Security Advisory

CVE-2012-0229: GE Proficy Historian Data Archiver Flaw

Last updated:
  • CVE-2012-0229

CVE-2012-0229 is a memory corruption flaw in the Data Archiver service of GE Proficy Historian 4.5 and earlier, the process historian used with GE iFIX and CIMPLICITY: crafted traffic on TCP port 14000 can crash the service or possibly run code. NVD scores it 10.0 (CVSS v2). GE released free Software Improvement Module updates for Historian 3.1, 3.5, 4.0 and 4.5.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

4.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2012-0229 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
GE Intelligent Platforms Proficy Historiancpe:2.3:a:ge:intelligent_platforms_proficy_historian:*:*:*:*:*:*:*:*CISA ICSA-12-032-01: 4.5 and prior; GE SIM product updates for 3.1, 3.5, 4.0 and 4.5; older than 3.1 upgrade first
GE Proficy HMI/SCADA iFIX and CIMPLICITY with Proficy Historian 4.5 or prior installed—CISA ICSA-12-032-01: iFIX 5.0, 5.1, 5.5 and CIMPLICITY 8.2 with Historian 4.5 or prior; apply the Historian SIM or uninstall Historian if unused

What does this mean for affected devices?

NVD's description reads: "The Data Archiver service in GE Intelligent Platforms Proficy Historian 4.5 and earlier allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted session on TCP port 14000 to (1) ihDataArchiver.exe or (2) ihDataArchiver_x64.exe." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-119; there is no NVD v3 score. CERT/CC assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-03-15 (NVD, CVE record).

What does CISA say?

CISA's advisory ICSA-12-032-01 (CSAF), "GE Proficy Historian ihDataArchiver", first released on March 2, 2012, says "a memory corruption vulnerability exists because of the way the Historian Data Archiver service processes incoming traffic on Port 14000/TCP". It credits Luigi Auriemma, who reported it through the Zero Day Initiative. Besides stand-alone Proficy Historian 4.5 and earlier, CISA lists Proficy HMI/SCADA iFIX 5.0, 5.1 and 5.5 and CIMPLICITY 8.2 when Historian 4.5 or earlier is installed alongside them. The CSAF file scores it CVSS v2 10.0 with CWE-119. GE's own security advisory and the updates sit behind its customer login.

How do I fix it?

GE released free Software Improvement Modules (SIMs) and recommends applying the product updates to Proficy Historian 3.1, 3.5, 4.0 and 4.5. Sites on a version older than 3.1 should upgrade to 3.1 or later first and then apply the update. iFIX and CIMPLICITY users with Historian installed should apply the same updates, or uninstall Historian if they do not use it. GE notes that SIMs are cumulative, so any later SIM also contains the fix. Restrict TCP port 14000 at the firewall so only the HMI/SCADA nodes that collect data can reach the archiver.

CVE-2012-3010 is a buffer overflow in GE Proficy Real-Time Information Portal from the same year, and CVE-2013-2811 covers a GE DNP3 driver. The memory corruption guide explains this bug class, and the OT/ICS security guide for small manufacturers covers historian placement.

CVE-2012-0229 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0474, a percentile of 92.6, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2012-03-15; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-119; CPE intelligent_platforms_proficy_historian up to and including 4.5 (plus 1.0-4.0 entries). — NVD
  • CISA ICSA-12-032-01 CSAF (read 2026-11-27): CVE-2012-0229, CWE-119, CVSS v2 10.0; Proficy Historian <= 4.5, CIMPLICITY 8.2 and iFIX 5.0/5.1/5.5 with Historian; free SIM updates for 3.1, 3.5, 4.0, 4.5; older than 3.1 upgrade first; SIMs cumulative; uninstall Historian if not in use; GE advisory needs a GE user ID. — CISA ICSA-12-032-01
  • CISA ICSA-12-032-01 web page (read 2026-11-27): originally released March 2, 2012; Data Archiver memory corruption on Port 14000/TCP; researcher Luigi Auriemma via Zero Day Initiative. — CISA ICSA-12-032-01
  • CVE record (read 2026-11-27): state PUBLISHED, assigner certcc; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.04744, percentile 0.92641, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-12-032-01: GE Proficy Historian ihDataArchiver
  3. CISA ICSA-12-032-01 CSAF (machine-readable advisory)
  4. CVE record CVE-2012-0229 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Proficy Historian versions need the update?

All versions up to 4.5. GE provides SIM updates for 3.1, 3.5, 4.0 and 4.5; sites on older versions must upgrade to 3.1 or later first and then apply the update.

Are iFIX and CIMPLICITY affected?

Only when Proficy Historian 4.5 or earlier is installed with them. CISA lists iFIX 5.0, 5.1 and 5.5 and CIMPLICITY 8.2 in that case; apply the Historian update or uninstall Historian if it is not used.

What network control reduces the risk?

The flaw is reached through the Data Archiver on TCP port 14000. Allow that port only from the SCADA nodes that write to the historian, and keep the historian off business networks and the internet.

Is CVE-2012-0229 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0474 (percentile 92.6) in the 2026-11-26 dataset.