Security Advisory

CVE-2023-0598: GE Proficy iFIX HMI Code Injection

Last updated:
  • CVE-2023-0598

CVE-2023-0598 is a code injection flaw in GE Digital Proficy iFIX, HMI and SCADA software. In iFIX 2022, 6.1 and 6.5 an attacker may plant malicious configuration files in the web server execution path and gain full control of the HMI software. NVD scores it 9.8 and CISA 7.8; iFIX 2023 or GE security patches fix it.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

0.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-0598 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
GE Digital Proficy iFIXcpe:2.3:a:ge:ifix:2022:*:*:*:*:*:*:*iFIX 2022, v6.1 and v6.5 (CISA ICSA-23-073-03, NVD CPE); fix: upgrade to iFIX 2023 or apply the GE SIM for 2022, 6.1 or 6.5

What does this mean for affected devices?

The CVE record from CISA says: "GE Digital Proficy iFIX 2022, GE Digital Proficy iFIX v6.1, and GE Digital Proficy iFIX v6.5 are vulnerable to code injection, which may allow an attacker to insert malicious configuration files in the expected web server execution path and gain full control of the HMI software." NVD's Primary analysis scores it 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and maps it to CWE-94, improper control of generation of code. CISA, the CNA, scored it 7.8 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), a local attack by a low-privileged user, and its advisory states that the vulnerability is not exploitable remotely. NVD's configuration covers iFIX 6.1, 6.5 and 2022 (NVD, CVE record).

Which iFIX versions are affected?

CISA's ICSA-23-073-03, released on 2023-03-14, lists Proficy iFIX 2022, v6.1 and v6.5. CISA names multiple critical infrastructure sectors and worldwide deployment, with GE headquartered in the United States. Michael Heinzl reported the flaw. CISA's summary is that exploitation could allow privilege escalation and full control of the system; it reports no known public exploits.

How do you fix CVE-2023-0598?

GE Digital's remedy in the CISA advisory is to upgrade to Proficy iFIX 2023. Sites that cannot upgrade can apply the GE security patch (SIM) for their release, published as separate support articles for iFIX 2022, 6.1 and 6.5 behind a GE support login. GE also points users to the iFIX Secure Deployment Guide for setting up access control lists; the GE Digital support link for that guide now redirects to GE Vernova's software support site. Practical steps:

  • upgrade iFIX nodes to 2023, or install the SIM that matches each node's release;
  • restrict who can log on to iFIX servers and who can write to the iFIX installation and web server folders, since the attack plants files there;
  • keep HMI and SCADA servers behind firewalls, isolated from business networks, with VPN-only remote access.

An older iFIX-related page on this site is CVE-2013-2823 in the Catapult DNP3 driver GE ships for iFIX. The command injection fix guide covers the code injection class, and the small manufacturers OT/ICS guide the network controls.

Is CVE-2023-0598 exploited?

CVE-2023-0598 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.00842, the 55.29th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Command injection. Our practical guide covers how to detect, fix, verify and disclose it: How to fix command injection in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2023-03-16; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; ICS-CERT Secondary 7.8 CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; CWE-94; CPE ge ifix 6.1, 6.5, 2022. — NVD
  • CISA ICSA-23-073-03 (page release date 2023-03-14, read 2026-11-27): iFIX 2022, v6.1, v6.5; CWE-94, CVSS 7.8; vendor fix: upgrade to iFIX 2023 or apply SIMs for 2022, 6.1, 6.5 (login required); Secure Deployment Guide for ACLs; sectors Multiple; worldwide; HQ United States; reported by Michael Heinzl; not exploitable remotely; no known public exploits. — CISA ICSA-23-073-03
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2023-03-16, CNA CVSS v3.1 7.8; affected Proficy iFIX 2022, v6.1, v6.5. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.00842, percentile 0.55292, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-23-073-03: GE iFIX (CSAF)
  3. CISA ICSA-23-073-03 advisory page
  4. CVE.org record CVE-2023-0598
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which iFIX release fixes CVE-2023-0598?

Proficy iFIX 2023. For iFIX 2022, 6.1 and 6.5, GE also published a security patch (SIM) per release, according to CISA ICSA-23-073-03.

Can CVE-2023-0598 be exploited over the network?

CISA, the CNA, scores it as a local attack (AV:L) by a low-privileged user and says it is not exploitable remotely. NVD's Primary score of 9.8 treats it as network-reachable. Plan patching on the 9.8, and restrict local access either way.

What does an attacker gain?

Full control of the iFIX HMI software, according to the CVE description, by placing malicious configuration files in the expected web server execution path.

Is CVE-2023-0598 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.00842 (55.29th percentile) in the 2026-11-26 dataset.