Schneider Electric HMI, SCADA and engineering software vulnerabilities: Operator Terminal Expert, Vijeo Designer, Control Expert, Machine Expert, Geo SCADA, Citect and Pro-face

Last updated:

Schneider Electric's HMI, SCADA and engineering software (EcoStruxure Operator Terminal Expert, Vijeo Designer, Control Expert, Machine Expert, Geo SCADA Expert, the older Citect line and Pro-face GP-Pro EX) had no CVE in CISA's KEV catalog as of 2026-11-28. Their published flaws cluster in malicious project files that corrupt memory or escape paths, hard-coded or weakly stored credentials, unauthenticated transfer and database services, and DLL or privilege weaknesses on Windows workstations. Fixes arrive as service packs, hotfixes and monthly server builds.

This guide covers the software layer: the HMI designers and runtimes, the PLC programming suites as Windows applications, and the SCADA servers. The controller side of Control Expert, meaning UMAS sessions, reservations and Modicon firmware, is covered in the Modicon UMAS protocol guide and not repeated here. Below are 30 CVEs by product, with the fixed releases and mitigations from Schneider's security notifications (SEVD) and CISA's ICS advisories. Every score names its scorer, because Schneider, CISA and NVD often disagree, and 5 of the 30 had no NVD Primary score as of 2026-11-28.

Key takeaways

  • This guide covers the software layer: the HMI designers and runtimes, the PLC programming suites as Windows applications, and the SCADA servers.
  • For the network zones these products sit in, see the Purdue model guide.
  • Malicious project files that corrupt memory or escape paths.
  • Operator Terminal Expert and its Pro-face twin, Pro-face BLUE, share code and fixes.

Which Schneider HMI, SCADA and engineering products does this guide cover?

Schneider's notices describe these products in their own words, and the names changed over time, which matters when you match an installed version to an advisory:

Product (former names) What it does, per Schneider's notices Where it runs
EcoStruxure Operator Terminal Expert (formerly Vijeo XD); Pro-face BLUE HMI configuration software supporting gestures and UI designs, with a runtime on Harmony HMIST6, HMIG3U and HMISTO and on Pro-face ST6000, SP5000 and GP4100 HMIs Engineering workstation and the HMI panel
Vijeo Designer and Vijeo Designer Basic HMI software for Magelis/Harmony XBT GT terminals and Smart and Compact iPCs Engineering workstation and the HMI panel
EcoStruxure Control Expert (formerly Unity Pro), Process Expert Software to design, diagnose, maintain and update applications for Modicon M340, M580, Momentum, Premium and Quantum PLCs Engineering workstation
EcoStruxure Machine Expert (formerly SoMachine), Machine SCADA Expert Software for developing, configuring and commissioning an entire machine in a single environment, including Harmony SCU HMI controllers; Machine SCADA Expert shares an AVEVA Edge component Engineering workstation, machine HMI
EcoStruxure Geo SCADA Expert (formerly ClearSCADA) An open, flexible and scalable software system for telemetry and remote SCADA SCADA server with ViewX and web clients
Vijeo Citect and CitectSCADA (now AVEVA Plant SCADA) Plant SCADA, sold under Schneider and then AVEVA SCADA servers and clients
Pro-face GP-Pro EX, Pro-Server EX, Remote HMI Pro-face HMI editor and runtime, data server, and a mobile remote HMI app Engineering workstation, HMI, phone or tablet

For the network zones these products sit in, see the Purdue model guide. Engineering workstations and SCADA servers usually sit at level 2 or 3, which is why a flaw that needs only a crafted file or a local user still matters.

What vulnerability families do Schneider and CISA report?

Four families recur across the notices, and each has its own fix pattern:

