**CVE-2021-27428** is a firmware upgrade flaw in GE UR protection relays before firmware 8.10: the EnerVista UR Setup tool, not the relay, validated firmware files, so an illegitimate user could upgrade firmware without appropriate privileges. NVD and CISA both score it 9.8 (CVSS v3.1), and CISA advisory ICSA-21-075-02 names 19 UR relay models.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-27428 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| GE UR relay family firmware (B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60) | — | Firmware below 8.10; mitigation implemented in 8.10 (per NVD and CISA ICSA-21-075-02; NVD CPEs cover multilin_<model>_firmware < 8.10 for all 19 models) |
What does this mean for affected devices?
NVD's description reads: "GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate user could upgrade firmware without appropriate privileges. The weakness is assessed, and mitigation is implemented in firmware Version 8.10" (NVD). NVD scores it 9.8 under CVSS v3.1 with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, the same score CISA submitted, and 7.5 under CVSS v2. NVD and CISA both record CWE-434 (unrestricted upload of file with dangerous type). NVD published the record on 2022-03-23, and its CPE configuration covers the firmware of all 19 UR models below 8.10.
The weakness is where the check lives. When the authenticity and integrity check runs in the engineering tool, anyone who talks to the relay without that tool skips it. A relay that accepts a firmware image controls protection logic and breaker tripping, so a replaced image is a full compromise of the device.
CISA published these findings as ICSA-21-075-02, "GE UR Family", on 2021-03-16 and reissued it as Update A on 2026-04-16 to revise the content into its current format (CSAF). The advisory lists ten CVEs and names the affected products: UR B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60, each at firmware below 8.10. It credits SCADA-X, DOE's Cyber Testing for Resilient Industrial Control Systems (CyTRICS) program, Verve Industrial and VuMetric. GE's remedy is to "update their UR devices to UR firmware Version 8.10 or greater", with details in GE publication GES-2021-004, which sits behind a login. GE also recommends "placing UR IED inside the control system network security perimeter" with access controls and intrusion detection, and CISA notes that no known public exploitation specifically targeting these vulnerabilities had been reported to it.
CVE-2021-27428 is not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.012, percentile 68.9, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).
Firmware 8.10 clears the 2021 advisory, but later UR notices raise the target. GE Vernova's GES-2025-005 fixes two VxWorks flaws in UR firmware up to 8.62 and recommends firmware 8.70, so a relay moved off a pre-8.10 build should go to 8.70. The same pattern came back in 2025: CVE-2025-27257 again found firmware signature checks enforced only in EnerVista UR Setup, through firmware 8.60, and GES-2025-005 states that "UR IEDs version 8.60 and higher validate the firmware file before upgrading." Our GE Vernova UR relay guide compares the two findings, and the secure boot and root of trust guide explains device-side image verification. CVE-2021-27426 and CVE-2021-27430 are two more CVEs from the same advisory.
Evidence
- UR IED firmware before 8.1x: EnerVista UR Setup validates firmware authenticity and integrity before upload; illegitimate user could upgrade firmware without appropriate privileges; mitigation in 8.10; NVD Primary CVSS v3.1 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), v2 7.5; CWE-434; CPEs multilin_<model>_firmware < 8.10 for 19 models; published 2022-03-23. — NVD
- ICSA-21-075-02 initial 2021-03-16, Update A 2026-04-16; affected UR B30 ... T60 < 8.10; CVSS 9.8; CWE-434; fix UR firmware 8.10 or greater (GES-2021-004, login required); credits SCADA-X, CyTRICS, Verve Industrial, VuMetric; no known public exploitation reported to CISA. — CISA ICSA-21-075-02 (Update A): GE UR Family (CSAF)
- UR IEDs version 8.60 and higher validate the firmware file before upgrading; GE Vernova recommends UR firmware 8.70. — GE Vernova Security Notice GES-2025-005: UR IED and EnerVista UR Setup vulnerabilities fixed in version 8.70 (PDF)
- Not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). — CISA KEV
- EPSS 0.0121 (percentile 68.9), dataset 2026-11-16, read 2026-11-16. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which GE UR relays are affected by CVE-2021-27428?
CISA lists UR B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60 at firmware below 8.10 (per CISA ICSA-21-075-02).
What does CVE-2021-27428 let an attacker do?
Per NVD, the firmware check ran in the EnerVista UR Setup tool, and "an illegitimate user could upgrade firmware without appropriate privileges" (per NVD).
Did firmware 8.10 end the firmware verification problem?
It fixed CVE-2021-27428, but CVE-2025-27257 later reported client-side-only signature checks through firmware 8.60, and GE Vernova states that UR IEDs from 8.60 validate the firmware file; it recommends firmware 8.70 (per NVD and GE Vernova GES-2025-005).
Is CVE-2021-27428 in the CISA KEV catalog?
No, as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.012, percentile 68.9, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).