Two operators at a control-room desk with a row of monitors, a laptop and keyboards

OT/ICS security

GE Proficy and CIMPLICITY vulnerabilities: Historian, iFIX, Plant Applications, Machine Edition and CIMPLICITY HMI/SCADA, fixed versions and hardening

Last updated:

GE's Proficy software (Historian, iFIX, Plant Applications, Machine Edition) and CIMPLICITY HMI/SCADA had no CVE in CISA's KEV catalog as of 2026-11-28, but their published flaws fall into four families: unauthenticated network services, path traversal and file upload, memory corruption in services and project files, and local privilege escalation on Windows nodes. Fixes ship as new releases or as cumulative SIM updates per release.

The rest of this guide maps each product to its place in a plant network, names the ports and services that GE and CISA give, walks through 32 CVE ids by product with the fixed versions and mitigations from CISA's ICS advisories, which carry GE's and Emerson's own recommendations, and ends with hardening, version checks, monitoring and a worked example. Scores name their scorer: CISA's advisory score and NVD's Primary score for the same CVE often differ, and the oldest advisories carry only CVSS v2.

This guide covers plant software. For GE Vernova's protection relays, see the separate UR relay vulnerabilities guide.

Key takeaways

  • This guide covers plant software.
  • CISA's advisories use the owner's name at the time: GE Intelligent Platforms for 2011 to 2014, GE Digital for 2016 to 2023, and GE Vernova for the August 2025 CIMPLICITY advisory.
  • CISA's 2011 and 2012 Historian advisories note that iFIX and CIMPLICITY installations can include Historian, so a Historian flaw can sit on an HMI node that nobody lists as a historian.
  • Three port numbers appear in the advisories, all in older ones.

Who makes Proficy and CIMPLICITY, and who publishes the advisories?

As of 2026-11-28, proficy.com redirects to Velotic, which describes itself as "a new independent industrial software company bringing together Proficy Software, formerly part of GE Vernova, along with ThingWorx and Kepware, formerly part of PTC." Velotic's Proficy product page lists CIMPLICITY, iFIX, Historian, CSense, Operations Hub, Scheduler, Smart Factory MES and Tracker. As of 2026-11-28, Velotic's public site lists no product security advisory page, and the GE support links in the advisories now resolve to a sign-in portal at softwaresupport.gevernova.com.

CISA's advisories use the owner's name at the time: GE Intelligent Platforms for 2011 to 2014, GE Digital for 2016 to 2023, and GE Vernova for the August 2025 CIMPLICITY advisory. The 2022 Proficy Machine Edition advisory appears under Emerson. Search all four names when you look for history on an installed product.

Where do Proficy and CIMPLICITY sit in a plant network?

CISA's advisories list the vendor as headquartered in the United States with products deployed worldwide; ICSA-20-098-02 names the chemical, critical manufacturing, energy, food and agriculture, and water sectors for CIMPLICITY. The products fall into five roles:

Product What it does Typical place in the network
CIMPLICITY HMI/SCADA Operator screens (CimView), screen editor (CimEdit), project servers, and web viewing through GlobalView, WebView and ThinView Supervisory servers and operator stations
iFIX HMI/SCADA Operator HMI and SCADA nodes with a web server component Supervisory servers and operator stations
Proficy Historian Time-series data collection and storage (Data Archiver service) Site operations level, often installed alongside iFIX or CIMPLICITY
Plant Applications Manufacturing execution: Server Manager, Gateway, Remote Data Service and License Manager services Site operations and business boundary
Proficy Machine Edition Engineering software that programs PACSystems controllers over the SRTP protocol Engineering workstations

CISA's 2011 and 2012 Historian advisories note that iFIX and CIMPLICITY installations can include Historian, so a Historian flaw can sit on an HMI node that nobody lists as a historian. For the zoning behind the table, see the Purdue model guide.

Which ports and services do GE and CISA name?

Three port numbers appear in the advisories, all in older ones. The newer advisories describe local or file-based attacks and name no ports.

