AVEVA's InTouch HMI, System Platform (Application Server), Historian, SuiteLink, PI System, Edge and Plant SCADA had no CVE in CISA's KEV catalog as of 2026-11-24, but their published flaws fall into five families: unauthenticated network services and parsers, credentials exposed in memory or weak hashes, file, DLL and privilege weaknesses on Windows nodes, web and remote-access flaws, and denial of service in data servers. Fixes come as product patches, SuiteLink and Communication Drivers Pack updates, and PI Server releases.
The rest of this guide maps the products to their place in a plant network, names the services and ports that AVEVA and CISA give, walks through 31 CVEs by product with the fixed versions and mitigations from AVEVA's security bulletins and CISA's ICS advisories, and ends with hardening, version checks, monitoring and a worked example. Every score names its scorer, because CISA's score and NVD's Primary score for the same CVE often differ, and 11 of the 31 had no NVD Primary score as of 2026-11-24.
Key takeaways
- Most of CISA's AVEVA advisories list the company as headquartered in the United Kingdom, with its software deployed worldwide.
- AVEVA and CISA name four ports in these advisories: SuiteLink on 5413, PI Data Archive on 5450 and Process Optimization on 8888 and 8889.
- The InTouch flaw with the highest CISA score, CVE-2018-10628, is an unauthenticated stack buffer overflow that CISA and NVD both score 9.8.
- System Platform advisories run from 2019 to 2025 and cluster around credentials, the AutoBuild service and local privilege.
Where do AVEVA InTouch, System Platform and PI sit in OT networks?
Most of CISA's AVEVA advisories list the company as headquartered in the United Kingdom, with its software deployed worldwide. The InTouch advisories name the chemical, critical manufacturing, energy, food and agriculture, and water and wastewater sectors. CISA published these products under the Wonderware name (Invensys, then Schneider Electric) until 2017 and under AVEVA from 2018; PI System advisories appear under OSIsoft until 2021 and under AVEVA from 2024. The product names in the advisories fall into six groups:
| Group | Products named in advisories | Typical place in the network |
|---|---|---|
| HMI and remote HMI access | InTouch (WindowViewer runtime), InTouch Access Anywhere and its Secure Gateway, Plant SCADA Access Anywhere | Operator stations at the supervisory level; Access Anywhere streams HMI sessions to browsers through a gateway |
| Supervisory platform | System Platform and Application Server, the Galaxy Repository (GR) node, the Application Server IDE, AutoBuild, Operations Control Logger | Engineering and runtime servers at the supervisory level |
| Data access and drivers | SuiteLink, Communication Drivers Pack, Data Acquisition Servers | On every node that serves or reads plant data between InTouch, Application Server, Historian and devices |
| Historians | AVEVA Historian (shipped on System Platform media) with its REST interface, PI Server and PI Data Archive, PI Asset Framework (AF) and PI System Explorer, PI Web API | Site operations level, often with a copy or interface toward business networks |
| HMI and SCADA editions | AVEVA Edge (formerly InduSoft Web Studio), Plant SCADA (formerly Citect SCADA), Telemetry Server | Machine HMIs, plant and telemetry SCADA servers |
| Other industrial software | Process Optimization (formerly ROMeo), Pipeline Integrity Monitor, Batch Management, MES | Engineering, optimization and pipeline applications |
For the zoning behind the table, see the Purdue model guide. The historian tier is the usual bridge between the control network and the business network, so it deserves its own zone and firewall rules.
How are AVEVA systems managed and reached?
