ABB's AC500 PLCs and the Automation Builder engineering suite, the System 800xA distributed control system with AC 800M controllers, the RTU500 remote terminal units and the Relion protection relays configured with PCM600 have published flaws in five main families: crafted packets that stop or reboot a controller, RTU or relay; memory-safety bugs in protocol stacks such as IEC 60870-5-104, MMS and OPC UA; weak file, service and project permissions on Windows engineering and licensing hosts; cleartext or unprotected credentials; and path traversal. Fixes are firmware or release updates per branch, for example AC500 V3 firmware 3.8.0. None of these CVEs is in CISA's KEV catalog as of 2026-11-23.
Key takeaways
- The products below appear in ABB's alerts and notifications list, in Hitachi Energy advisories that CISA republishes, and in the CVE records.
- The management and data paths the advisories name are also the attack paths.
- ABB's AC500 V2 advisory 3ADR011162 passes on CODESYS Control V2 CVEs, and the AC500 V3 advisory names CODESYS runtime components; the CODESYS runtime guide covers that shared code.
- ABB's 800xA-specific CLS advisory 2PAA121230 (Rev E, 16 August 2022) maps CLS builds to 800xA releases and shows System 800xA 6.1.1 with CLS 6.1.1-0 unaffected by all five CLS CVEs.
Where do ABB AC500, 800xA, RTU500 and Relion sit in OT networks?
The products below appear in ABB's alerts and notifications list, in Hitachi Energy advisories that CISA republishes, and in the CVE records. They cover two different worlds: factory and process automation (AC500, 800xA) and power-grid substations and distribution (RTU500, Relion, PCM600).
| Group | Products named in advisories and CVE records | Typical place in the network |
|---|---|---|
| PLCs and engineering | AC500 V2 (PM5xx, for example PM554, PM564, PM573-ETH, PM583-ETH) and AC500 V3 (PM5xxx); Automation Builder, which also builds SM560-S safety projects | Control level in machines and process skids; the engineering PC sits one level up |
| Distributed control | System 800xA with AC 800M and AC 800M High Integrity controllers, 800xA Base, OPC Server for AC 800M, Control Builder Safe, Compact HMI, the Central Licensing System (CLS) | Supervisory servers and clients above the controllers on a client/server network and a control network |
| Remote terminal units | RTU500 series communication modules (CMU) running CMU firmware 12.x and 13.x; end-of-life 11.x and earlier | Substations and remote sites, reporting to control centers over IEC 60870-5-104 and talking to relays over IEC 61850 |
| Protection relays and their tool | Relion 670, 650 and SAM600-IO (Hitachi Energy); Relion 611, 615, 620, 630 and REX640 (ABB); PCM600 and its IED Connectivity Packages | Bay level in substations; PCM600 runs on a Windows engineering workstation |
The CVE records show which company is the CVE Numbering Authority. ABB assigns CVEs for AC500, Automation Builder, 800xA, the Relion 611, 615, 620 and REX640 relays and PCM600 itself. Hitachi Energy assigns them for RTU500, Relion 670, 650 and SAM600-IO and the PCM600 Connectivity Packages, and CISA titles its RTU500 advisories from 2021 on as Hitachi Energy. CVE-2021-27196 still names "Hitachi ABB Power Grids", and CISA's 2019 Relion 670 advisories say ABB. So a substation inventory needs both vendors' advisory lists. The Purdue model guide explains how to zone these levels.
How are AC500, 800xA, RTU500 and Relion devices managed?