Path Product What the sources say
TCP port 14000, ihDataArchiver.exe Proficy Historian 4.5 and earlier A crafted session can corrupt memory or run code without authentication (CVE-2012-0229, ICSA-12-032-01)
TCP port 12401, PRLicenseMgr.exe Plant Applications 5.0 and earlier A crafted TCP session can corrupt memory or run code (CVE-2012-0231, ICSA-12-032-02)
TCP port 10212, CimWebServer.exe CIMPLICITY WebView before 8.0 SIM 27, 8.1 SIM 25 and 8.2 SIM 19 Buffer overflows from crafted packets can run code (CVE-2013-2785, ICSA-13-170-01)
CIMPLICITY built-in web server (HTTP) CIMPLICITY GlobalView, WebView and ThinView Path traversal and crafted requests (CVE-2013-0653, CVE-2013-0654, CVE-2014-0750); GE's workaround is to disable the built-in server or host the pages on IIS
SRTP sessions to the controller Machine Edition 9.00 and earlier with PACSystems No authentication or authorization of packets after the connection is set up (CVE-2022-2793, ICSA-22-228-06)

CISA's ICSA-12-341-01 records GE's point that when the pages are hosted on IIS, CimWebServer.exe still runs but "is no longer listening on a port that is processing HTTP traffic." The BOD 23-02 guide on internet-exposed management interfaces shows how to confirm that none of these services answers from outside.

Which CIMPLICITY vulnerabilities did CISA publish?

CIMPLICITY has the longest record: unauthenticated web server flaws up to 2014, then mostly local privilege escalation and file-parsing memory corruption from 2016 on. The table lists 16 CVE ids from 11 advisories:

CVE Weakness CISA score NVD Primary Fix or mitigation named
CVE-2013-0653 Path traversal in WebView substitute.bcl, unauthenticated file read (4.01 to 8.0) v2 4.3 v2 4.3 GE patches GEIP12-13 and GEIP12-19 with configuration changes (ICSA-13-022-02)
CVE-2013-0654 CimWebServer crafted packet, command execution or crash (4.01 to 8.0) v2 8.8 v2 9.3 Same
CVE-2013-2785 Buffer overflows in CimWebServer.exe via TCP port 10212 v2 8.8 v2 9.3 CIMPLICITY 8.2 SIM 19, 8.1 SIM 25 or 8.0 SIM 27 (ICSA-13-170-01)
CVE-2014-0750 Path traversal in WebView gefebt.exe, code execution from a crafted HTTP request v2 7.5 v2 7.5 Delete or move every web-reachable copy of gefebt.exe (ICSA-14-023-01); NVD lists CIMPLICITY through 8.2 SIM 24 as affected
CVE-2016-5787 Service DACLs let local users change a service configuration v3 5.7 v3.1 6.3 CIMPLICITY 8.2 SIM 27 or later (ICSA-16-194-02)
CVE-2017-12732 Stack buffer overflow from an unchecked packet length (9.0 and earlier) v3 6.8 v3.0 6.8 CIMPLICITY 9.5 or later; Series 90 TCP/IP support is deprecated (ICSA-17-278-01A)
CVE-2020-6992 Local privilege escalation, systemwide configuration change (10.0 and earlier) v3 6.0 v3.1 6.7 CIMPLICITY 11.0 or newer (ICSA-20-098-02)
CVE-2022-21798 Cleartext transmission of credentials (all versions) v3 7.5 v3.1 9.8 Configure communication encryption per the Secure Deployment Guide; IPsec per GE's Windows hardening guide (ICSA-22-053-02)
CVE-2022-23921 Improper privilege management, local escalation and code execution (11.1 and earlier) v3 7.5 v3.1 7.8 The CIMPLICITY release of January 2022, plus restricting which projects may run (ICSA-22-053-01)
CVE-2022-2948 Heap buffer overflow when opening a crafted file (2022 and earlier) v3 7.8 v3.1 7.8 Secure Deployment Guide sections 3.5 Projects and 4.2 CimView (ICSA-22-326-04)
CVE-2022-2952 Uninitialized pointer access in gmmiObj v3 7.8 v3.1 7.8 Same
CVE-2022-3084 Uninitialized pointer access in gmmiObj v3 7.8 v3.1 7.8 Same
CVE-2022-3092 Out-of-bounds write v3 7.8 v3.1 7.8 Same
CVE-2022-2002 Untrusted pointer dereference in gmmiObj v3 7.8 v3.1 7.8 Same
CVE-2023-3463 Memory corruption, including a heap buffer overflow, from documents of untrusted origin (all versions not following the SDG) v3 6.6 v3.1 9.8 Follow the Secure Deployment Guide; latest CIMPLICITY from GE (ICSA-23-199-06)
CVE-2023-4487 Process control: malicious configuration files in the web server execution path give SYSTEM (2023) v3 7.8 v3.1 7.8 CIMPLICITY 2023 SIM 1 (ICSA-23-243-02)