AVEVA and CISA name four ports in these advisories: SuiteLink on 5413, PI Data Archive on 5450 and Process Optimization on 8888 and 8889. The services and interfaces that the advisories name are the attack paths:
| Path | Products | What the sources say |
|---|---|---|
| SuiteLink server, TCP port 5413 by default | Every product that ships the SuiteLink server | Crafted packets crash the server or, in theory, run code (2021); unlimited resource use slows data I/O (CVE-2024-7113). AVEVA asks owners to accept SuiteLink traffic only from trusted sources |
| AutoBuild service | System Platform 2017 to 2020 R2 P01 | Meant only for the GR node during configuration; five chained flaws (ICSA-21-180-05) |
| PI Data Archive, port 5450 | PI Server and PI Data Archive | AVEVA and CISA ask owners to limit port 5450 inbound to trusted workstations, users and software |
| PI Web API REST endpoints | PI Web API | XML import deserialization (CVE-2024-3468) and annotation-attachment scripting (CVE-2025-2745) |
| Historian REST interface | AVEVA Historian | SQL injection through a crafted URL opened by a Historian REST user (CVE-2024-6456) |
| InTouch Access Anywhere Secure Gateway | InTouch and Plant SCADA Access Anywhere | Path traversal outside the gateway web server (CVE-2022-23854); escape from the streamed application to the OS (CVE-2022-1467) |
| Process Optimization taoimr service, ports 8888 and 8889 (TLS) | Process Optimization 2024.1 and earlier | Unauthenticated remote code execution (CVE-2025-61937) |
| Project files and engineering IDEs | Edge, Application Server IDE, Pipeline Integrity Monitor | DLL loading, weak password hashes in project files, script injection into help files |
No other port number appears in the advisories used here. For the rest of the PI System, AVEVA's bulletins point to its PI System firewall port requirements knowledge base article. The BOD 23-02 guide on internet-exposed management interfaces shows how to check that none of these services answers from outside.
Which InTouch and Access Anywhere vulnerabilities did CISA publish?
The InTouch flaw with the highest CISA score, CVE-2018-10628, is an unauthenticated stack buffer overflow that CISA and NVD both score 9.8. The InTouch and Access Anywhere flaws range from that runtime overflow to path traversal in the remote-access gateway:
| CVE | Weakness | CISA CVSS v3 | NVD Primary | Fix or mitigation named |
|---|---|---|---|---|
| CVE-2018-10628 | Stack buffer overflow from a crafted packet, unauthenticated | 9.8 | v3.0 9.8 | HF-11_1_SP1/CR149705 for InTouch 2014 R2 SP1; HF-17_2/CR149706 for 2017 Update 2 |
| CVE-2021-32942 | Cleartext credentials in a WindowViewer memory dump | 6.6 | v3.1 5.5 | InTouch 2020 R2 P01; Security Update 1216934 (2020) or 1216933 (2017 U3 SP1 P01) |
| CVE-2022-1467 | Windows language bar lets a user escape the streamed application | 7.4 | v3.1 9.9 | Disable the language bar, dedicated least-privilege accounts, group policy (AVEVA-2022-001) |
| CVE-2022-23854 | Path traversal in the Access Anywhere Secure Gateway, unauthenticated | 7.5 | v3.1 7.5 | Secure Gateway hotfixes for 2020 R2 (20.1.0) and 2020b (20.0.1) (AVEVA-2023-001) |
CISA's ICSA-18-200-02 notes that CVE-2018-10628 only applies when the operating system locale does not use a dot as the floating-point separator, and that it runs code with the privileges of the InTouch View process. Owners on releases older than 2014 R2 SP1, or on 2017 and 2017 Update 1, must first move to a supported release and then apply the hotfix.
For CVE-2022-23854, AVEVA's bulletin AVEVA-2023-001 covers InTouch Access Anywhere 2023 and all prior versions and Plant SCADA Access Anywhere 2020 R2 and all prior versions, while the CVE description says 2020 R2 and older. The same CISA advisory lists two third-party library CVEs fixed by the same hotfixes. Access Anywhere is a remote-access path into the HMI layer, so treat its gateway like any other remote-access appliance.
What are the System Platform and Application Server vulnerabilities?