The management and data paths the advisories name are also the attack paths. Ports appear in the table only where ABB or CISA give them.
| Path | Products | What the sources say |
|---|---|---|
| Automation Builder engineering protocol | AC500 V2 | ABB: "ABB Tcp/Ip Level 2 AC" on port 1200 is affected by CVE-2022-3192; the "Tcp/Ip" protocol on port 1201 is not |
| Web server and WebVisu | AC500 V2 and V3 | CVE-2020-24686 stops the V2 web visualization; CISA's ICSA-12-320-01 gives TCP port 8080 for the old CoDeSys web server flaw CVE-2011-5007 |
| Modbus TCP server | AC500 V2 | Unsupported function codes return fragments of earlier responses (CVE-2025-7745) |
| OPC UA server and client | AC500 V3 | A crafted request can crash the runtime (CVE-2024-5000) |
| MMS | AC 800M controllers; Relion 670 | ABB: MMS carries messages between controllers and between the engineering station and controllers; CISA: IEC 61850 MMS uses TCP port 102 on Relion 670 |
| SPA over TCP/IP | Relion 650 and 670 | CISA advises blocking TCP port 7001 from outside the network (CVE-2019-18247) |
| CSLib | 800xA Base clients and services | ABB calls it a TCP/IP-based protocol; no port given |
| IEC 60870-5-104 (BCI, HCI, SCI) | RTU500 CMU | Five of the RTU500 CVEs below are in these functions |
| Web interface and firmware update | RTU500 CMU | XSS, WebSocket and end-of-life update-endpoint flaws |
| VxWorks WDB debug agent | End-of-life RTU500 CMU firmware | CISA's ICSA-26-279-06 gives UDP port 17185 for CVE-2010-2965 |
| Windows engineering hosts | Automation Builder, PCM600, 800xA CLS and OPC Server | File, service, COM and project permissions; update certificate checks |
ABB names no port for the AC 800M MMS stack and neither ABB nor CISA gives one for IEC 60870-5-104 in these advisories, so confirm ports from the product manuals or a capture. The BOD 23-02 guide on internet-exposed management interfaces explains how to check exposure from outside instead of trusting the firewall configuration.
Which AC500 and Automation Builder vulnerabilities matter?
ABB's AC500 V2 advisory 3ADR011162 passes on CODESYS Control V2 CVEs, and the AC500 V3 advisory names CODESYS runtime components; the CODESYS runtime guide covers that shared code. The ABB advisories:
| CVE | Flaw, per ABB | Affected and fixed | Scores |
|---|---|---|---|
| CVE-2020-24685 | One unauthenticated crafted packet stops the PLC (ERR LED flashing red); physical access is needed to restart the application | All AC500 V2 with onboard Ethernet; ABB 3ADR010667 Rev C (27 January 2021) released firmware 2.8.5 first for PM573-ETH and PM583-ETH; NVD lists firmware before 2.8.5 | ABB and NVD 8.6 |
| CVE-2020-24686 | Long URLs or ping floods stop the web visualization; logins then fail and the PLC refuses Automation Builder connections, while the PLC application keeps running | PM554, PM556, PM564, PM566, PM572, PM573; ABB 3ADR010645 (2 February 2021) had no fix and says to disable web visualization where the PLC might be reached from untrusted networks | ABB and NVD 7.5 |
| CVE-2022-3192 | Denial of service on port 1200 | Firmware 2.0.0 to before 2.8.6; fixed in 2.8.6 | ABB and NVD 5.3 |
| CVE-2022-31805 | CODESYS V2 passwords cross the network unprotected | Same advisory; not fixed by 2.8.6, so ABB says to separate the PLC network from general-purpose networks | ABB 9.8; NVD 4.3 (CVSS v2) and 7.5 (CVSS v3.1) |
| CVE-2025-7745 | Unsupported Modbus function codes return fragments of earlier responses | AC500 V2 2.5.2 and earlier; fixed in 2.5.3, which ABB 3ADR011432 (23 July 2025) says was released in 2016 | ABB 5.8 (v3.1), 6.9 (v4.0); no NVD score |
ABB's 3ADR011162 of 28 March 2023 lists twelve CVEs for all AC500 V2 firmware before 2.8.6. Ten of them need a successful login, so ABB says a configured password for password level 1 protects against them even where the update cannot be applied. For CVE-2022-3192 there is no workaround except switching the engineering connection from "ABB Tcp/Ip Level 2 AC" on port 1200 to "Tcp/Ip" on port 1201.
