CVE-2023-1256 is an improper authorization flaw in AVEVA Plant SCADA, formerly Citect SCADA, and AVEVA Telemetry Server. Without logging in, a remote user can read data, crash the service and tamper with alarm states. NVD, AVEVA and CISA all score it 9.8. Plant SCADA 2023 Update 1, 2020R2 Update 11 and Telemetry Server 2020 R2 SP2 fix it.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
0.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-1256 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| AVEVA Plant SCADA (formerly Citect SCADA) 2023 | cpe:2.3:a:aveva:aveva_plant_scada:2023:-:*:*:*:*:*:* | 2023; fixed in 2023 Update 1 (AVEVA-2023-002) |
| AVEVA Plant SCADA (formerly Citect SCADA) 2020R2 | cpe:2.3:a:aveva:aveva_plant_scada:2020r2:update_10:*:*:*:*:*:* | 2020R2 Update 10 and all prior versions; fixed in 2020R2 Update 11 or 2023 Update 1; no fix for older versions (AVEVA-2023-002) |
| AVEVA Telemetry Server | cpe:2.3:a:aveva:telemetry_server:2020r2:sp1:*:*:*:*:*:* | 2020 R2 SP1 and all prior versions; fixed in 2020 R2 SP2 (AVEVA-2023-002) |
What does this mean for affected devices?
NVD carries the CISA (ICS-CERT) description: "The listed versions of AVEVA Plant SCADA and AVEVA Telemetry Server are vulnerable to an improper authorization exploit which could allow an unauthenticated user to remotely read data, cause denial of service, and tamper with alarm states." NVD's Primary score and the CISA score are both CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). NVD lists no CWE of its own; AVEVA and CISA classify it as CWE-285, improper authorization. The record was published on 2023-03-16 (NVD, CVE record).
What does AVEVA say?
AVEVA's bulletin AVEVA-2023-002 of 2023-03-14 rates it Critical and credits the UK's National Cyber Security Centre (NCSC) with the discovery. CISA republished it as ICSA-23-073-04 for the critical manufacturing sector. Neither source names the port or protocol involved; both describe the same three outcomes. On a SCADA server, tampered alarm states mean operators can miss or dismiss real process alarms.
Which versions are affected and fixed?
| Product | Affected | Fix |
|---|---|---|
| Plant SCADA 2023 | 2023 | 2023 Update 1 or later |
| Plant SCADA 2020R2 | Update 10 and all prior versions | 2020R2 Update 11 or later, or 2023 Update 1 |
| Telemetry Server | 2020 R2 SP1 and all prior versions | 2020 R2 SP2 or later |
AVEVA states that fixes for older versions outside mainstream support are not available, so those sites have to upgrade. NVD's CPE list copies the CVE record, which names "2023 Update 10" as affected; AVEVA's bulletin names plain 2023 and fixes it in 2023 Update 1.
What should operators do?
Upgrade Plant SCADA and Telemetry Server first, since the attack needs no credentials. Until then, keep the SCADA servers off business networks and the internet and allow only known operator and engineering hosts to reach them. The AVEVA InTouch and System Platform guide puts this flaw next to the other AVEVA advisories, such as the PI Server crash CVE-2023-34348. The authentication bypass fix guide covers this class of weakness.
CVE-2023-1256 is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS gives it 0.00678, the 53.3rd percentile, in the 2026-11-23 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-24): status Modified; published 2023-03-16; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, ICS-CERT Secondary 9.8; no NVD CWE; CPE aveva_plant_scada 2020r2 (-, update_10), 2023 (-, update_10), telemetry_server 2020r2 (-, sp1). — NVD
- AVEVA Security Bulletin AVEVA-2023-002 (2023-03-14, read 2026-11-24): Critical; Plant SCADA 2023, 2020R2 Update 10 and prior, Telemetry Server 2020 R2 SP1 and prior; CWE-285, CVSS v3.1 9.8; fixes Plant SCADA 2023 Update 1, 2020R2 Update 11, Telemetry Server 2020 R2 SP2; no fixes for older versions; credit UK NCSC. — AVEVA
- CISA ICSA-23-073-04 CSAF (read 2026-11-24): CWE-285, CVSS v3.1 9.8; read data, denial of service, tamper with alarm states; same fixes; sector Critical Manufacturing. — CISA
- CVE record (checked 2026-11-24): state PUBLISHED, CNA icscert, published 2023-03-16, CNA CVSS v3.1 9.8; affected Plant SCADA 2023 Update 10, 2020R2 Update 10, Telemetry Server 2020 R2 SP1. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.23, 1,792 entries, checked 2026-11-24. — CISA KEV
- EPSS 0.00678, percentile 0.53281, dataset 2026-11-23, read 2026-11-24. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which versions fix CVE-2023-1256?
Plant SCADA 2023 Update 1 or later, Plant SCADA 2020R2 Update 11 or later, and Telemetry Server 2020 R2 SP2 or later (AVEVA-2023-002). AVEVA has no fix for older versions.
Does an attacker need an account?
No. AVEVA, CISA and NVD all describe an unauthenticated remote user, which is why the score is 9.8 with no privileges required.
What can an attacker do to the SCADA system?
Read data, cause a denial of service and tamper with alarm states. Changed alarm states can hide real process alarms from operators.
Is CVE-2023-1256 in the CISA KEV catalog?
No, not as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS rates it 0.00678 (53.3rd percentile) in the 2026-11-23 dataset.
Questions about this page?