System Platform advisories run from 2019 to 2025 and cluster around credentials, the AutoBuild service and local privilege. The table lists the ten CVEs:
| CVE | Weakness | CISA CVSS v3 | NVD Primary | Fix or mitigation named |
|---|---|---|---|---|
| CVE-2019-6525 | Low-privilege user can obtain the ArchestrA network user account credentials through an API | 8.8 | v3.1 8.8 | System Platform 2017 Update 3 (LFSEC00000135) |
| CVE-2021-33008 | AutoBuild: missing authentication | 8.8 | v3.1 9.8 | Disable AutoBuild, or Communication Drivers Pack 2020 R2.1 (AVEVA-2021-002) |
| CVE-2021-33010 | AutoBuild: uncaught exception (denial of service) | 7.5 | v3.1 7.5 | Same |
| CVE-2021-32981 | AutoBuild: path traversal | 7.2 | v3.1 7.2 | Same |
| CVE-2021-32985 | AutoBuild: origin validation error | 7.2 | v3.1 7.2 | Same |
| CVE-2021-32977 | AutoBuild: improper signature verification | 7.2 | v3.1 7.2 | Same |
| CVE-2022-0835 | Cleartext credentials of the network account or logged-in users in process memory | 8.1 | v3.1 5.5 | System Platform 2020 R2 SP1, or 2020 P01 for 2020 |
| CVE-2023-33873 | Operations Control Logger runs with unnecessary privileges (local escalation to System) | 7.8 | v3.1 7.8 | System Platform 2023 or later, or Operations Control Logger v22.1 (AVEVA-2023-003) |
| CVE-2023-34982 | Operations Control Logger arbitrary file delete with System privilege | 5.5 | v3.1 7.1 | Same |
| CVE-2025-8386 | Stored script in App Object help files, Application Server IDE | 6.9 | none | System Platform 2023 R2 SP1 P03 or later (AVEVA-2025-005) |
AVEVA's bulletin AVEVA-2021-002 says the AutoBuild service is intended only for the GR node during configuration and should be disabled on all Runtime nodes; if AutoBuild is unused on the GR node, disabling it there too is a mitigation that needs no patch. The five AutoBuild flaws were reported by Sharon Brizinov of Claroty, and AVEVA says that chained together they can give code execution with system privileges.
AVEVA-2023-003 lists many more products that carry the Operations Control Logger, among them Historian, InTouch, Application Server, Edge, Plant SCADA and Communication Drivers Pack, and warns that System Platform 2020 through 2020 R2 SP1 cannot be newly installed on top of products already patched with Operations Control Logger v22.1. Its general precautions are to disable Guest or anonymous local accounts and allow only trusted users to log in on those nodes. For CVE-2025-8386, AVEVA also asks owners to audit who is in the aaConfigTools operating system group, since only its members can exploit the flaw.
Which SuiteLink and Historian flaws matter most?
SuiteLink is installed with InTouch, System Platform, Historian and the Communication Drivers Pack, so one flaw reaches many nodes:
- CVE-2021-32959 (ICSA-21-231-01, Claroty): a heap overflow while the SuiteLink server processes commands 0x05 and 0x06. CISA scores it 8.1; NVD's Primary score is v3.1 9.8. The same advisory has CVE-2021-32963, a NULL pointer dereference on commands 0x03 and 0x10 (7.5 from both), and four more denial-of-service CVEs. AVEVA-2021-003 says the server crashes on a malicious packet and that code execution is theoretically possible but has no proof of concept. The fix is SuiteLink 3.2.002 for System Platform, InTouch and Historian 2014 R2 SP1 P02 through 2020 R2 P01; Communication Drivers Pack 2020 R2 and earlier take SuiteLink 3.2.002 or Communication Drivers Pack 2020 R2.1. SuiteLink clients are not affected.
- CVE-2024-7113 (ICSA-24-226-01, reported through Idaho National Laboratory's CyTRICS program): the SuiteLink server consumes excessive resources and slows data I/O during an attack. CISA scores it v3.1 7.5 and v4 8.7; NVD had no Primary score as of 2026-11-24. It affects SuiteLink 3.7.0 and earlier as shipped with Historian, InTouch and Application Server up to 2023 R2 P01, Communication Drivers Pack up to 2023 R2 and Batch Management up to 2023. The fix is SuiteLink 3.7.100, and AVEVA's bulletin AVEVA-2024-007 adds host or network firewall rules so that port 5413 accepts only trusted sources.
AVEVA Historian has one recent CVE:
- CVE-2024-6456 (ICSA-24-228-10): SQL injection that runs under the privileges of a Historian REST interface user who opens a crafted URL. CISA scores it v3.1 8.1 and v4 8.5; NVD had no Primary score as of 2026-11-24. AVEVA's recommended fix is System Platform 2023 R2 P01; alternatives are System Platform 2023 P04 for Historian 2023 through 2023 P03, or System Platform 2020 R2 SP1 P01 plus Hotfix 3190476 for Historian 2020 R2 through 2020 R2 SP1 P01. AVEVA also asks REST users to check that shared URLs come from a trusted source.
