511.1 through 511.5 TCU3, 520.1 through 520.1 TCU4 and 520.2 through 520.2 TCU2 as affected, so a C300 on early R520.2 updates is still in range. Treat "R520.2" as a release family and check the TCU level against Honeywell's notice.
Which hard-coded credential and authentication flaws affect ControlEdge and Experion LX?
The 2022 Forescout research known as OT:ICEFALL produced two Honeywell advisories on the same day, 30 August 2022, both crediting Daniel dos Santos and Jos Wetzels:
- ControlEdge, CVE-2022-30318. CISA's ICSA-22-242-06 says the root credentials are hard-coded and not changed automatically when the device is first commissioned, so an attacker with SSH access can gain full control. The CVE record names SSH on TCP port 22 for the ControlEdge PLC and RTU. CISA and NVD score it 9.8 (CVSS v3). Honeywell fixed it in version 151.2; NVD's configuration lists PLC and RTU firmware before R151.2.
- Experion LX, CVE-2022-30317. CISA's ICSA-22-242-07 says the CDA EpicMo protocol has no authentication, so an attacker who can reach it can manipulate firmware or cause a denial of service. CISA and NVD score it 9.1. CISA lists all versions as affected. Experion LX R520.1 adds secure boot and signed firmware images, and R501.6, R511.5 and R520 add a secure lock that restricts all firmware downloads to process controllers while the lock is invoked.
Two earlier advisories belong to the same family. CISA's ICSA-21-278-04 of 5 October 2021, reported by Rei Henigman and Nadav Erez of Claroty, covers all versions of the C200, C200E, C300 and ACE controllers:
| CVE | Flaw | CISA score | NVD score |
|---|---|---|---|
| CVE-2021-38397 | Unrestricted file upload, remote code execution | 10.0 | 10.0 |
| CVE-2021-38395 | Improper neutralization of special elements in output, remote code execution | 9.1 | 9.8 |
| CVE-2021-38399 | Relative path traversal to unauthorized files and directories | 7.5 | 7.5 |
CISA names no fixed version for these three. Honeywell's mitigation is to follow all guidance in the Experion Network and Security Planning Guide, with details in support document SN2021-02-22-01.
CISA's ICSA-20-175-02 of 23 June 2020, reported by Nikolay Sklyarenko of Kaspersky, covers ControlEdge PLC R130.2, R140, R150 and R151 and ControlEdge RTU R101, R110, R140, R150 and R151. CVE-2020-10628 exposes unencrypted passwords on the network and CVE-2020-10624 exposes a session token. CISA scores both 5.9 and NVD 7.5. The fix is a configuration procedure in Honeywell's SN2020-04-17-01, "ControlEdge PLC and RTU Secure Communication", which requires a login.
The guide to hard-coded credentials in embedded firmware explains why one extracted root password then works on every unit of the same firmware.
Which older Experion and Excel Web flaws still matter?
Long plant lifetimes keep old Experion releases in service. These advisories cover releases that may still be running:
| Advisory | Product and CVEs | Affected and fixed | Scores |
|---|---|---|---|
| CISA ICSA-14-352-01 | Experion PKS: CVE-2014-9187 heap overflows; CVE-2014-9189 stack overflows; CVE-2014-5435 arbitrary memory write in dual_onsrv.exe; CVE-2014-5436 directory traversal and CVE-2014-9186 file inclusion in confd.exe | R40x before R400.6, R41x before R410.6, R43x before R430.2; Experion Update Patch R400.6, R410.6 or R430.2 | NVD 9.8, 9.8, 9.8, 7.5, 9.8 (CVSS v3.0) |
| CISA ICSA-15-272-01 | Experion PKS 310.x and earlier: CVE-2007-6483, directory traversal in the bundled SafeNet Sentinel Protection Server | Update to a supported Experion release; the vulnerable service stays installed, so keep the Windows firewall enabled | NVD 5.0 (CVSS v2); CISA CSAF 9.4 |
