CVE-2011-3330 is a buffer overflow in the UnitelWay Windows device driver that Schneider Electric shipped with Unity Pro and PL7 Pro, OPC Factory Server, Vijeo Citect, Monitor Pro and the Telemecanique Driver Pack. A local user, and possibly a remote attacker, could run code through a crafted system parameter. NVD scores it 7.2 (CVSS v2). Schneider released a hotfix that replaces one of the driver libraries.
Vulnerability summary
CVSS base score
7.2
High severity
EPSS score (FIRST)
1.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2011-3330 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric UnitelWay Windows Device Driver in Unity Pro, PL7 Pro, OPC Factory Server, Vijeo Citect, Monitor Pro and Telemecanique Driver Pack | cpe:2.3:a:schneider-electric:unity_pro:*:*:*:*:*:*:*:* | NVD and CISA ICSA-11-277-01: Unity Pro <= 6, OPC Factory Server 3.34, Vijeo Citect <= 7.20, Telemecanique Driver Pack <= 2.6, Monitor Pro <= 7.6, PL7 Pro <= 4.5 (Windows XP). Fix: Schneider hotfix replacing a UnitelWay driver library |
What does this mean for affected devices?
NVD's description reads: "Buffer overflow in the UnitelWay Windows Device Driver, as used in Schneider Electric Unity Pro 6 and earlier, OPC Factory Server 3.34, Vijeo Citect 7.20 and earlier, Telemecanique Driver Pack 2.6 and earlier, Monitor Pro 7.6 and earlier, and PL7 Pro 4.5 and earlier, allows local users, and possibly remote attackers, to execute arbitrary code via an unspecified system parameter." NVD's Primary score is CVSS v2 7.2 (AV:L/AC:L/Au:N/C:C/I:C/A:C) with CWE-119, so NVD rates it as a local attack. NVD published the record on 2011-11-04; CERT/CC assigned it with no CNA score (NVD, CVE record).
Which Schneider products are affected?
CISA advisory ICSA-11-277-01 (CSAF), "Schneider Electric UnitelWay Buffer Overflow", lists the same six packages on Windows XP: Unity Pro and PL7 Pro, OPC Factory Server 3.34, the Vijeo Citect and Monitor Pro SCADA packages and the Telemecanique Driver Pack. The flaw sits in a Windows driver that these packages install on the PC, so the hosts to fix are the Windows engineering and SCADA machines, not the PLCs. CISA scores it CVSS v2 7.2 with CWE-119.
How do I fix it?
Schneider Electric created a fix that modifies one of the libraries of the UnitelWay Windows Device Driver and published a customer notification. Because the fix does not change how the driver works, Schneider recommends that all customers install it. CISA's advisory names the hotfix package HFPEP0047398R. Vijeo Citect users should ask Schneider's SCADA and MES support centre and users of the other products their local Schneider support centre for the fix. On hosts that no longer need UnitelWay at all, removing the driver also removes the exposure. Keep engineering workstations off the internet and limit who can log on to them.
CVE-2013-0662 is a comparable overflow in Schneider's Modbus serial driver, and CVE-2019-6808 covers a later Modicon PLC flaw. The memory corruption guide explains this class of bug, and the OT/ICS security guide for small manufacturers covers protecting engineering workstations.
CVE-2011-3330 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0130, a percentile of 70.6, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2011-11-04; NVD Primary CVSS v2 7.2 AV:L/AC:L/Au:N/C:C/I:C/A:C; CWE-119; CPEs monitor_pro <=7.6, opc_factory_server <=3.34, pl7_pro <=4.5, telemecanique_driver_pack <=2.6, unity_pro <=6.0, vijeo_citect <=7.20. — NVD
- CISA ICSA-11-277-01 CSAF (read 2026-11-28): CWE-119, CVSS v2 7.2; six products on Windows XP; Schneider fix modifies one of the driver libraries, recommends all customers install it; hotfix HFPEP0047398R.zip; contact SCADA and MES support (Vijeo Citect) or local support centre. — CISA ICSA-11-277-01
- CVE record (read 2026-11-28): state PUBLISHED, assigner certcc; affected n/a; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.01302, percentile 0.70571, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Does CVE-2011-3330 affect Schneider PLC firmware?
No. The flaw is in the UnitelWay Windows device driver that Unity Pro, PL7 Pro, OPC Factory Server, Vijeo Citect, Monitor Pro and the Telemecanique Driver Pack install on the Windows PC. The PLCs themselves are not listed.
How does Schneider fix it?
Schneider released a hotfix that modifies one of the UnitelWay driver libraries (named HFPEP0047398R in the CISA advisory) and recommends that every customer install it, since it does not change how the driver works. Ask Schneider support for the package.
Why is the NVD score only 7.2?
NVD scores it with a local attack vector (AV:L), because the description says local users can exploit it and remote attackers only possibly. CISA uses the same 7.2 score.
Is CVE-2011-3330 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0130 (percentile 70.6) in the 2026-11-27 dataset.