SuiteLink parsing bugs are the classic memory-safety pattern described in the memory corruption fix guide, here in Windows server software rather than firmware.
What are the PI Server, PI Data Archive and PI Web API vulnerabilities?
The PI System advisories since 2024 are mostly denial of service in PI Data Archive services and code execution through crafted XML:
| CVE | Product and weakness | CISA CVSS v3 | NVD Primary | Fix named |
|---|---|---|---|---|
| CVE-2023-34348 | PI Message Subsystem crash, unauthenticated | 7.5 | v3.1 7.5 | PI Server 2023 Patch 1, or 2018 SP3 Patch 6 (AVEVA-2024-001) |
| CVE-2023-31274 | PI Message Subsystem memory exhaustion, unauthenticated | 5.3 | v3.1 5.3 | Same |
| CVE-2024-3468 | PI Web API deserialization through XML import | 7.6 | none | PI Web API 2023 SP1 or later (AVEVA-2024-003) |
| CVE-2024-3467 | PI AF Client deserialization when PI System Explorer imports XML | 7.3 | v3.1 7.8 | PI AF Client 2023 Patch 1, or 2018 SP3 Patch 5 (AVEVA-2024-004) |
| CVE-2025-44019 | PI Data Archive uncaught exception, authenticated | 7.1 | none | PI Server 2024, or 2018 SP3 Patch 7 (AVEVA-2025-001) |
| CVE-2025-36539 | PI Data Archive uncaught exception, authenticated | 6.5 | none | PI Server 2024 |
| CVE-2025-2745 | PI Web API stored script in annotation attachments | 6.5 | none | PI Web API 2023 SP1 Patch 1 or later (AVEVA-2025-003) |
| CVE-2026-1507 | PI Data Archive uncaught exception, unauthenticated | 7.5 | none | PI Server 2024 R2, or 2018 SP3 Patch 8 (AVEVA-2026-002) |
CVE-2026-1507 is the newest and the most serious of the PI Data Archive flaws: CISA's ICSA-26-041-03 of 10 February 2026 says an unauthenticated attacker can remotely crash core PI services, and covers PI Server 2024, 2023 Patch 1, 2023 and 2018 SP3 Patch 7 and earlier. CISA scores it v3.1 7.5 and v4 8.7. AVEVA says the issue was self-discovered under OSIsoft's ethical disclosure program.
The PI advisories repeat the same defensive measures: limit port 5450 to trusted workstations, users and software; set PI Network Manager, PI Archive Subsystem and the other PI Data Archive services to restart automatically and monitor that they are alive; and, for PI Web API, set DisableWrites to true on read-only instances, remove the Core Endpoints feature where an instance only collects data from AVEVA Adapters through OMF, and restrict AF server administrator rights. For CVE-2025-2745, AVEVA adds reviewing the attachment file-extension allowlist and granting the Annotate right only to trusted users. CVE-2025-44019 can also lose data held in snapshots or the write cache, depending on when the crash happens.
Which AVEVA Edge and Plant SCADA flaws should owners know?
AVEVA Edge advisories centre on project files and DLL loading on the engineering and runtime computer:
- CVE-2023-6132 (ICSA-24-032-03): Edge 2020 R2 SP2 and earlier can be tricked into loading an unsafe DLL, giving code execution and privilege escalation to someone with file system access. CISA scores it 7.3; NVD's Primary score is v3.1 7.8. Fixed in Edge 2023 or 2020 R2 SP2 P01.
- CVE-2025-9317 (ICSA-25-317-03): Edge 2023 R2 and earlier protect app-native and Active Directory passwords in project files and offline cache files with weak hashes that can be brute-forced. CISA scores it 8.4; NVD had no Primary score as of 2026-11-24. The fix is the Edge 2023 R2 P01 security update, migrating old project files and making users change their passwords. AVEVA warns the migration is one-way, and asks owners to restrict read access to project copies that cannot be migrated and to set a strong project master password.