| CISA ICSA-16-301-01 | Experion PKS 3xx and earlier, 400, 410, 430 and 431: CVE-2016-8344, a crafted packet stops the process and prevents firmware uploads to Series-C devices | R400.8 HOTFIX1, R410.8 HOTFIX6, R430.5 HOTFIX1, R431.2 HOTFIX2; otherwise isolate or stop the eNAP Server service when not uploading firmware | NVD 3.7 (CVSS v3.0) |
| CISA ICSA-12-150-01 | Experion R2xx, R30x, R31x and R400.x: CVE-2012-0254, stack overflow in the HMIWeb Browser HSCDSPRenderDLL ActiveX control | Honeywell notice SN 2012 03 09 01A; do not use a Station node to browse the internet | NVD 7.5 (CVSS v2) |
On the building side, CISA's ICSA-15-076-02 covers CVE-2015-0984, a directory traversal in the FTP server of Excel Web XL1000 controllers before 2.04.01 that lets a remote attacker read files under the web root and obtain administrative login access (NVD 10.0, CVSS v2). The fix is Excel Web Linux 2.04.01 with the CARE programming tool 10.02, both from March 2014. CISA notes that Excel Web controllers were also sold as FALCON through Centraline partners. CISA's ICSA-17-033-01, reported by Maxim Rupp, covers XL Web II controllers (XL1000C500 XLWebExe 2-01-00 and earlier, XLWeb 500 XLWebExe 1-02-08 and earlier), fixed in version 3.04.05.05:
- CVE-2017-5139: any user can disclose a password through a specific URL (NVD 9.8).
- CVE-2017-5140: password stored in clear text (NVD 9.8).
- CVE-2017-5141: session fixation, new sessions do not invalidate existing identifiers (NVD 6.0).
- CVE-2017-5142: a low-privileged user can change parameters through a specific URL (NVD 9.1).
- CVE-2017-5143: unauthenticated directory traversal through a specific URL (NVD 8.6).
CISA's CSAF record for ICSA-17-033-01 gives 8.6 for all five while its own text says 9.8 for two of them, so use NVD's per-CVE scores. The path traversal guide covers the traversal pattern behind CVE-2015-0984, CVE-2017-5143 and the confd.exe flaw. If the same building network carries BACnet, the BACnet protocol security guide covers that traffic.
Are Honeywell Experion vulnerabilities exploited in the wild?
No Honeywell CVE is in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries, no Honeywell vendor entry). ICSA-23-194-06, ICSA-24-116-04 and ICSA-25-205-03 all say no known public exploitation specifically targeting these vulnerabilities has been reported to CISA, and the 2020, 2021 and 2022 advisories say no known public exploits specifically target them.
FIRST EPSS scores dated 2026-11-21, the latest as of 2026-11-22:
| CVE | Product | EPSS | Percentile |
|---|---|---|---|
| CVE-2007-6483 | SafeNet Sentinel server bundled with Experion PKS 310.x | 0.10361 | 0.958 |
| CVE-2015-0984 | Excel Web XL1000 | 0.05612 | 0.931 |
| CVE-2014-9189 | Experion PKS R40x to R43x | 0.05234 | 0.927 |
| CVE-2014-5436 | Experion PKS confd.exe | 0.04199 | 0.912 |
| CVE-2012-0254 | HMIWeb Browser | 0.04083 | 0.910 |
| CVE-2022-30318 | ControlEdge PLC and RTU | 0.01900 | 0.802 |
| CVE-2021-38397 | C200, C200E, C300, ACE | 0.01211 | 0.692 |
| CVE-2022-30317 | Experion LX | 0.00940 | 0.618 |
| CVE-2025-2523 | Experion PKS CDA | 0.00790 | 0.572 |
| CVE-2023-5389 | Experion controllers | 0.00779 | 0.568 |
| CVE-2020-10628 | ControlEdge PLC and RTU | 0.00743 | 0.556 |
| CVE-2023-24480 | C300 | 0.00718 | 0.548 |
| CVE-2025-2521 | Experion PKS CDA | 0.00502 | 0.438 |
The top entry is a third-party licensing service, and the next four are a decade old. The 2023 to 2025 CDA and controller flaws score low, but EPSS predicts exploitation activity; it says nothing about how easy a controller is to reach once someone is on the control network. Rank by reachability first, as the KEV and EPSS prioritization guide explains: a C300 reachable from the business network matters more than any of these numbers.
How should Experion and ControlEdge systems be hardened?