  1. Malicious project files that corrupt memory or escape pathsOpening a crafted project file causes SQL injection or path traversal in Operator Terminal Expert (CVE-2020-7493, CVE-2020-7497), a write-what-where condition in Control Expert (CVE-2020-7560), path traversal into unauthorized locations (CVE-2021-22797) and heap overflows in the bundled Xmill XML library (CVE-2022-26507). The memory corruption fix guide and the path traversal fix guide cover the root causes.
  2. Insecure credentialsHard-coded credentials in Vijeo Designer project and firmware transfer (CVE-2020-7501) and the GP-Pro EX FTP server (CVE-2015-7921), weak password hashes in Geo SCADA database files (CVE-2021-22741) and MD5 password hashes in Machine SCADA Expert projects (CVE-2025-9317).
  3. Unauthenticated or under-checked network servicesThe Operator Terminal Expert Ethernet Download feature (CVE-2020-28221), the Harmony HMI FTP service on port 6001 (CVE-2021-22704), the Geo SCADA database port (CVE-2023-22610, CVE-2023-22611) and Citect and ClearSCADA crash bugs (CVE-2013-2824, CVE-2017-6021).
  4. Windows workstation weaknessesDLL loading and privilege escalation in Operator Terminal Expert, Vijeo Designer, Citect, GP-Pro EX, the FlexNet licensing component and the Schneider Electric Software Update (SESU) client (CVE-2022-41666, CVE-2024-8306, CVE-2018-7799, CVE-2024-2658, CVE-2025-5296).

Which EcoStruxure Operator Terminal Expert and Pro-face BLUE flaws matter?

Operator Terminal Expert and its Pro-face twin, Pro-face BLUE, share code and fixes. Schneider and CISA published these flaws:

CVE Flaw Vendor or CISA score NVD Primary Fixed in
CVE-2020-7493 SQL injection when a user opens a crafted project file CISA v3 8.6 v3.1 7.8 Operator Terminal Expert 3.1 SP1A (ICSA-20-142-02)
CVE-2020-7497 Path traversal that could cause arbitrary application execution when the computer starts CISA v3 6.3 v3.1 9.8 3.1 SP1A (ICSA-20-142-02)
CVE-2020-28221 Improper input validation, arbitrary code execution on the HMI when Ethernet Download is enabled Schneider v3.0 8.8 v3.1 9.8 Operator Terminal Expert and Pro-face BLUE 3.1 SP1B (SEVD-2021-012-01)
CVE-2022-41666 Missing signature check lets a local user load a malicious DLL Schneider v3.1 7.0 v3.1 7.8 V3.3 SP1 of both products (SEVD-2022-284-01)
CVE-2022-41667 Path traversal lets a local user load a malicious DLL Schneider v3.1 7.0 v3.1 7.8 V3.3 SP1 (SEVD-2022-284-01)
CVE-2023-1049 Code injection, arbitrary code execution and access to all information on the machine CISA v3 7.8 v3.1 7.8 Operator Terminal Expert v3.4 (ICSA-23-180-02)

CVE-2020-28221 is the one that reaches the HMI itself. Schneider's SEVD-2021-012-01 lists Operator Terminal Expert 3.1 SP1A and earlier running on Harmony HMIST6, HMIG3U and HMISTO panels and Pro-face BLUE on ST6000, SP-5B41 and GP4100 panels. Owners who cannot update should disable "Always Allow Ethernet Transfer" in the project's target preferences. SEVD-2022-284-01 covers four more DLL, project-conversion and project-migration flaws with the same V3.3 SP1 fix; all six need a local user on the engineering workstation.

For the 2020 project-file flaws, CISA's ICSA-20-142-02 repeats Schneider's mitigations: use the software only on a trusted workstation, do not run it with Windows administrator privileges, only accept project files from trusted users, and use a project password when saving project files.

What are the Vijeo Designer and Harmony HMI vulnerabilities?

Vijeo Designer configures the older Magelis and current Harmony HMI families, and two of its flaws sit on the transfer path between workstation and panel:

  • CVE-2020-7501, hard-coded credentials. Schneider's SEVD-2020-133-02 (V1.1, 11 August 2020) says hard-coded credentials allow unauthorized read and write when downloading and uploading projects or firmware. Schneider scores it CVSS v3.0 8.6, NVD 8.8. Affected are Vijeo Designer Basic V1.1 HotFix 16 and earlier and Vijeo Designer V6.2 SP9 and earlier; fixed are Vijeo Designer Basic V1.1 HotFix 17 and Vijeo Designer V6.2 SP10. The mitigations are to enable "Download security", which overrides the hard-coded password, and to block all unauthorized access to TCP port 6001, which Schneider calls a non-standard FTP port.
  • CVE-2021-22704, FTP path traversal on the HMI. Schneider's SEVD-2021-222-01 (10 August 2021) gives denial of service or unauthorized access to system information when connecting to the Harmony HMI over FTP. Schneider scores it 8.8, NVD 9.1. It names Harmony/Magelis STO, STU, GTO, GTU, GTUX, GK, GXU and SCU panels. The fix is two steps: update to Vijeo Designer V6.2 SP11, Vijeo Designer Basic V1.2 or Machine Expert V2.0, then connect to each HMI and download the project or firmware again.
  • CVE-2024-8306, privilege escalation on the workstation. CISA's ICSA-25-014-02 (Update A) scores it 7.8, as does NVD. A non-admin user can tamper with binaries. Vijeo Designer V6.3 SP1, through SESU, or Vijeo Designer 6.3.2.16 shipped with Machine Expert v2.3 fixes it; the mitigation is to remove write permissions for "Everyone" on the Vijeo-Runtime folder.
  • CVE-2024-11999, unmaintained third-party component in Harmony and Pro-face HMIs. CISA's ICSA-25-010-02 scores it 8.8 and lists Harmony HMIST6, HMISTM6, HMIG3U and HMIG3X and Pro-face ST6000, STM6000, SP5000 and GP4100 panels. An authenticated user who installs malicious code could take complete control of the device. The advisory lists only mitigations, no fixed version: keep HMIs off public and untrusted networks, segment and firewall them, restrict portable media and verify digital signatures. NVD had no Primary score as of 2026-11-28.

Which EcoStruxure Control Expert flaws are about project files and the workstation?

These Control Expert and Unity Pro flaws are in the Windows application and its drivers, not in the PLC link; for the PLC-side flaws see the Modicon UMAS guide.

CVE Flaw Vendor or CISA score NVD Primary Fix or status
CVE-2020-7560 Write-what-where on opening a malicious file; crash or code execution Schneider v3.0 8.6 v3.1 8.6 Control Expert V15.0 SP1 file encryption feature (SEVD-2020-343-01 V2.0)
CVE-2021-22797 Path traversal: a malicious project file deploys a script to unauthorized locations CISA v3 7.8 v3.1 7.8 No fixed version; mitigations only (ICSA-21-259-02)
CVE-2022-26507 Heap overflow in the Xmill 0.7 XML decompressor bundled with the software CISA v3 9.8 v3.1 9.8 Control Expert V15.1 HF001, Process Expert V2021, SCADAPack RemoteConnect R2.7.3 (ICSA-22-223-03)
CVE-2024-2658 Uncontrolled search path in Revenera FlexNet Publisher licensing CISA v3 7.8 none Control Expert 16.2; Vijeo Designer V6.3 SP1 HF1 from support (ICSA-25-037-02 Update D)
CVE-2011-3330 Buffer overflow in the UnitelWay Windows device driver n/a v2 7.2 Schneider driver fix HFPEP0047398R (ICSA-11-277-01)
CVE-2013-0662 Stack overflows in ModbusDrv.exe, Modbus Serial Driver 1.10 to 3.2 n/a v2 9.3 New versions of OFS V3.5 and Unity Pro V8 carry the updated ModbusDriverSuite (ICSA-14-086-01A)

CVE-2021-22797 is worth reading in full. CISA's ICSA-21-259-02 lists all versions of Control Expert (including Unity Pro), Process Expert and SCADAPack RemoteConnect for x70 as affected, and its mitigations are process controls: store project files in secure storage with access limited to trusted users, exchange them over secure protocols, compute and check a checksum on every project file before use, start the software without administrator rights, and migrate from Unity Pro to Control Expert.

CVE-2022-26507 is one of 13 Xmill CVEs in ICSA-22-223-03; CISA notes that AT&T Labs no longer supports Xmill. CVE-2013-0662 sits in a shared driver suite: CISA's affected list includes Unity Pro 7.0 and earlier, SoMachine 2.0 to 3.1, OPC Factory Server 3.40 and earlier, TwidoSuite, PowerSuite, SoMove and PL7. That driver speaks Modbus to devices, the protocol covered in the Modbus security guide.

What about EcoStruxure Machine Expert and Machine SCADA Expert?

Machine Expert shares two flaws above: it configures Harmony SCU panels affected by CVE-2021-22704 (fixed in Machine Expert V2.0 plus an SCU firmware update), and v2.3 ships the Vijeo Designer build that fixes CVE-2024-8306. CISA's ICSA-26-020-02 lists Machine Expert and Vijeo Designer among the Schneider products tied to the CODESYS runtime, so the CODESYS runtime guide applies to that side.