- ICSA-22-249-02 lists six earlier CVEs in Edge 2020 R2 SP1 and prior, from DLL search paths to deserialization and XML external entities, fixed by hotfix HF 2020.2.00.40 on top of 2020 R2 SP1.
Plant SCADA, formerly Citect SCADA, has one critical recent CVE:
- CVE-2023-1256 (ICSA-23-073-04, reported by the UK's National Cyber Security Centre): improper authorization lets an unauthenticated user remotely read data, cause a denial of service and tamper with alarm states. CISA, AVEVA and NVD all score it 9.8. It affects Plant SCADA 2023, Plant SCADA 2020R2 Update 10 and earlier, and Telemetry Server 2020 R2 SP1 and earlier. The fixes are Plant SCADA 2023 Update 1, Plant SCADA 2020R2 Update 11, and Telemetry Server 2020 R2 SP2.
Which other AVEVA products have advisories worth knowing?
Two newer advisories touch engineering and pipeline software that often sits next to the HMI layer:
- CVE-2025-61937 (ICSA-26-015-01, Veracode): code injection in AVEVA Process Optimization 2024.1 and earlier lets an unauthenticated attacker run code with the privileges of the taoimr service. CISA scores it 10.0; NVD had no Primary score as of 2026-11-24. The fix is Process Optimization v2025; until then, AVEVA asks owners to restrict the taoimr service, which listens on 8888 and 8889 (TLS) by default, to trusted sources. The same advisory lists six more CVEs.
- CVE-2026-81822 (advisory page): Pipeline Integrity Monitor 2025 SP1 P1 and earlier store PIMBoards passwords with a weak hash. CISA scores it 8.4. The fix is the 2025 SP1 P2 security update with a one-way project migration and a password reset (AVEVA-2026-006).
The latest notice on AVEVA's Cyber Security Updates page, AVEVA-2026-007, concerns unauthorized access to AVEVA's corporate SharePoint. As of 2026-11-24, AVEVA states it has no impact on AVEVA software or production environments and recommends no specific defensive measures.
How do you harden AVEVA InTouch, System Platform and PI systems?
Work from AVEVA's and CISA's own mitigations:
Update SuiteLink on every nodeto 3.7.100, the version AVEVA names for the 2024 advisory and later than the 3.2.002 fix for the 2021 flaws, and firewall port 5413 so that only the InTouch, Application Server, Historian and driver hosts that need it can connect. Disable AutoBuild on Runtime nodes, and on the GR node when unused, or apply Communication Drivers Pack 2020 R2.1. Move System Platform to 2023 R2 SP1 P03 or later, which is at or above the System Platform releases AVEVA names for the Historian and Operations Control Logger fixes, and keep the aaConfigTools group to trusted engineers. Bring PI Server to 2024 R2, or 2018 SP3 Patch 8 on the older line, limit port 5450, and set PI services to restart automatically. Harden PI Web API: 2023 SP1 Patch 1 or later, DisableWrites on read-only instances, and no Core Endpoints on OMF-only collectors. Patch Access Anywhere Secure Gatewaysand apply AVEVA's language-bar, account and group policy mitigations to the streamed HMI server. Protect project filesfor Edge and Pipeline Integrity Monitor with access control lists, a trusted chain of custody and the one-way migration AVEVA requires. Firewall the control networkCISA asks owners to keep control system devices off the internet, put control networks behind firewalls isolated from business networks, and use VPNs for remote access, keeping the VPN itself updated.
AVEVA's own advisories point to NIST SP 800-82 for general ICS security, covered in the NIST SP 800-82 guide. For zone and conduit requirements on the historian boundary, see the IEC 62443-3-3 system security requirements guide, and plan updates through a change process such as the one in the IEC 62443-2-3 patch management guide. If you bridge HMI or historian data to other systems over OPC UA, the OPC UA security guide covers the security modes to require.
How do you check which version an AVEVA system runs?