For AC500 V3, ABB's 3ADR011377 of 7 January 2025 covers all PM5xxx firmware before 3.8.0. It includes CVE-2024-5000, a buffer size miscalculation in the CmpOPCUAStack component that a malicious OPC UA client (or a malicious server the PLC connects to) can use to crash the runtime: ABB scores it 8.8, the CERT@VDE CVE record 7.5, and NVD has no score of its own. CVE-2024-12429 is a directory traversal through a crafted memory card (ABB 4.3), and CVE-2024-12430 lets an authenticated attacker who has used it run commands as root (ABB 7.0). Both need physical access. The fix is firmware 3.8.0 from Automation Builder 2.8.0; the workaround is activated user management with strong passwords, preferably online user management. The OPC UA security guide covers hardening the OPC UA side.
Automation Builder itself has two flaws in ABB's 3ADR011407 (Rev B, 25 July 2025), republished by CISA as ICSA-25-133-04:
- CVE-2025-3394: user management information stored in the project file can be overruled by crafted file contents (ABB and NVD 7.8).
- CVE-2025-3395: application files of AC500 V2 and SM560-S devices inside a project can be modified to overrule user management (ABB 7.1, NVD 5.5).
ABB says all Automation Builder versions are affected and that the project setting "Security" closes the gap: "Integrity check" for CVE-2025-3394 and "Encryption" for CVE-2025-3395. From version 2.8.1 the default is "Integrity check". CISA's CSAF lists 2.8.0 and earlier as affected and 2.8.1 and later as fixed. ABB's alerts list also shows two newer advisories dated 28 September 2026, 3ADR011565 (AC500 V3 invalid type usage in visualization, 7.5) and 3ADR011566 (Automation Builder deserialization of untrusted data, 7.8), so check that list for anything after this guide.
What did the System 800xA advisories cover?
Four advisories cover 800xA servers, licensing and controllers:
| CVE | Component and flaw | Affected and fixed | Scores |
|---|---|---|---|
| CVE-2020-8481 | Central Licensing System: confidential data in an unprotected file; full control of the computer | CLS 5.1.0/0 (5.1.0.14) and 5.1.0/1 (5.1.0.35); for 800xA, only the CLS of the first 5.1 release | ABB, CISA and NVD 9.8 |
| CVE-2020-8479 | CLS XML external entity injection: read or call files from the license server or network, block license handling | CLS 5.1 to 6.1 before 6.1.00100.417 | ABB PDF 9.3; CISA and CVE record 9.4; NVD 9.8 |
| CVE-2020-8471 | CLS weak file permissions: block licensing, escalate privileges, run code | CLS 5.1.0/0 to 5.1.0-5 | ABB, CISA and NVD 7.8 |
| CVE-2021-22277 | AC 800M MMS stack input validation: MMS unreachable for up to 30 seconds, then the controller stops | AC 800M firmware 5.1, 6.0.0-0 to 6.0.0-3 and 6.1.0-0 to 6.1.1-1, including SoftController and Control Builder Safe; NVD lists 6.0.0-4 and 6.1.1-2 as the first unaffected levels | ABB and NVD 7.5 |
| CVE-2021-22284 | OPC Server for AC 800M COM access control: a low-privileged user runs code on the OPC Server node | 5.1.0-x, 5.1.1-x, 6.0.0-1 to 6.0.0-3; fixed in 6.1.0-0 and later and 6.0.0-4 | ABB and CISA 8.4; NVD 8.8 |
| CVE-2024-3036 | 800xA Base CSLib: crafted messages crash and restart services on PC-based client and server nodes; controllers are not affected | 800xA Base 6.0.3-9 and earlier and 6.1.1-2 and earlier; fixed in 6.0.3-10 (RollUp, September 2025, needs System 800xA 6.0.3.4), 6.1.1-3 (System 800xA 6.1.1.2) and 6.2.0-0 | ABB 5.7 (v3.1), 6.9 (v4.0); no NVD score |
ABB's 800xA-specific CLS advisory 2PAA121230 (Rev E, 16 August 2022) maps CLS builds to 800xA releases and shows System 800xA 6.1.1 with CLS 6.1.1-0 unaffected by all five CLS CVEs. It also warns that CVE-2020-8481, -8479 and -8471 may, under certain conditions, affect the integrity of safety functions, which is prevented by turning the AC 800M High Integrity Access Enable key off and setting safety variables to "Read Only" or "Confirm and Access Enable". CISA's ICSA-20-154-04 adds IPsec and firewalls between the client/server network and other networks, and blocking interactive login to service accounts.