EcoStruxure Machine SCADA Expert and Pro-face BLUE Open Studio embed an AVEVA Edge component. CISA's ICSA-25-322-01 covers CVE-2025-9317: passwords hashed with MD5 let someone with read access to project files or offline cache files brute-force users' app-native or Active Directory passwords. CISA scores it v3.1 8.4; NVD had no Primary score as of 2026-11-28. Version 2023.1 Patch 1 of both products fixes it. Until then, CISA asks owners to apply access control lists to project folders, keep a trusted chain of custody for project files and set a strong master password on the project.

Which Geo SCADA Expert (ClearSCADA) vulnerabilities did Schneider publish?

Geo SCADA Expert is versioned by year and build number (for example 2021, build 84.8335.2), with monthly updates, so match the build, not just the year:

CVE Flaw Vendor or CISA score NVD Primary Fixed in
CVE-2017-6021 Crafted command and data sequences terminate the ClearSCADA server and driver processes CISA v3 7.5 v3.0 7.5 2014 R1.1 hotfix build 75.6239, 2015 R1.1 SP build 76.6191, 2015 R2 hotfix build 77.6181 (ICSA-17-068-01)
CVE-2021-22741 Weak password hashes in server database files Schneider v3.1 6.7 v3.1 6.7 Geo SCADA Expert 2020 April 2021 (83.7787.1) (SEVD-2021-130-07)
CVE-2023-22610 Incorrect authorization, denial of service over the database server TCP port Schneider v3.1 9.1 v3.1 7.5 October 2022 updates: 2019 81.8333.1, 2020 83.8332.1, 2021 84.8335.2 (SEVD-2023-010-02)
CVE-2023-22611 Information disclosure over the database server TCP port Schneider v3.1 7.5 v3.1 7.5 Same October 2022 updates (SEVD-2023-010-02)

Schneider's SEVD-2023-010-02 lists ClearSCADA, all versions, as affected with no fix, and tells ClearSCADA owners to upgrade to the latest Geo SCADA release. Its mitigations name the ports: restrict the database port (default 5481) to ViewX clients only, and use the Client Access Control list to keep unauthorized IP addresses off the server and restrict the web services port (default 443). For CVE-2021-22741, Schneider asks owners to protect the Config files under Program Data\Schneider Electric\ClearSCADA and their backups, set to LocalSystem and Administrators access only on 2019 and later. Installing new server software needs a restart or a changeover of redundant servers.

What happened to Citect, and which Citect CVEs still matter?

CISA titled its Vijeo Citect and CitectSCADA advisories under Schneider Electric up to 2013 and under AVEVA from 2018; the product is now AVEVA Plant SCADA, covered with its 2023 flaw CVE-2023-1256 in the AVEVA InTouch and Plant SCADA guide. Older Citect installations still carry these:

  • CVE-2013-2824 (ICSA-13-350-01A, NVD v2 7.8): a crafted packet triggers an unhandled exception and denial of service in Vijeo Citect 7.20 to 7.40, CitectSCADA 7.20 to 7.30 SP1, PowerSCADA Expert and PowerLogic SCADA. Schneider shipped per-version hotfixes such as HF740RTM60777.1 for Vijeo Citect 7.40, then reissued them as security-only patches after some customers saw crashes from the bundled quality fix.
  • CVE-2018-7799 (ICSA-18-331-01, CISA v3 7.8, NVD v3.0 7.8): an uncontrolled search path lets a local attacker run code on Citect SCADA 2015, 2016 and 7.40 and Vijeo Citect 2015 and 7.40. AVEVA's fix is to upgrade the Schneider Electric Software Update (SESU) software.
  • CVE-2019-13537 (ICSA-19-290-01 Update A, CISA and NVD 7.5): a stack overflow in the IEC870IP driver v4.14.02 and earlier crashes the server. It affects Vijeo Citect, Citect SCADA and Schneider's Power SCADA Operation; the fix is IEC870IP driver v4.15.00.
  • CVE-2011-3330 in the UnitelWay driver, listed in the Control Expert table, also covered Vijeo Citect 7.20 and earlier.