AVEVA's fixes depend on product release, patch level and shared components, so record each one:
Record the System Platform release and patch per node(for example 2020 R2 SP1 P01 or 2023 R2 P01), and which nodes are GR, Runtime, Historian or InTouch-only. Record the SuiteLink version separatelyIt is updated on its own (3.2.002, 3.7.100), so a current HMI release does not prove a current SuiteLink. Record PI Server, PI Data Archive, PI AF Client and PI Web API versionsindividually; the PI advisories name each one with its own patch line (2018 SP3 Patch 5 to 8, 2023 Patch 1, 2024, 2024 R2). Record Access Anywhere Secure Gateway versions(20.0.1, 20.1.0) and whether the hotfix is installed. Do not rely on NVD aloneAs of 2026-11-24, 11 of the 31 CVEs in this guide had no NVD Primary score and NVD's description of CVE-2022-23854 gives a narrower version range than AVEVA's bulletin. Read the bulletins.
How do you monitor AVEVA HMI and historian networks?
Start with a baseline of which hosts talk to each HMI, platform, historian and PI node, and on which ports, then alert on changes:
- New hosts connecting to port 5413 on SuiteLink servers, which fits CVE-2021-32959 and CVE-2024-7113.
- Connections to port 5450 on PI Data Archive nodes from outside the list of PI clients and interfaces, which fits CVE-2023-34348 and CVE-2026-1507.
- Unexpected restarts of PI Network Manager, PI Archive Subsystem or other PI Data Archive services, whose liveness AVEVA asks owners to monitor.
- Sessions to the Access Anywhere Secure Gateway from unexpected sources, which fits CVE-2022-23854.
- Connections to ports 8888 or 8889 on Process Optimization servers from untrusted hosts, which fits CVE-2025-61937.
Flow records show who connected to which port and when, not which SuiteLink command or PI call was sent. Map alerts to MITRE ATT&CK for ICS techniques such as exploitation of remote services and denial of service.
Worked example: what does a review of a water utility's AVEVA estate find?
Synthetic example, not a real site. A water utility runs System Platform 2020 R2 SP1 with InTouch operator stations, AVEVA Historian on the same release, PI Server 2018 SP3 Patch 6 in a site DMZ fed from the historian, PI Web API 2021 SP3 for dashboards, and InTouch Access Anywhere 2020 R2 for on-call staff.
| Observation | Why it matters | Action |
|---|---|---|
| SuiteLink 3.2.002 on all nodes | CVE-2024-7113 is open | Install SuiteLink 3.7.100; firewall port 5413 |
| AutoBuild service running on two Runtime nodes | AutoBuild is meant only for the GR node | Disable it on Runtime nodes |
| System Platform 2020 R2 SP1 without later patches | CVE-2023-33873, CVE-2023-34982 and CVE-2024-6456 are open | Plan System Platform 2023 R2 SP1 P03 |
| PI Server 2018 SP3 Patch 6 | CVE-2025-44019 and CVE-2026-1507 are open | Move to 2018 SP3 Patch 8 or PI Server 2024 R2; limit port 5450 |
| PI Web API 2021 SP3, writes enabled | CVE-2024-3468 and CVE-2025-2745 are open | Upgrade to 2023 SP1 Patch 1; set DisableWrites |
| Access Anywhere gateway reachable from the internet, no hotfix | CVE-2022-23854 is unauthenticated | Apply the Secure Gateway hotfix; put the gateway behind a VPN |
Where does passive monitoring fit in an AVEVA review?
A passive capture shows who talks to HMI, platform and historian nodes without logging in to anything. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from a mirror-port recording and builds a host-by-port inventory at connection level, including hosts using ports 5413 and 5450, and lists remote-access sessions that cross from outside the private address range. It does not decode SuiteLink, PI or Access Anywhere messages or read software versions from traffic. Component and version identification comes from the asset records and software lists you share. SoftWSP matches the versions found against CVE, CISA KEV and FIRST EPSS data, and an engineer reviews the AI-written summary before it reaches you.
What are the common pitfalls?
- Patching InTouch or System Platform and leaving an older SuiteLink in place on the same node.
- Leaving AutoBuild running on Runtime nodes after commissioning.
- Treating the PI tier as IT-only, when its port 5450 and PI Web API reach back into the plant data path.
- Running Edge or Pipeline Integrity Monitor password migrations without keeping a plan for the old project copies that stay readable.