Two notes on the 2022 to 2025 advisories. GE maintains, per ICSA-22-053-01, that CVE-2022-23921 needs login access to a machine running CIMPLICITY that is not already running a project and is licensed for multiple projects. ICSA-22-326-04 offers no fixed release, only Secure Deployment Guide sections, so CIMPLICITY 2022 and earlier stay exposed to those five file-parsing flaws unless project and screen files come only from trusted sources.

The newest advisory, ICSA-25-240-06 of August 2025, describes an uncontrolled search path element (CWE-427) in CIMPLICITY 2024, 2023, 2022 and 11.0 that lets a low-privileged local user escalate privileges. CISA scores it CVSS v3.1 7.8, and GE Vernova's fix is CIMPLICITY 2024 SIM 4 (knowledge base article 000071725), with the Secure Deployment Guide for owners who cannot upgrade. The advisory lists CVE-2025-7719, but as of 2026-11-28 the CVE.org record for CVE-2025-7719, filed by GE Vernova, describes a path traversal in GE Vernova Smallworld 5.3.5 and earlier. Track this CIMPLICITY flaw by advisory id and fixed SIM. For the code side of the file-parsing family, see the memory corruption fix guide; the path traversal pattern behind CVE-2013-0653 and CVE-2014-0750 is covered in the path traversal fix guide.

What are the Proficy Historian vulnerabilities?

Historian advisories cluster in two periods: unauthenticated Data Archiver memory corruption in 2011 and 2012, and five network flaws in Historian 7.0 and later in January 2023.

CVE Weakness CISA score NVD Primary Fix or mitigation named
CVE-2011-1918 Stack buffer overflow in the Data Archiver service from crafted TCP traffic v2 10.0 v2 10.0 Historian 4.0 SIM 12, 3.5 SIM 17 or the 3.1 SIM named in ICSA-11-243-03A
CVE-2012-0229 Data Archiver memory corruption from a crafted session on TCP port 14000 (4.5 and earlier) v2 10.0 v2 10.0 Updates for Historian 3.1, 3.5, 4.0 and 4.5; move from releases older than 3.1 first (ICSA-12-032-01)
CVE-2022-46732 Authentication bypass: a command runs even when local service authentication fails v3 9.8 v3.1 9.8 Historian 2023, or the SIM for each affected version (ICSA-23-017-01)
CVE-2022-46660 Unrestricted file upload: write files with full control of path and content v3 7.5 v3.1 6.5 Same
CVE-2022-43494 Improper access control: read any file on the system v3 7.5 v3.1 6.5 Same
CVE-2022-46331 Improper access control: delete any file on the system v3 7.5 v3.1 8.1 Same

For the 2011 and 2012 flaws, GE's instructions in the CISA advisories give iFIX and CIMPLICITY owners two options: apply the Historian SIM, or uninstall Historian if it is not in use. ICSA-23-017-01 lists a fifth CVE, a weak password encoding flaw that needs network access and the decryption key; the same Historian 2023 release and SIMs cover it.

Which iFIX vulnerabilities should owners know?