Which Pro-face GP-Pro EX flaws should owners know?

Schneider Electric publishes Pro-face security notices next to its own, and Pro-face BLUE shares fixes with Operator Terminal Expert. CISA published early Pro-face advisories under the Pro-face and Digital Electronics names and later ones under Schneider Electric:

  • CVE-2012-3797 (ICSA-12-179-01, NVD v2 10.0): Pro-Server EX 1.30.000 and earlier and WinGP PC Runtime 3.1.00 and earlier do not check packet sizes before reusing buffers, which allows heap memory corruption. Digital Electronics released patch modules; CISA's advisory lists four sibling crash flaws in the same component.
  • CVE-2015-7921 (ICSA-16-096-01, CISA and NVD 9.1): the FTP server in GP-Pro EX EX-ED and related packages before 4.05.000 has hard-coded credentials. GP-Pro EX 4.05.000 fixes it together with two buffer overflows from the same advisory.
  • CVE-2018-7832 (ICSA-19-003-01, CISA v3 9.0, NVD v3.0 8.8): an error lets an arbitrary executable be launched in GP-Pro EX 4.08 and earlier; version 4.08.200 fixes it.
  • CVE-2024-12399 (ICSA-25-035-07 Update A, CISA v3 7.1, no NVD Primary score as of 2026-11-28): improper message integrity between Pro-face Remote HMI and GP-Pro EX enables a man-in-the-middle. GP-Pro EX 5.00.100 and Remote HMI 1.70.000 fix it, and Schneider recommends Pro-face Connect or another VPN to encrypt the remote session.

How does Schneider version its fixes?

The fix unit differs by product, so a single "latest version" check misses things:

  • Desktop software gets service packs and hotfixes: Operator Terminal Expert 3.1 SP1A and SP1B, V3.3 SP1 and v3.4; Vijeo Designer V6.2 SP10 and SP11, V6.3 SP1 and V6.3 SP1 HF1; Control Expert V15.0 SP1, V15.1 HF001 and 16.2. Some hotfixes come only from Schneider Customer Care, not SESU.
  • Geo SCADA Expert gets monthly updates identified by build number; SEVD-2023-010-02 names one fixed build each for 2019, 2020 and 2021.
  • Fixes that need a second step. Updating Vijeo Designer does not fix a Harmony panel until the project or firmware is downloaded again (CVE-2021-22704). The Control Expert V15.0 SP1 fix for CVE-2020-7560 is a file encryption feature that must be turned on for each project.
  • The updater is itself software to patch. SESU, which delivers many of these fixes, had its own flaw, CVE-2025-5296 (ICSA-25-266-03, CISA v3 7.3, no NVD Primary score as of 2026-11-28): a low-privileged user who tampers with the installation folder can escalate privileges. SESU 3.0.12 fixes it and is pushed as an automatic critical update where automatic updates are enabled. CISA lists it as installed alongside Control Expert, Machine Expert, Operator Terminal Expert and many other Schneider products.
  • Shared components. FlexNet Publisher (CVE-2024-2658), the Xmill library (CVE-2022-26507), the Modbus Serial Driver (CVE-2013-0662) and the AVEVA Edge component (CVE-2025-9317) each touch several products at once.

Plan these updates through a change process such as the one in the IEC 62443-2-3 patch management guide.

Are any of these in CISA KEV, and what do EPSS scores say?

None of the 30 CVEs is in the KEV catalog as of 2026-11-28 (version 2026.11.27, 1,808 entries); the only Schneider Electric entry is for U.motion Builder. In FIRST's EPSS data dated 2026-11-27, three stand out: CVE-2021-22797 at 0.261 (98th percentile), CVE-2013-0662 at 0.222 and CVE-2012-3797 at 0.120. Every other CVE here is below 0.03. The KEV and EPSS prioritization guide explains how to combine those signals with exposure: a project-file flaw on an internet-isolated workstation ranks below a reachable database or FTP port.

How do you harden Schneider HMI, SCADA and engineering systems?