- Assuming one score: NVD rates CVE-2022-1467 at 9.9 where CISA says 7.4, and CISA rates CVE-2022-0835 at 8.1 where NVD says 5.5.
- Publishing an Access Anywhere gateway to the internet without the hotfix or a VPN in front of it.
This guide draws on AVEVA security bulletins AVEVA-2021-002, AVEVA-2021-003, AVEVA-2023-001, AVEVA-2023-002, AVEVA-2023-003, AVEVA-2024-005, AVEVA-2024-007, AVEVA-2025-001 and AVEVA-2026-002 and AVEVA's Cyber Security Updates page; CISA ICS advisories ICSA-18-200-02, ICSA-19-029-03, ICSA-21-159-03, ICSA-21-180-05, ICSA-21-231-01, ICSA-22-067-02, ICSA-22-130-05, ICSA-22-249-02, ICSA-22-342-02, ICSA-23-073-04, ICSA-23-318-01, ICSA-24-018-01, ICSA-24-032-03, ICSA-24-163-02, ICSA-24-163-03, ICSA-24-226-01, ICSA-24-228-10, ICSA-25-162-07, ICSA-25-162-08, ICSA-25-317-02, ICSA-25-317-03, ICSA-26-015-01, ICSA-26-041-03 and ICSA-26-253-01 and their CSAF records; NVD and CVE.org records; CISA KEV and FIRST EPSS, all checked as of 2026-11-24.
Put this guide to work
Frequently asked questions
Are any AVEVA, Wonderware or OSIsoft vulnerabilities in the CISA KEV catalog?
No. As of 2026-11-24, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.23, 1,792 entries) has no entry for AVEVA, Wonderware or OSIsoft, and none of the 31 CVEs in this guide is listed. The highest FIRST EPSS score among them, dated 2026-11-23, belongs to CVE-2022-23854, the InTouch Access Anywhere Secure Gateway path traversal, at 0.497. Next come CVE-2018-10628 in InTouch at 0.054 and CVE-2025-61937 in Process Optimization at 0.015; every other CVE here is below 0.014.
Which ports do AVEVA and CISA name for these products?
Three. AVEVA's bulletin AVEVA-2024-007 says SuiteLink listens on TCP port 5413 by default and should accept traffic only from trusted sources. AVEVA's PI bulletins and CISA's PI Server and PI Data Archive advisories ask owners to limit port 5450 on PI Data Archive nodes to trusted workstations, users and software. CISA's ICSA-26-015-01 says AVEVA Process Optimization listens on 8888 and 8889 (TLS) by default. For other PI System ports, AVEVA points to its PI System firewall port requirements knowledge base article.
How do I fix the 2021 SuiteLink and AutoBuild vulnerabilities in System Platform?
For SuiteLink (AVEVA-2021-003, ICSA-21-231-01), install SuiteLink 3.2.002 on System Platform, InTouch and Historian 2014 R2 SP1 P02 through 2020 R2 P01; Communication Drivers Pack 2020 R2 and earlier take SuiteLink 3.2.002 or Communication Drivers Pack 2020 R2.1. SuiteLink clients are not affected. For AutoBuild (AVEVA-2021-002, ICSA-21-180-05), disable the AutoBuild service on all Runtime nodes, and on the Galaxy Repository node too if you do not use it. Where AutoBuild must stay on, apply Communication Drivers Pack 2020 R2.1 on System Platform 2020 to 2020 R2 P01; 2017 U3 SP1 P01 needs Communication Drivers Pack 2020 R2 first.
What changed for PI Server owners in 2024 to 2026?
Three PI Data Archive advisories asked for upgrades. CVE-2023-34348 and CVE-2023-31274 in the PI Message Subsystem are fixed in PI Server 2023 Patch 1 or 2018 SP3 Patch 6. CVE-2025-44019 and CVE-2025-36539 are fixed in PI Server 2024, and CVE-2025-44019 also in 2018 SP3 Patch 7. CVE-2026-1507, an unauthenticated crash of core PI services, is fixed in PI Server 2024 R2 or 2018 SP3 Patch 8. Each advisory also asks owners to limit port 5450 and set PI services to restart automatically.