For CVE-2021-22277, ABB found no workaround and treats the control network as a trusted zone. For CVE-2021-22284, ABB recommends COM and DCOM hardening: turn off DCOM and allow only valid local users to reach the OPC Server COM objects. For CVE-2024-3036, the workaround is IPsec as described in the 800xA user documentation. Where 800xA runs safety applications, the IEC 61511 guide covers how safety systems should be separated.
Which RTU500 vulnerabilities affect IEC 60870-5-104 and the web server?
Most RTU500 CVEs reboot or block the communication module (CMU) through a crafted IEC 60870-5-104 message. The IEC 60870-5-104 protocol guide explains the APDU, U-format frames and the IEC 62351 security extensions these CVEs refer to.
| CVE | Function and flaw | Affected CMU firmware | Fixed CMU firmware | Scores |
|---|---|---|---|---|
| CVE-2021-35533 | BCI IEC 104 APDU parser; crafted message reboots the CMU | 12.0, 12.2, 12.4 (all) | 12.6.5.0 or later, for example 12.7.x or 13.2.x | Hitachi Energy, CISA and NVD 7.5 |
| CVE-2022-2502 | HCI IEC 104 with IEC 62351-5 and the separately ordered "Advanced security" licence; buffer overflow, reboot | 13.3.1 to 13.3.2 | 13.3.3 or 13.4.1 | 7.5 |
| CVE-2022-4608 | HCI IEC 104 with IEC 62351-3; stack overflow when session parameters are renewed | 13.3.1 to 13.3.2 | 13.3.3 or 13.4.1 | 7.5 |
| CVE-2023-6711 | SCI and HCI IEC 104 buffer overflow, CMU reboot | 12.0.1 to 13.5.1 in eight branches | 12.0.15, 12.2.12, 12.4.12, 12.6.10, 12.7.7, 13.2.7, 13.4.4, 13.5.2 | Hitachi Energy and CISA 5.9; NVD 7.5 |
| CVE-2026-1773 | Bidirectional IEC 104: invalid U-format frame, denial of service | 12.7.1 to 12.7.7, 13.5.1 to 13.5.4, 13.6.1 to 13.6.2, 13.7.1 to 13.7.7, 13.8.1 | 12.7.8, 13.7.8, 13.8.2 | Hitachi Energy 8.7 (v4.0); CISA and NVD 7.5 |
Three conditions limit exposure: BCI IEC 104 is disabled by default (ICSA-21-336-04), HCI IEC 104 and its IEC 62351 support are disabled by default (ICSA-23-220-02), and CVE-2026-1773 applies only when bidirectional IEC 104 is configured. For CVE-2026-1773 Hitachi Energy says IEC 62351-3 secure communication mitigates but does not remediate the flaw. Disable any 104 function that is not used, then update.
Two more RTU500 advisories reach beyond the protocol stacks:
- OpenSSL in the CMU. CISA's ICSA-23-143-02 (Update B, 19 October 2023) lists CMU firmware from the 12.0 to 13.4 branches as affected by CVE-2023-0286, an OpenSSL X.400 type confusion (CISA and NVD 7.4), with per-branch updates such as 12.6.9, 12.7.6, 13.2.6 and 13.4.2.