Schneider's notices and CISA's advisories repeat the same advice:

  1. Treat project files as executable inputAccept them only from trusted users, store them with access control, exchange them over secure protocols, checksum them, and use project passwords or Control Expert file encryption.
  2. Run engineering software without administrator rightson trusted, hardened workstations with antivirus, current operating systems and application allowlisting.
  3. Close the transfer pathsDisable "Always Allow Ethernet Transfer" in Operator Terminal Expert projects, enable Vijeo Designer "Download security", and firewall TCP port 6001 on Harmony HMIs.
  4. Restrict Geo SCADA portsAllow port 5481 only from ViewX clients and use the Client Access Control list for port 443; protect the Config database files and their backups.
  5. Keep SESU currentat 3.0.12 or later and keep its installation folder off the network.
  6. Firewall the control networkSchneider's general recommendations ask owners to put control and safety networks behind firewalls isolated from the business network, never connect programming software to any network other than the one it is meant for, scan removable media, and use VPNs for remote access, keeping the VPN itself updated.

How do you check which version a Schneider system runs?

  1. Record each engineering tool's release and service pack or hotfixper workstation, for example Control Expert V15.1 HF001 or Vijeo Designer V6.3 SP1 HF1. The About or General tab shows the version, as Schneider's SEVD-2020-133-02 notes for Vijeo Designer.
  2. Record HMI panel runtime and firmware separatelyfrom the designer version, since a fixed designer does not fix a panel until you download again.
  3. Record Geo SCADA year and full build numberon every server, including standby servers.
  4. Record shared components: the SESU version, FlexNet licensing, communication drivers (UnitelWay, Modbus serial, IEC870IP) and the Machine SCADA Expert release.
  5. Do not rely on NVD aloneAs of 2026-11-28, 5 of the 30 CVEs here had no NVD Primary score, and NVD scores CVE-2020-7497 at 9.8 where CISA's advisory says 6.3.

How do you monitor Schneider HMI and SCADA networks?

Baseline which hosts talk to each HMI, SCADA server and engineering station, and on which ports, then alert on change:

  • New hosts connecting to port 5481 on Geo SCADA servers, which fits CVE-2023-22610 and CVE-2023-22611.
  • Connections to TCP port 6001 or FTP on Harmony HMIs from outside the engineering workstations, which fits CVE-2020-7501 and CVE-2021-22704.
  • Project downloads to Operator Terminal Expert panels from unknown hosts, which fits CVE-2020-28221.
  • Remote HMI sessions that bypass the VPN, which fits CVE-2024-12399.

Flow records show who connected to which port and when, not which project or command was sent. Map alerts to MITRE ATT&CK for ICS techniques such as exploitation of remote services and program download.

Worked example: what does a review of a water utility's Schneider estate find?

Synthetic example, not a real site. A water utility runs Geo SCADA Expert 2021 build 84.8269.1 for its telemetry, Harmony GTU panels built with Vijeo Designer V6.2 SP9, Control Expert V15.0 for its M580 PLCs, and an older Vijeo Citect 7.40 system at one treatment works.

Observation Why it matters Action
Geo SCADA 2021 build 84.8269.1, port 5481 open to the office VLAN CVE-2023-22610 and CVE-2023-22611 are open Install 84.8335.2 or later; allow port 5481 only from ViewX clients
Vijeo Designer V6.2 SP9, port 6001 reachable on panels CVE-2020-7501 and CVE-2021-22704 are open Update to V6.2 SP11 or later, download every panel project again, enable Download security, firewall port 6001
Control Expert V15.0 without SP1 CVE-2020-7560 and CVE-2022-26507 are open Move to V15.1 HF001 or later, turn on file encryption, checksum project files
Vijeo Citect 7.40 with an old SESU CVE-2018-7799 and CVE-2025-5296 apply Update SESU to 3.0.12; plan a move to a supported AVEVA Plant SCADA release
Project files shared by e-mail with contractors CVE-2021-22797 has no fixed version Use a controlled share with checksums and access lists

Where does passive monitoring fit in a Schneider review?

A passive capture shows who talks to HMIs, SCADA servers and engineering stations without logging in to anything. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from a mirror-port recording and builds a host-by-port inventory at connection level, including hosts using ports 5481 and 6001, and lists remote-access sessions that cross from outside the private address range. It does not decode Geo SCADA, Vijeo Designer transfer or project-file contents, and it does not read software versions from traffic. Component and version identification comes from the software lists and asset records you share. SoftWSP matches the versions found against CVE, CISA KEV and FIRST EPSS data, and an engineer reviews the AI-written summary before it reaches you.