Why do NVD and CISA scores differ so much for AVEVA CVEs?
They score different assumptions. NVD's Primary score is CVSS v3.1 9.9 for the Access Anywhere language-bar escape CVE-2022-1467, where CISA says 7.4, and 9.8 for the AutoBuild flaw CVE-2021-33008, where CISA says 8.8. NVD is lower for the System Platform credential flaw CVE-2022-0835 (5.5 against CISA's 8.1). As of 2026-11-24, 11 of the 31 CVEs here had no NVD Primary score at all, only CISA's, so read both and name the scorer when you report a number.
Sources
- AVEVA: Cyber Security Updates (security bulletins index)
- AVEVA Security Bulletin AVEVA-2021-002: System Platform AutoBuild
- AVEVA Security Bulletin AVEVA-2021-003: SuiteLink Server
- AVEVA Security Bulletin AVEVA-2023-001: InTouch Access Anywhere and Plant SCADA Access Anywhere
- AVEVA Security Bulletin AVEVA-2023-002: Plant SCADA and Telemetry Server
- AVEVA Security Bulletin AVEVA-2023-003: Operations Control Logger
- AVEVA Security Bulletin AVEVA-2024-005: Historian Server
- AVEVA Security Bulletin AVEVA-2024-007: SuiteLink Server
- AVEVA Security Bulletin AVEVA-2025-001: PI Data Archive
- AVEVA Security Bulletin AVEVA-2026-002: PI Data Archive
- CISA CSAF: ICSA-18-200-02 AVEVA InTouch
- CISA CSAF: ICSA-21-159-03 AVEVA InTouch
- CISA CSAF: ICSA-22-130-05 AVEVA InTouch Access Anywhere and Plant SCADA Access Anywhere
- CISA CSAF: ICSA-22-342-02 AVEVA InTouch Access Anywhere and Plant SCADA Access Anywhere
- CISA CSAF: ICSA-19-029-03 AVEVA Wonderware System Platform
- CISA CSAF: ICSA-21-180-05 AVEVA System Platform (Update A)
- CISA CSAF: ICSA-22-067-02 AVEVA System Platform
- CISA CSAF: ICSA-23-318-01 AVEVA Operations Control Logger
- CISA CSAF: ICSA-25-317-02 AVEVA Application Server IDE
- CISA CSAF: ICSA-21-231-01 AVEVA SuiteLink Server
- CISA CSAF: ICSA-24-226-01 AVEVA SuiteLink Server
- CISA CSAF: ICSA-24-228-10 AVEVA Historian Web Server
- CISA CSAF: ICSA-24-018-01 AVEVA PI Server
- CISA CSAF: ICSA-24-163-02 AVEVA PI Web API
- CISA CSAF: ICSA-24-163-03 AVEVA PI Asset Framework Client
- CISA CSAF: ICSA-25-162-07 AVEVA PI Data Archive
- CISA CSAF: ICSA-25-162-08 AVEVA PI Web API
- CISA CSAF: ICSA-26-041-03 AVEVA PI Data Archive
- CISA CSAF: ICSA-22-249-02 AVEVA Edge 2020 R2 SP1 and all prior versions
- CISA CSAF: ICSA-24-032-03 AVEVA Edge products (formerly InduSoft Web Studio)
- CISA CSAF: ICSA-25-317-03 AVEVA Edge
- CISA CSAF: ICSA-23-073-04 AVEVA Plant SCADA and AVEVA Telemetry Server
- CISA CSAF: ICSA-26-015-01 AVEVA Process Optimization
- CISA CSAF: ICSA-26-253-01 AVEVA Pipeline Integrity Monitor
- NVD: CVE-2018-10628 (InTouch stack buffer overflow)
- NVD: CVE-2021-33008 (System Platform AutoBuild missing authentication)
- NVD: CVE-2022-23854 (InTouch Access Anywhere path traversal)
- NVD: CVE-2023-1256 (Plant SCADA and Telemetry Server improper authorization)
- CVE.org: CVE-2026-1507 (PI Data Archive uncaught exception)
- CISA Known Exploited Vulnerabilities catalog
- FIRST: Exploit Prediction Scoring System (EPSS)