The steps below come from CISA's advisories and Honeywell's recommendations:
Move Experion PKS to R520.2 TCU9 Hot Fix 1 or R530 TCU3 Hot Fix 1That fixes the 2025 CDA set and is later than the 2024 fix level (R520.2 TCU4 HF2) and the 2023 target (R520.2). Check each controller type named in the CVE records, not only the servers. Update OneWireless WDM to R322.5 or R331.1where it is deployed, since it shares four CDA CVEs. Move ControlEdge PLCs and RTUs to 151.2 or laterand apply the secure communication procedure from SN2020-04-17-01, so root SSH credentials are no longer hard-coded and passwords and session tokens do not cross the network in clear text. Use secure boot, signed firmware and secure lock on Experion LXR520.1 adds signed firmware images; on R501.6, R511.5 and R520, invoke the secure lock so firmware downloads to process controllers are blocked except during scheduled changes. Follow the Experion Network and Security Planning Guidefor the C200, C200E, C300 and ACE flaws, which CISA lists without a fixed version. Protect backups and engineering filesCISA's 2023 advisory asks users to store Experion backup files where only authorized users can reach them and not to share them. Retire unsupported releases and devicesIn ICSA-14-352-01 Honeywell already urged customers on releases before R400 to upgrade, and Excel Web controllers below 2.04.01 and XL Web II below 3.04.05.05 need replacement or an update. Segment and firewallCISA asks owners to keep control system devices off the internet, put them behind firewalls isolated from business networks, follow least privilege and use VPNs for remote access. Zone servers, controllers and safety systems with the Purdue model.
How do you check which release an Experion system runs?
Honeywell fixes arrive as release, TCU (update) and hot fix levels, so record each node in detail:
Record the release, TCU and hot fix on every server and station"R520.2" alone does not tell you whether the 2024 fix (TCU4 HF2) or the 2025 fix (TCU9 HF1) is installed. Record controller firmware separatelyNVD's C300 configuration for the 2023 CVEs lists firmware ranges per release, and the 2025 CVE records name nine controller and interface module types. Record ControlEdge PLC and RTU firmwareReleases before R151.2 carry the hard-coded SSH credential. Record OneWireless WDM, Safety Manager and Safety Manager SC releasesThe 2024 and 2025 advisories reach beyond Experion PKS itself. Do not rely on CPE matching aloneAs of 2026-11-22, NVD has no CPE configuration for the 2025 CDA CVEs or for 14 of the 16 CVEs from 2024, and its CVE-2023-5389 configuration names only ControlEdge UOC and vUOC. Read the advisory, as the IEC 62443-2-3 patch management guide describes for vendor-tracked patching.
How do you monitor Experion and ControlEdge networks?
Start with a baseline of which hosts talk to each controller and server, and on which ports, then alert on changes:
- New hosts talking to C300, C200E, UOC or ACE controllers, since every CDA flaw needs a crafted message from the network.
- TCP connections to port 55565 on Experion LX controllers from anything other than the engineering and server nodes, which fits CVE-2022-30317.
- SSH sessions to ControlEdge PLCs and RTUs, especially from outside the engineering subnet, which fits CVE-2022-30318.
- Large or unexpected transfers to controllers outside scheduled maintenance windows, which fits the firmware manipulation in CVE-2022-30317 and CVE-2023-25178.
- FTP or web access to Excel Web controllers from outside the building management network.
Flow records show who connected to which port and when, not which CDA function was invoked. Map alerts to MITRE ATT&CK for ICS techniques such as program download and remote services.
Worked example: what does a review of a chemical plant find?
Synthetic example, not a real site. A chemical plant runs Experion PKS with C300 controllers, two ControlEdge RTUs at a tank farm and an older Excel Web controller for the control building HVAC.
| Observation | Why it matters | Action |
|---|---|---|
| Experion PKS servers on R520.2 TCU4 HF2 | Fixes the 2024 advisory but not the 2025 CDA flaws (CVE-2025-2523 and others) | Install R520.2 TCU9 Hot Fix 1 |
| C300 PCNT05 controllers on the same release | Named in the 2025 CVE records | Update controller firmware with the server release |
| OneWireless WDM on R322.3 | Shares four CDA CVEs | Update to R322.5 |
| ControlEdge RTUs on R151.1, SSH reachable from the plant network | Hard-coded root credential (CVE-2022-30318) | Update to 151.2 or later; restrict SSH to the engineering subnet |
| Excel Web XL1000 on 2.03 firmware, FTP enabled | Directory traversal to admin login (CVE-2015-0984) | Update to 2.04.01 with CARE 10.02 or replace; disable FTP where it is not used |
| Experion backups on a shared file server | CISA's 2023 advisory asks for restricted backup storage | Move backups to an access-controlled location |
Where does passive monitoring fit in a Honeywell review?