The three iFIX CVE ids in this guide are local privilege escalation flaws, two through configuration permissions and one through the web server execution path:

CVE Weakness CISA score NVD Primary Fix or mitigation named
CVE-2019-18243 Local user can change systemwide iFIX configuration through the registry (6.1 and earlier) v3 6.1 v3.1 5.5 iFIX 6.5 and the iFIX Secure Deployment Guide (ICSA-21-040-01)
CVE-2019-18255 Local user can change systemwide iFIX configuration through section objects v3 6.1 v3.1 5.5 Same
CVE-2023-0598 Code injection: malicious configuration files in the web server execution path give full control of the HMI (2022, 6.1, 6.5) v3 7.8 v3.1 9.8 iFIX 2023, or the WebSecurity SIM for iFIX 2022, 6.1 or 6.5, plus ACLs per the Secure Deployment Guide (ICSA-23-073-03)

CVE-2023-0598 in iFIX and CVE-2023-4487 in CIMPLICITY 2023 describe the same pattern in two products: a local attacker places configuration files in the path the web server loads them from. Both advisories came from GE Digital in 2023.

What about Plant Applications and Machine Edition?

Plant Applications has two network-reachable flaws from 2011 and 2012:

CVE Weakness CISA score NVD Primary Fix or mitigation named
CVE-2011-1919 Stack buffer overflows in PRProficyMgr.exe, PRGateway.exe, PRRDS.exe and PRLicenseMgr.exe from crafted TCP traffic v2 10.0 v2 10.0 Plant Applications 5.0 SIM 43 or 4.4.1 SIM v10 (ICSA-11-243-01; NVD's description says 4.4.1 SIM 101)
CVE-2012-0231 PRLicenseMgr.exe memory corruption from a crafted TCP session on port 12401 (5.0 and earlier) v2 10.0 v2 10.0 Updates for 5.0 and 4.4.1; unsupported releases through GE support (ICSA-12-032-02)

Proficy Machine Edition programs PACSystems controllers. CISA's ICSA-22-228-06 lists six CVEs and warns that exploitation could allow hidden code execution on the connected PLC and malicious files moving from the PLC to the workstation. Two show the file families:

CVE Weakness CISA score NVD Primary Fix or mitigation named
CVE-2022-2788 Path traversal (ZipSlip) through an upload: a malicious .BLZ file on the PLC reaches the engineering station (9.80 and earlier) v3 3.9 v3.1 7.3 Install as administrator but run as a non-administrator, program PLCs only over a trusted network, enable PLC authentication
CVE-2022-2791 Unrestricted upload: any file written into the PLC logic folder is uploaded to the PLC (9.00 and earlier) v3 5.9 v3.1 7.8 Verify operators and restrict who can upload files

For the SRTP flaw CVE-2022-2793, Emerson recommends the SRP-6a authentication that SRTP and SNP support. For the project directory permissions flaw CVE-2022-2792, the advisory says Emerson "plans to fix this vulnerability in a future version" and recommends the latest PAC Machine Edition with good physical security.

Why do NVD and CISA scores differ for these CVEs?

They score different assumptions, and the gap runs both ways. NVD's Primary CVSS v3.1 score is 9.8 for the CIMPLICITY file-parsing flaw CVE-2023-3463, where CISA says 6.6, 9.8 for the iFIX code injection CVE-2023-0598, where CISA says 7.8, and 9.8 for the CIMPLICITY cleartext credentials flaw CVE-2022-21798, where CISA says 7.5. NVD rates the Machine Edition ZipSlip flaw CVE-2022-2788 at 7.3 against CISA's 3.9. NVD is lower for the Historian file read and file upload flaws CVE-2022-43494 and CVE-2022-46660 (6.5 against CISA's 7.5) and for the iFIX registry flaws CVE-2019-18243 and CVE-2019-18255 (5.5 against 6.1). Advisories from 2011 to 2014 carry only CVSS v2 scores from both. As of 2026-11-28, every CVE id in the tables has an NVD Primary score, so name the scorer whenever you quote a number.

