CVE-2013-0662 is a stack-based buffer overflow in ModbusDrv.exe, the Schneider Electric Modbus Serial Driver installed with engineering tools such as Unity Pro, SoMachine, TwidoSuite and OPC Factory Server. A large buffer-size value in a Modbus Application Header can let a remote attacker run code with user privileges. NVD and CISA score it CVSS v2 9.3. OFS V3.5 and Unity Pro V8 ship the fixed driver.
Vulnerability summary
CVSS base score
9.3
Critical severity
EPSS score (FIRST)
22.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2013-0662 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Modbus Serial Driver (ModbusDrv.exe) | cpe:2.3:a:schneider-electric:modbus_serial_driver:3.2:*:*:*:*:*:*:* | V1.10 IE v37 (Windows XP 32-bit), V2.2 IE12 (Vista and Windows 7 32-bit), V3.2 IE12 (Windows 7 64-bit) (CISA ICSA-14-086-01A) |
| Schneider Electric Unity Pro | cpe:2.3:a:schneider-electric:unity_pro:*:*:*:*:*:*:*:* | 7.0 and earlier (CISA); Unity Pro V8 includes the updated ModbusDriverSuite |
| Schneider Electric OPC Factory Server (OFS) | cpe:2.3:a:schneider-electric:opc_factory_server:*:*:*:*:*:*:*:* | 3.40 and earlier (CISA); OFS V3.5 includes the updated ModbusDriverSuite |
| Schneider Electric TwidoSuite, PowerSuite, SoMove, SoMachine, UnityLoader, Concept, ModbusCommDTM sl, PL7, SFT2841 | cpe:2.3:a:schneider-electric:somachine:*:*:*:*:*:*:*:* | TwidoSuite <= 2.31.04, PowerSuite <= 2.6, SoMove <= 1.7, SoMachine 2.0, 3.0, 3.1 and 3.0 XS, UnityLoader <= 2.3, Concept <= 2.6 SR7, ModbusCommDTM sl <= 2.1.2, PL7 <= 4.5 SP5, SFT2841 14 and 13.1 (CISA); updated driver ships with each product's next version, contact Schneider Electric support |
What does this mean for affected devices?
NVD says "multiple stack-based buffer overflows in ModbusDrv.exe in Schneider Electric Modbus Serial Driver 1.10 through 3.2 allow remote attackers to execute arbitrary code via a large buffer-size value in a Modbus Application Header." CISA classifies it as CWE-121 and NVD as CWE-787. The record was assigned by ICS-CERT and published on 2014-04-01 (NVD, CVE record).
How severe is CVE-2013-0662?
NVD's Primary score is CVSS v2 9.3, AV:N/AC:M/Au:N/C:C/I:C/A:C, which matches CISA's 9.3; the CVE record carries no CNA score. CISA's ICSA-14-086-01A, first released on 2014-03-27, credits Carsten Eiram of Risk-Based Security and says successful exploitation could allow code execution with user privileges. CISA rated it remotely exploitable but needing high skill, with no known public exploit at the time; NVD's reference list has since added public exploit database entries.
Which Schneider Electric products include the vulnerable driver?
The driver is not a product on its own; it is installed with Schneider engineering and connectivity software. The advisory CSAF lists TwidoSuite up to 2.31.04, PowerSuite up to 2.6, SoMove up to 1.7, SoMachine 2.0, 3.0, 3.1 and 3.0 XS, Unity Pro up to 7.0, UnityLoader up to 2.3, Concept up to 2.6 SR7, ModbusCommDTM sl up to 2.1.2, PL7 up to 4.5 SP5, SFT2841 14 and 13.1, and OPC Factory Server up to 3.40. Driver builds: V1.10 IE v37 on Windows XP 32-bit, V2.2 IE12 on Vista and Windows 7 32-bit, and V3.2 IE12 on Windows 7 64-bit. CISA notes use in chemical, energy, nuclear and transportation sectors, mainly in China, the United States and Europe. NVD's CPE range for OPC Factory Server runs up to 3.5.0, while CISA names V3.5 as the version carrying the fix.
What fixes CVE-2013-0662?
Schneider Electric's security notification SEVD 2013-070-01 asks users to update products that use the driver to the latest software. Update A of the CISA advisory adds that OFS V3.5 and Unity Pro V8 include the updated ModbusDriverSuite, and that the other products receive it with their next version; until then, contact Schneider Electric technical support and keep engineering workstations and PLCs behind firewalls that limit access to authorised people and protocols. The memory corruption fix guide covers the class, and the Modbus protocol guide covers filtering Modbus traffic. Later Schneider engineering-chain flaws: CVE-2018-7842 (Modicon UMAS authentication bypass) and CVE-2019-6808 (Modicon configuration overwrite).
Is CVE-2013-0662 exploited?
CVE-2013-0662 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.22217, the 98.19th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2014-04-01; NVD Primary CVSS v2 9.3 AV:N/AC:M/Au:N/C:C/I:C/A:C; CWE-787 (NVD); CPEs modbus_serial_driver 1.10, 2.2, 3.2; unity_pro <=7.0; opc_factory_server <=3.5.0; somachine, twidosuite, somove, powersuite, pl7, concept, sft2841, unityloader, modbuscommdtm_sl; references include SEVD 2013-070-01 and exploit-db entries tagged Exploit. — NVD
- CISA ICSA-14-086-01A CSAF (read 2026-11-27): product list and versions; CWE-121; CVSS v2 9.3; SEVD 2013-070-01; update products to latest software; OFS V3.5 and Unity Pro V8 include the updated ModbusDriverSuite; other products updated with each new version, contact technical support; firewalls limiting access. — CISA ICSA-14-086-01A
- CISA advisory page (read 2026-11-27 via a page fetch): original release March 27, 2014; Carsten Eiram, Risk-Based Security; code execution with user privileges; chemical, energy, nuclear, transportation; China, US, Europe; remotely exploitable, no known public exploits, high skill. — CISA
- CVE record (read 2026-11-27): CNA ICS-CERT; no CNA CVSS in the record. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.22217, percentile 0.98193, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which products install the vulnerable Modbus Serial Driver?
TwidoSuite, PowerSuite, SoMove, SoMachine, Unity Pro, UnityLoader, Concept, ModbusCommDTM sl, PL7, SFT2841 and OPC Factory Server, in the versions CISA ICSA-14-086-01A lists (for example Unity Pro 7.0 and earlier and OFS 3.40 and earlier).
Which versions fix CVE-2013-0662?
OPC Factory Server V3.5 and Unity Pro V8 include the updated ModbusDriverSuite. For the other products, the fixed driver comes with each product's next version; Schneider Electric support can advise in the meantime.
Who discovered CVE-2013-0662?
CISA credits Carsten Eiram of Risk-Based Security. Schneider Electric's own notification is SEVD 2013-070-01.
Is CVE-2013-0662 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.22217 (98.19th percentile) in the 2026-11-26 dataset.