A passive capture shows who talks to controllers and servers without logging in to anything. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from a mirror-port recording and builds a host-by-port inventory at connection level, including hosts using TCP 55565, SSH, FTP and web ports, and lists remote-access sessions that cross from outside the private address range. It does not decode CDA or EpicMo messages or read Experion releases from traffic, so those come from the asset list. For that list, Device & Firmware Security identifies components and versions and matches them against NVD, CISA KEV, FIRST EPSS and CISA ICS advisories. An engineer reviews every AI-drafted, cited report before it is sent.
What are the common pitfalls?
- Treating "R520.2" as fixed, when the 2024 and 2025 advisories need specific TCU and hot fix levels within it.
- Updating Experion servers but not controller firmware, or not the OneWireless WDM that shares the CDA code.
- Relying on a CPE-based scanner, when most 2024 and 2025 Honeywell CVEs have no NVD configuration.
- Assuming CISA's score is the only one: for the 2023 set CISA says 9.8 where NVD says 7.5, and for CVE-2023-5407 Honeywell says 5.9 where CISA says 7.4.
- Leaving ControlEdge SSH reachable from the plant network after the update, or leaving Experion LX secure lock off between maintenance windows.
- Keeping an old Excel Web or XL Web II controller on the network because it still runs the HVAC.
This guide draws on CISA ICS advisories ICSA-25-205-03, ICSA-25-247-01, ICSA-24-116-04, ICSA-23-194-06, ICSA-22-242-06, ICSA-22-242-07, ICSA-21-278-04, ICSA-20-175-02, ICSA-16-301-01, ICSA-15-272-01, ICSA-15-076-02, ICSA-14-352-01, ICSA-17-033-01 and ICSA-12-150-01 and their CSAF records; Honeywell's product security page and CVE records; NVD records; the CISA KEV catalog; and FIRST EPSS data. KEV and EPSS facts are as of 2026-11-22. It is general information, not a substitute for Honeywell's Security Notifications or a check of your exact releases, TCU and hot fix levels.
Put this guide to work
Frequently asked questions
What are the 2025 Experion PKS Control Data Access vulnerabilities?
CISA's ICSA-25-205-03 of 24 July 2025 (Update A, 4 August 2025) covers six CVEs reported by Demid Uzenkov and Kirill Kutaev of Positive Technologies. Five are in the Control Data Access (CDA) component: a buffer overread (CVE-2025-2521, 8.6), buffer reuse (CVE-2025-2522, 6.5), two integer underflows (CVE-2025-2523, 9.4, and CVE-2025-3947, 8.2) and a wrong-handler flaw (CVE-2025-3946, 8.2). The sixth, CVE-2025-2520 (7.5), is an uninitialized variable in Epic Platform Analyzer (EPA) communications. All scores are CVSS v3.1 from CISA and Honeywell. Honeywell's CVE records name the C300 PCNT02 and PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM and C200E as affected.
Which Experion PKS release fixes the CDA flaws?
CISA lists Experion PKS R520.2 TCU9 Hot Fix 1 and R530 TCU3 Hot Fix 1. Honeywell's CVE records say the affected releases run from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3, and name the fixes as 520.2 TCU9 HF1 and 530.1 TCU3 HF1. Four of the six CVEs also affect the OneWireless Wireless Device Manager, which CISA's ICSA-25-247-01 says is fixed in R322.5 or R331.1.
What is the ControlEdge hard-coded credential flaw?