How are Proficy and CIMPLICITY fixes versioned?

GE names each fix as a release plus a SIM, and some fixes are a whole new release:

  • SIMs are cumulative. CISA's 2011 and 2012 advisories quote GE: "Proficy SIMs are cumulative. All future SIMs will include these updates." A node on CIMPLICITY 8.2 SIM 27 therefore also carries the SIM 19 fix for CVE-2013-2785.
  • Release lines changed naming. Numbered releases (CIMPLICITY 8.2, 9.5, 10.0, 11.0, 11.1; iFIX 5.x, 6.1, 6.5; Historian 3.x to 7.x) gave way to year releases (CIMPLICITY 2022 to 2024, iFIX 2022 and 2023, Historian 2023).
  • Some fixes are configuration only. ICSA-22-326-04 and ICSA-23-199-06 for CIMPLICITY and ICSA-22-053-02 for cleartext credentials give Secure Deployment Guide steps, not a fixed build.
  • Historian may come with the HMI. Check for Historian on every iFIX and CIMPLICITY node, as the 2011 and 2012 advisories advise.

Record release and SIM level separately: "CIMPLICITY 2023" alone does not tell you whether CVE-2023-4487 is fixed, because the fix is SIM 1.

How do KEV and EPSS rank these CVEs?

As of 2026-11-28, none of the 32 CVE ids here is in CISA's KEV catalog (version 2026.11.27, 1,808 entries), and the catalog has no GE, GE Vernova, Velotic or Emerson entry at all. FIRST EPSS scores dated 2026-11-27 put the old unauthenticated web and network flaws on top:

CVE Product EPSS (2026-11-27) Percentile
CVE-2014-0750 CIMPLICITY WebView 0.698 0.995
CVE-2013-0653 CIMPLICITY WebView 0.191 0.979
CVE-2012-0231 Plant Applications 0.069 0.948
CVE-2011-1918 Proficy Historian 0.063 0.944
CVE-2012-0229 Proficy Historian 0.047 0.926
CVE-2022-46732 Proficy Historian 0.010 0.625

Every other CVE id here scored below 0.047, and every one from 2016 onward below 0.011. Sites that still run pre-2014 CIMPLICITY WebView, Historian 4.x or Plant Applications 5.0 are the ones these numbers point at. The KEV and EPSS prioritization guide explains how to combine the two signals.

How do you harden Proficy and CIMPLICITY systems?

Work from GE's, Emerson's and CISA's own mitigations:

  1. Move to supported releases with current SIMs: CIMPLICITY 2024 SIM 4 or later, iFIX 2023 or the WebSecurity SIMs, Historian 2023 or the ICSA-23-017-01 SIMs.
  2. Turn off the CIMPLICITY built-in web serverif GlobalView, WebView and ThinView are not used, or host the pages on a patched IIS, as ICSA-12-341-01 describes. Remove web-reachable copies of gefebt.exe.
  3. Uninstall Historian where it is not used, GE's second option in the 2011 and 2012 advisories, and limit which hosts can reach port 14000 on the Historian servers that remain.
  4. Follow the Secure Deployment Guidesfor CIMPLICITY and iFIX: access control lists, project restrictions, communication encryption and screen files only from trusted sources.
  5. Protect .CIM screen and project filesICSA-14-289-02 advises not opening .CIM files from unknown sources, not sending them unprotected over public networks, and hashing them to detect tampering.
  6. Run Machine Edition as a non-administrator, program PLCs only over trusted networks, enable PLC authentication and use SRP-6a authentication for SRTP.
  7. Firewall the control networkCISA asks owners to keep control system devices off the internet, put control networks behind firewalls isolated from business networks, and use VPNs for remote access, keeping the VPN itself updated.

CISA's advisories point to its defense-in-depth paper and ICS recommended practices; the NIST SP 800-82 guide covers the same ground. Plan release and SIM changes through a change process such as the one in the IEC 62443-2-3 patch management guide. If you compare against another HMI and historian vendor, the AVEVA InTouch and System Platform guide uses the same structure.

