Security Advisory

CVE-2021-27426: GE UR Relay Factory Mode Always On

Last updated:
  • CVE-2021-27426

**CVE-2021-27426** is a flaw in GE UR protection relay firmware before 8.10: with the "Basic" security variant, the "Factory Mode" used to service the relay cannot be disabled. NVD and CISA both score it 9.8 (CVSS v3.1), and CISA advisory ICSA-21-075-02 names 19 UR relay models as affected.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2021-27426 · Source: NVD

Affected components

ComponentCPEVersion range
GE UR relay family firmware (B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60)—Firmware below 8.10 with the "Basic" security variant; fixed in 8.10 (per CISA ICSA-21-075-02; NVD CPEs cover multilin_<model>_firmware < 8.10 for all 19 models)

What does this mean for affected devices?

NVD's description reads: "GE UR IED firmware versions prior to version 8.1x with 'Basic' security variant does not allow the disabling of the 'Factory Mode,' which is used for servicing the IED by a 'Factory' user" (NVD). NVD scores it 9.8 under CVSS v3.1 with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, the same score CISA submitted, and 7.5 under CVSS v2. CISA classes the weakness as CWE-453 (insecure default variable initialization); NVD's own entry is NVD-CWE-Other. NVD published the record on 2022-03-23, a year after CISA's advisory, and its CPE configuration covers the firmware of all 19 UR models below 8.10.

The condition is narrow: it applies to relays ordered with the "Basic" security variant, where a servicing mode for a "Factory" user stays available and the owner has no setting to turn it off. NVD's network vector with no privileges reflects that an attacker who reaches the relay does not need the owner's credentials for that path. CISA's CSAF record carries an SSVC note dated 2026-04-15 of exploitation none and automatable yes.

CISA published these findings as ICSA-21-075-02, "GE UR Family", on 2021-03-16 and reissued it as Update A on 2026-04-16 to revise the content into its current format (CSAF). The advisory lists ten CVEs and names the affected products: UR B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60, each at firmware below 8.10. It credits SCADA-X, DOE's Cyber Testing for Resilient Industrial Control Systems (CyTRICS) program, Verve Industrial and VuMetric. GE's remedy is to "update their UR devices to UR firmware Version 8.10 or greater", with details in GE publication GES-2021-004, which sits behind a login. GE also recommends "placing UR IED inside the control system network security perimeter" with access controls and intrusion detection, and CISA notes that no known public exploitation specifically targeting these vulnerabilities had been reported to it.

CVE-2021-27426 is not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.012, percentile 68.9, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).

Firmware 8.10 clears the 2021 advisory, but later UR notices raise the target. GE Vernova's GES-2025-005 fixes two VxWorks flaws in UR firmware up to 8.62 and recommends firmware 8.70, so a relay moved off a pre-8.10 build should go to 8.70. Until then, check which relays use the Basic security variant and keep their management ports reachable only from named engineering workstations. Our GE Vernova UR relay guide puts this advisory next to the 2025 and 2026 UR CVEs, and the authentication bypass fix guide covers service and debug modes. CVE-2021-27428 and CVE-2021-27430 are two more CVEs from the same advisory.

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • UR IED firmware before 8.1x with Basic security variant does not allow disabling Factory Mode; NVD Primary CVSS v3.1 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), v2 7.5; CISA CWE-453, NVD NVD-CWE-Other; CPEs multilin_<model>_firmware < 8.10 for 19 models; published 2022-03-23. — NVD
  • ICSA-21-075-02 initial 2021-03-16, Update A 2026-04-16; affected UR B30 ... T60 < 8.10; CVSS 9.8; CWE-453; SSVC E:N/A:Y 2026-04-15; fix UR firmware 8.10 or greater (GES-2021-004, login required); credits SCADA-X, CyTRICS, Verve Industrial, VuMetric; no known public exploitation reported to CISA. — CISA ICSA-21-075-02 (Update A): GE UR Family (CSAF)
  • UR firmware up to 8.62 affected by two VxWorks CVEs; GE Vernova recommends UR firmware 8.70. — GE Vernova Security Notice GES-2025-005: UR IED and EnerVista UR Setup vulnerabilities fixed in version 8.70 (PDF)
  • Not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). — CISA KEV
  • EPSS 0.0121 (percentile 68.9), dataset 2026-11-16, read 2026-11-16. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-21-075-02 (Update A): GE UR Family (CSAF)
  3. GE Vernova Security Notice GES-2025-005: UR IED and EnerVista UR Setup vulnerabilities fixed in version 8.70 (PDF)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which GE UR relays are affected by CVE-2021-27426?

CISA lists UR B30, B90, C30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60 at firmware below 8.10; the flaw applies to the "Basic" security variant (per CISA ICSA-21-075-02 and NVD).

What fixes CVE-2021-27426?

GE recommends UR firmware 8.10 or greater (per CISA ICSA-21-075-02). GE Vernova's later notice recommends firmware 8.70 for two further VxWorks flaws (per GE Vernova GES-2025-005).

Why does CVE-2021-27426 score 9.8?

NVD and CISA both rate it network reachable with no privileges or user interaction and high impact on confidentiality, integrity and availability, vector AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (per NVD).

Is CVE-2021-27426 in the CISA KEV catalog?

No, as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.012, percentile 68.9, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).