CVE-2022-30318, from Forescout's research and CISA's ICSA-22-242-06 of 30 August 2022, is a hard-coded root credential in ControlEdge PLC and RTU firmware that is not changed when the device is first commissioned, so an attacker with SSH access can take full control. The CVE record, quoting Forescout's FSCT-2022-0056, says the SSH service listens on TCP port 22 and allows root login. CISA and NVD both score it 9.8 (CVSS v3). Honeywell fixed it in ControlEdge 151.2 and later.
Are any Honeywell Experion or ControlEdge vulnerabilities in the CISA KEV catalog?
No. As of 2026-11-22, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.20, 1,790 entries) has no Honeywell entry at all. CISA's 2023, 2024 and 2025 Experion advisories say no known public exploitation specifically targeting these vulnerabilities has been reported to CISA. The highest FIRST EPSS score among the Honeywell-specific CVEs in this guide is 0.05612 for CVE-2015-0984 in Excel Web controllers.
Where are Honeywell's security notifications for Experion?
Honeywell's public product security page lists security notices with their CISA advisory numbers, but for Honeywell Process Solutions products such as Experion and ControlEdge it says customers must log in to read the Security Notifications. CISA advisories cite them by number, for example SN2023-06-22 for the R520.2 fixes, SN2021-02-22-01 for the C200, C300 and ACE controller flaws and SN2020-04-17-01 for ControlEdge secure communication. Without a login, the CISA advisory and the CVE record are the public sources.
Sources
- Honeywell: Product Security (security notices and PSIRT)
- CISA CSAF: ICSA-25-205-03 Honeywell Experion PKS (Update A)
- CISA: ICSA-25-205-03 Honeywell Experion PKS (web page)
- CISA CSAF: ICSA-25-247-01 Honeywell OneWireless Wireless Device Manager (WDM)
- CISA CSAF: ICSA-24-116-04 Honeywell Experion PKS, Experion LX, PlantCruise by Experion, Safety Manager, Safety Manager SC
- CISA CSAF: ICSA-23-194-06 Honeywell Experion PKS, LX and PlantCruise
- CISA CSAF: ICSA-22-242-06 Honeywell ControlEdge
- CISA CSAF: ICSA-22-242-07 Honeywell Experion LX
- CISA CSAF: ICSA-21-278-04 Honeywell Experion PKS and ACE Controllers
- CISA CSAF: ICSA-20-175-02 Honeywell ControlEdge PLC and RTU
- CISA CSAF: ICSA-16-301-01 Honeywell Experion PKS Improper Input Validation Vulnerability
- CISA CSAF: ICSA-15-272-01 Honeywell Experion PKS Directory Traversal Vulnerability
- CISA CSAF: ICSA-14-352-01 Honeywell Experion PKS Vulnerabilities
- CISA CSAF: ICSA-12-150-01 Honeywell HMIWeb Browser Buffer Overflow Vulnerability
- CISA CSAF: ICSA-15-076-02 Honeywell XL Web Controller Directory Traversal Vulnerability
- CISA CSAF: ICSA-17-033-01 Honeywell XL Web II Controller Vulnerabilities
- NVD: CVE-2025-2523 (Experion PKS CDA integer underflow)
- NVD: CVE-2025-2521 (Experion PKS CDA buffer overread)
- NVD: CVE-2023-5389 (Experion controller file modification)
- NVD: CVE-2023-5407 (controller stack-based buffer overflow)
- NVD: CVE-2023-23585 (Experion server heap overflow)
- NVD: CVE-2023-25178 (C300 firmware authenticity)
- NVD: CVE-2022-30317 (Experion LX CDA EpicMo missing authentication)
- NVD: CVE-2022-30318 (ControlEdge hard-coded SSH root credentials)
- NVD: CVE-2021-38397 (C200, C200E, C300 and ACE unrestricted file upload)
- NVD: CVE-2020-10628 (ControlEdge unencrypted passwords on the network)
- NVD: CVE-2014-9189 (Experion PKS stack-based buffer overflows)
- NVD: CVE-2016-8344 (Experion PKS eNAP input validation)
- NVD: CVE-2017-5142 (XL Web II improper privilege management)
- CISA Known Exploited Vulnerabilities catalog
- FIRST: Exploit Prediction Scoring System (EPSS)
About this guide
SoftWSP OT/ICS Desk
Covers the OT/ICS security cluster: 87 guides.

In this cluster