How do you check which version a Proficy system runs?

The advisories tie fixes to release and SIM level, so collect both for each node:

  1. Record the product and release per node: CIMPLICITY, iFIX, Historian, Plant Applications or Machine Edition, with the release (8.2, 11.0, 2023, 2024).
  2. Record the SIM level separatelyCIMPLICITY 2023 needs SIM 1 for CVE-2023-4487 and CIMPLICITY 2024 needs SIM 4 for the ICSA-25-240-06 flaw.
  3. List Historian components on HMI nodes, including ones installed with iFIX or CIMPLICITY and never used.
  4. Note which web components are on: the CIMPLICITY built-in web server, WebView and ThinView, and the iFIX web server.
  5. Do not rely on CVE ids aloneAs of 2026-11-28 the CVE id in ICSA-25-240-06 points to a different product on CVE.org, and the oldest records carry only CVSS v2. Read the advisories.

How do you monitor Proficy and CIMPLICITY networks?

Start with a baseline of which hosts talk to each HMI, historian and MES node, and on which ports, then alert on changes:

  • New hosts connecting to TCP port 14000 on Historian nodes, which fits CVE-2011-1918 and CVE-2012-0229.
  • Connections to port 12401 on Plant Applications servers from outside the client list, which fits CVE-2012-0231.
  • HTTP sessions or TCP port 10212 connections to CIMPLICITY nodes from unexpected sources, which fits CVE-2013-2785 and CVE-2014-0750.
  • Engineering workstations reaching PACSystems controllers from networks you do not program from.

Flow records show who connected to which port and when, not which file was requested or which SRTP command was sent. Map alerts to MITRE ATT&CK for ICS techniques such as exploitation of remote services.

Worked example: what does a review of a food plant's Proficy estate find?

Synthetic example, not a real site. A food plant runs CIMPLICITY 2023 without SIMs on two SCADA servers with WebView on for the maintenance office, iFIX 6.5 on a packaging line, Proficy Historian 7.0 fed by both, Plant Applications for batch records, and Machine Edition on a shared engineering laptop.

Observation Why it matters Action
CIMPLICITY 2023, no SIM CVE-2023-4487 and the ICSA-25-240-06 flaw are open Move to CIMPLICITY 2024 SIM 4
CIMPLICITY WebView on, built-in web server Web paths were the entry point in older CIMPLICITY flaws Disable the built-in server if unused, or host on a patched IIS; restrict HTTP to the office subnet
iFIX 6.5 without the WebSecurity SIM CVE-2023-0598 is open Apply the iFIX 6.5 SIM or move to iFIX 2023; set ACLs
Historian 7.0 without the GED-23-01 SIM CVE-2022-46732 is network reachable and scored 9.8 by CISA Upgrade to Historian 2023 or apply the SIM; firewall the Historian ports to known collectors
Machine Edition run as administrator on a laptop that also browses the web CVE-2022-2788 and CVE-2022-2791 abuse files moving between PLC and workstation Run as a non-administrator; program PLCs only from the trusted network; enable PLC authentication

Where does passive monitoring fit in a Proficy review?

A passive capture shows who talks to HMI, historian and engineering nodes without logging in to anything. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from a mirror-port recording and builds a host-by-port inventory at connection level, including hosts using ports 14000, 12401 and 10212, and lists remote-access sessions that cross from outside the private address range. It does not decode CIMPLICITY, iFIX, Historian or SRTP messages or read software versions from traffic. Component and version identification comes from the asset records and software lists you share, with release and SIM level per node. SoftWSP matches the versions found against CVE, CISA KEV and FIRST EPSS data, and an engineer reviews the AI-written summary before it reaches you.

What are the common pitfalls?

  • Recording "CIMPLICITY 2023" or "iFIX 6.5" without the SIM level, when the fix is a SIM.
  • Forgetting that Historian can be installed on iFIX and CIMPLICITY nodes.
  • Leaving the CIMPLICITY built-in web server on when nobody uses WebView or ThinView.
  • Opening .CIM screens and project files from vendors or integrators without checking where they came from.
  • Searching for advisories under one name only, when CISA used GE Intelligent Platforms, GE Digital, GE Vernova and Emerson.
  • Trusting a CVE id over the advisory text, as the ICSA-25-240-06 mismatch shows.