What are the common pitfalls?

  • Updating Vijeo Designer and assuming the Harmony panels are fixed without downloading the projects again.
  • Installing Control Expert V15.0 SP1 without enabling file encryption on existing projects.
  • Matching Geo SCADA by year instead of by build number, or leaving ClearSCADA in place, which has no fix for the 2023 database-port flaws.
  • Trusting SESU to deliver every fix, when some hotfixes come only from Customer Care and SESU itself needed a patch.
  • Assuming one score: NVD rates CVE-2020-7497 at 9.8 where CISA says 6.3, and Schneider rates CVE-2023-22610 at 9.1 where NVD says 7.5.
  • Opening project files from contractors or e-mail on the engineering workstation without checking them first.

This guide draws on Schneider Electric security notifications SEVD-2020-133-02, SEVD-2020-343-01, SEVD-2021-012-01, SEVD-2021-130-07, SEVD-2021-222-01, SEVD-2022-284-01 and SEVD-2023-010-02 (PDF and CSAF) and Schneider's security notifications page; CISA ICS advisories ICSA-11-277-01, ICSA-12-179-01, ICSA-13-350-01A, ICSA-14-086-01A, ICSA-16-096-01, ICSA-17-068-01, ICSA-18-331-01, ICSA-19-003-01, ICSA-19-290-01, ICSA-20-142-02, ICSA-21-259-02, ICSA-22-223-03, ICSA-23-180-02, ICSA-25-010-02, ICSA-25-014-02, ICSA-25-035-07, ICSA-25-037-02, ICSA-25-266-03 and ICSA-25-322-01 and their CSAF records; NVD and CVE.org records; CISA KEV and FIRST EPSS, all checked as of 2026-11-28.

Put this guide to work

Frequently asked questions

Are any Schneider Electric HMI or SCADA software vulnerabilities in the CISA KEV catalog?

No. As of 2026-11-28, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.27, 1,808 entries) has a single Schneider Electric entry, for the U.motion Builder building-automation software, and none of the 30 CVEs in this guide is listed. The highest FIRST EPSS scores among them, dated 2026-11-27, belong to the Control Expert project-file path traversal CVE-2021-22797 at 0.261, the Modbus Serial Driver overflow CVE-2013-0662 at 0.222 and the Pro-Server EX memory flaw CVE-2012-3797 at 0.120; every other CVE here is below 0.03.

Which ports do Schneider's notices name for these products?

Three. Schneider's SEVD-2023-010-02 asks Geo SCADA Expert owners to restrict the server's database port (default 5481) to ViewX clients and to use the Client Access Control list to restrict the web services port (default 443). SEVD-2020-133-02 and SEVD-2021-222-01 ask owners of Vijeo Designer-configured Harmony HMIs to block all unauthorized access to TCP port 6001, which Schneider describes as a non-standard FTP port used for project and firmware transfer.

Is updating the engineering software enough to fix a Harmony HMI?

Not always. For the FTP path traversal CVE-2021-22704, Schneider's SEVD-2021-222-01 says to update Vijeo Designer to V6.2 SP11, Vijeo Designer Basic to V1.2 or EcoStruxure Machine Expert to V2.0, and then connect to each HMI and download the project or firmware again with the fixed version. For the Control Expert write-what-where flaw CVE-2020-7560, the fix in V15.0 SP1 is a file encryption feature that Schneider asks owners to apply to new projects and to existing projects from trusted sources.

Why do Schneider, CISA and NVD scores differ for the same CVE?

They score different assumptions. For the Operator Terminal Expert path traversal CVE-2020-7497, CISA's advisory gives CVSS v3 6.3 with high privileges and user interaction required, while NVD's Primary score is 9.8. For the Geo SCADA database-port flaw CVE-2023-22610, Schneider gives 9.1 and NVD gives 7.5. Five of the 30 CVEs in this guide, all from 2024 and 2025, had no NVD Primary score as of 2026-11-28, so the vendor or CISA score is the only one.

What happened to Vijeo Citect and CitectSCADA?