This guide draws on CISA ICS advisories ICSA-11-243-01, ICSA-11-243-03A, ICSA-12-032-01, ICSA-12-032-02, ICSA-12-341-01, ICSA-13-022-02, ICSA-13-170-01, ICSA-14-023-01, ICSA-14-289-02, ICSA-16-194-02, ICSA-17-278-01A, ICSA-20-098-02, ICSA-21-040-01, ICSA-22-053-01, ICSA-22-053-02, ICSA-22-228-06, ICSA-22-326-04, ICSA-23-017-01, ICSA-23-073-03, ICSA-23-199-06, ICSA-23-243-02 and ICSA-25-240-06 and their CSAF records, which carry GE's and Emerson's recommendations; Velotic's company and product pages; NVD and CVE.org records; CISA KEV and FIRST EPSS, all checked as of 2026-11-28.

Put this guide to work

Frequently asked questions

Are any GE Proficy or CIMPLICITY vulnerabilities in the CISA KEV catalog?

No. As of 2026-11-28, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.27, 1,808 entries) has no entry for GE, GE Vernova, Velotic or Emerson, and none of the 32 CVE ids in this guide is listed. The highest FIRST EPSS score among them, dated 2026-11-27, belongs to CVE-2014-0750, the CIMPLICITY WebView gefebt.exe path traversal, at 0.698. Next come CVE-2013-0653 in CIMPLICITY WebView at 0.191 and CVE-2012-0231 in Plant Applications at 0.069; every CVE from 2016 onward is below 0.011.

Which ports do GE and CISA name for Proficy and CIMPLICITY?

Three, all in older CISA advisories. ICSA-12-032-01 names TCP port 14000 for the Proficy Historian Data Archiver (ihDataArchiver.exe), ICSA-12-032-02 names port 12401 for the Plant Applications Server License Manager (PRLicenseMgr.exe), and ICSA-13-170-01 names TCP port 10212 for CimWebServer.exe in CIMPLICITY WebView. ICSA-12-341-01 also covers the CIMPLICITY built-in web server that serves GlobalView, WebView and ThinView over HTTP. The newer advisories name no port numbers.

Which Proficy and CIMPLICITY flaws can be reached over the network without a login?

In CISA's advisories, the unauthenticated network flaws are the older ones: the Historian Data Archiver overflows CVE-2011-1918 and CVE-2012-0229 (TCP port 14000), the Plant Applications service overflows CVE-2011-1919 and CVE-2012-0231 (port 12401), and the CIMPLICITY web server flaws CVE-2013-0653, CVE-2013-0654, CVE-2013-2785 (TCP port 10212) and CVE-2014-0750. The newest one is in Proficy Historian 7.0 and later: CVE-2022-46732, an authentication bypass that CISA and NVD both score 9.8, fixed in Historian 2023 or by GE's SIMs. Most CIMPLICITY and iFIX CVEs since 2016 need local access or a malicious file.

What is a SIM in GE Proficy fixes?

CISA's 2011 and 2012 advisories expand SIM as Software Improvement Module, GE's product update for a given release, and say Proficy SIMs are cumulative, so every later SIM carries the earlier fixes. Fixes are named as release plus SIM, for example CIMPLICITY 8.2 SIM 27, Historian 4.0 SIM 12, Plant Applications 5.0 SIM 43 or CIMPLICITY 2024 SIM 4. A newer release line (iFIX 2023, Historian 2023, CIMPLICITY 11.0) can also be the fix.

Who publishes security advisories for Proficy products now?