CISA published CitectSCADA and Vijeo Citect advisories under Schneider Electric up to the 2013 exception-handler flaw (ICSA-13-350-01A) and under AVEVA from 2018 (ICSA-18-331-01, ICSA-19-290-01). The product continues as AVEVA Plant SCADA, whose 2023 improper-authorization flaw CVE-2023-1256 is fixed in Plant SCADA 2023 Update 1 and 2020R2 Update 11. Schneider's Power SCADA Operation shares the Citect IEC870IP driver, which CISA names in CVE-2019-13537.

Sources

  1. Schneider Electric: Security Notifications
  2. Schneider Electric SEVD-2021-012-01: EcoStruxure Operator Terminal Expert and Pro-face BLUE (CVE-2020-28221)
  3. Schneider Electric SEVD-2022-284-01: EcoStruxure Operator Terminal Expert and Pro-face BLUE (CVE-2022-41666, CVE-2022-41667 and four related CVEs)
  4. Schneider Electric SEVD-2020-133-02: Vijeo Designer and Vijeo Designer Basic (CVE-2020-7501)
  5. Schneider Electric SEVD-2021-222-01: Harmony/Magelis HMI products configured by Vijeo Designer, Vijeo Designer Basic and EcoStruxure Machine Expert (CVE-2021-22704)
  6. Schneider Electric SEVD-2020-343-01: EcoStruxure Control Expert, Process Expert and RemoteConnect (CVE-2020-7560)
  7. Schneider Electric SEVD-2021-130-07: EcoStruxure Geo SCADA Expert (CVE-2021-22741)
  8. Schneider Electric SEVD-2023-010-02: EcoStruxure Geo SCADA Expert (CVE-2023-22610, CVE-2023-22611)
  9. CISA CSAF: ICSA-20-142-02 Schneider Electric EcoStruxure Operator Terminal Expert
  10. CISA CSAF: ICSA-23-180-02 Schneider Electric EcoStruxure Operator Terminal Expert
  11. CISA CSAF: ICSA-25-010-02 Schneider Electric Harmony HMI and Pro-face HMI Products
  12. CISA CSAF: ICSA-25-014-02 Schneider Electric Vijeo Designer and EcoStruxure Machine Expert (Update A)
  13. CISA CSAF: ICSA-21-259-02 Schneider Electric EcoStruxure and SCADAPack
  14. CISA CSAF: ICSA-22-223-03 Schneider Electric EcoStruxure, EcoStruxure Process Expert, SCADAPack RemoteConnect for x70
  15. CISA CSAF: ICSA-25-037-02 Schneider Electric EcoStruxure (Update D)
  16. CISA CSAF: ICSA-11-277-01 Schneider Electric UnitelWay Buffer Overflow
  17. CISA CSAF: ICSA-14-086-01A Schneider Electric Serial Modbus Driver Buffer Overflow (Update A)
  18. CISA CSAF: ICSA-25-322-01 Schneider Electric EcoStruxure Machine SCADA Expert and Pro-face BLUE Open Studio
  19. CISA CSAF: ICSA-17-068-01 Schneider Electric ClearSCADA
  20. CISA CSAF: ICSA-13-350-01A Schneider Electric CitectSCADA Products Exception Handler Vulnerability (Update A)
  21. CISA CSAF: ICSA-18-331-01 AVEVA Vijeo Citect and Citect SCADA
  22. CISA CSAF: ICSA-19-290-01 AVEVA Vijeo Citect and Citect SCADA (Update A)
  23. CISA CSAF: ICSA-12-179-01 Pro-Face Pro-Server EX Vulnerabilities
  24. CISA CSAF: ICSA-16-096-01 Pro-face GP-Pro EX HMI Vulnerabilities
  25. CISA CSAF: ICSA-19-003-01 Schneider Electric Pro-face GP-Pro EX
  26. CISA CSAF: ICSA-25-035-07 Schneider Electric Pro-face GP-Pro EX and Remote HMI (Update A)
  27. CISA CSAF: ICSA-25-266-03 Schneider Electric SESU
  28. NVD: CVE-2020-7497 (Operator Terminal Expert path traversal)
  29. NVD: CVE-2021-22704 (Harmony HMI FTP path traversal)
  30. NVD: CVE-2023-22610 (Geo SCADA Expert incorrect authorization)
  31. CVE.org record: CVE-2024-11999 (Harmony and Pro-face HMI unmaintained third-party component)
  32. CISA Known Exploited Vulnerabilities catalog