As of 2026-11-28, proficy.com redirects to Velotic, which describes itself as a new independent industrial software company formed from Proficy, formerly part of GE Vernova, and ThingWorx and Kepware from PTC. CISA published Proficy and CIMPLICITY advisories under GE Intelligent Platforms, GE Digital and, in August 2025, GE Vernova, and the 2022 Machine Edition advisory under Emerson. GE's support links in those advisories now resolve to a sign-in portal at softwaresupport.gevernova.com.

Why does CVE-2025-7719 not match the CIMPLICITY advisory?

CISA's ICSA-25-240-06 lists CVE-2025-7719 for an uncontrolled search path flaw in CIMPLICITY 2024, 2023, 2022 and 11.0, fixed in CIMPLICITY 2024 SIM 4. As of 2026-11-28, the CVE.org record for CVE-2025-7719, filed by GE Vernova, describes a path traversal in GE Vernova Smallworld 5.3.5 and earlier instead. Track the CIMPLICITY flaw by the advisory id and fixed version, not by the CVE id, until the two sources agree.

Sources

  1. Velotic: Introducing Velotic (Proficy from GE Vernova, ThingWorx and Kepware from PTC)
  2. Velotic: Proficy product family
  3. CISA CSAF: ICSA-11-243-01 GE Intelligent Platforms Proficy Plant Applications
  4. CISA CSAF: ICSA-11-243-03A GE Intelligent Platforms Proficy Historian Data Archiver
  5. CISA CSAF: ICSA-12-032-01 GE Proficy Historian ihDataArchiver
  6. CISA CSAF: ICSA-12-032-02 GE Intelligent Platforms Proficy Plant Applications
  7. CISA CSAF: ICSA-12-341-01 GE Proficy HMI/SCADA CIMPLICITY Integer Overflow
  8. CISA CSAF: ICSA-13-022-02 GE Intelligent Platforms Proficy CIMPLICITY
  9. CISA CSAF: ICSA-13-170-01 GE Proficy HMI/SCADA CIMPLICITY WebView
  10. CISA CSAF: ICSA-14-023-01 GE Proficy Vulnerabilities
  11. CISA CSAF: ICSA-14-289-02 GE Proficy HMI/SCADA CIMPLICITY CimView Memory Access Violation
  12. CISA CSAF: ICSA-16-194-02 GE Proficy HMI/SCADA CIMPLICITY Privilege Management
  13. CISA CSAF: ICSA-17-278-01A GE CIMPLICITY (Update A)
  14. CISA CSAF: ICSA-20-098-02 GE Digital CIMPLICITY
  15. CISA CSAF: ICSA-21-040-01 GE Digital HMI/SCADA iFIX
  16. CISA CSAF: ICSA-22-053-01 GE Proficy CIMPLICITY (privilege management)
  17. CISA CSAF: ICSA-22-053-02 GE Proficy CIMPLICITY (cleartext transmission)
  18. CISA CSAF: ICSA-22-228-06 Emerson Proficy Machine Edition
  19. CISA CSAF: ICSA-22-326-04 GE CIMPLICITY
  20. CISA CSAF: ICSA-23-017-01 GE Digital Proficy Historian
  21. CISA CSAF: ICSA-23-073-03 GE iFIX
  22. CISA CSAF: ICSA-23-199-06 GE Digital CIMPLICITY
  23. CISA CSAF: ICSA-23-243-02 GE Digital CIMPLICITY
  24. CISA CSAF: ICSA-25-240-06 GE Vernova CIMPLICITY
  25. NVD: CVE-2014-0750 (CIMPLICITY WebView gefebt.exe path traversal)
  26. NVD: CVE-2022-46732 (Proficy Historian authentication bypass)
  27. NVD: CVE-2023-0598 (Proficy iFIX code injection)
  28. CVE.org API record: CVE-2025-7719 (GE Vernova Smallworld)
  29. CISA Known Exploited Vulnerabilities catalog
  30. FIRST: Exploit Prediction Scoring System (EPSS)
Was this guide helpful?

In this cluster

GE Proficy and CIMPLICITY vulnerabilities: Historian, iFIX, Plant Applications, Machine Edition and CIMPLICITY HMI/SCADA, fixed versions and hardening