- End-of-life firmware. CISA's ICSA-26-279-06, republishing Hitachi Energy's 8DBD000251 of 29 September 2026, covers findings reported by Dragos in CMU firmware 11.x and earlier. CVE-2026-8065 lets an unauthenticated attacker upload arbitrary firmware through a crafted POST request to the update endpoint (Hitachi Energy and CISA 9.1; NVD Awaiting Analysis, no score); the CVE record gives the affected range as 9.0 up to 12.0. The same advisory lists the VxWorks WDB debug service CVE-2010-2965 on UDP port 17185 (CISA 9.8; NVD 10.0 in CVSS v2) and four other CVEs. The only remedy is to upgrade to 12.7.8, 13.9.1 or later.
The web interface has its own flaws. CVE-2023-5767 is cross-site scripting through an improperly sanitized RDT language file in CMU firmware 12.0.1 to 13.4.3 (Hitachi Energy 6.0, NVD 6.1), fixed in the same branch versions as CVE-2023-6711. It shares an advisory with two sibling IDs, and CISA's CSAF for it (ICSA-25-128-02) swaps the descriptions of those two compared with the CVE records, so match on the CVE record text. Most of the IEC 104 flaws above are buffer and stack overflows in message parsers; the memory corruption guide explains why such bugs recur in embedded protocol stacks.
Which Relion relay and PCM600 flaws are published?
Relion relays are the protection layer, so a reboot means protection is unavailable while the relay restarts, as ABB's Relion 630 advisory says. The IEC 61850 protocol guide covers the MMS and GOOSE traffic many of these flaws ride on.
| CVE | Product and flaw | Affected and fixed | Scores |
|---|---|---|---|
| CVE-2019-18253 | Relion 670: crafted paths read or delete files outside the intended directory | 1p1r26, 1.2.3.17, 2.0.0.10 (RES670 2.0.0.4), 2.1.0.1 and earlier; fixed in 1p1r27, 1.2.3.18, 2.0.0.11 (RES670 2.0.0.5), 2.1.0.2 | CISA and NVD 10.0 |
| CVE-2019-18247 | Relion 650 and 670: crafted message forces a reboot | 650 1.3.0.5 and earlier, fixed in 1.3.0.6; 670 1.2.3.18, 2.0.0.11, 2.1.0.1 and earlier, fixed in 1.2.3.19, 2.0.0.12, 2.1.0.2 | CISA 5.3; NVD 7.5 |
| CVE-2018-20720 | Relion 630: reboot command in an SPA message | 1.1 before 1.1.0.C0, 1.2 before 1.2.0.B3, 1.3 before 1.3.0.A6 | ABB 5.3; NVD 7.5 (CVSS v3.0) |
| CVE-2021-27196 | IEC 61850 sequence reboots the device for about 60 seconds | Relion 670, 650 and SAM600-IO branches (for example 2.2.1 before 2.2.1.6), REB500 7.3 to 8.3, RTU500 7.x to 12.x, FOX615, MSM, GMS600, PWC600 | NVD 7.5 |
| CVE-2021-35535 | Relion 670, 650, SAM600-IO: older VxWorks loaded briefly during boot, reachable from the front network port | Fixed in 2.2.1.7, 2.2.2.5, 2.2.3.4, 2.2.4.3; 2.2.0 all revisions affected | Hitachi Energy and NVD 8.1 |
| CVE-2022-3864 | Relion 670, 650, SAM600-IO: tampered update package restarts the IED; needs security privileges | Fixed in 2.2.1.9, 2.2.2.6, 2.2.3.7, 2.2.4.4, 2.2.5.6; 2.2.0 all revisions affected | Hitachi Energy and NVD 4.5 |
| CVE-2021-22283 | Relion 611, 615, 620, REX640, RER615, REC615, SMU615: MMS clients opening files without closing them cause internal fault code 7 | Fixed per series (for example 615 IEC 5.0 FP1 5.1.20, 620 IEC/CN 2.0 FP1 2.1.15, REX640 PCL3 1.2.1); many older series have no fix | ABB 6.2; NVD 5.5 |
CISA's text for the two 2019 advisories is specific about ports. For CVE-2019-18253, the only known workaround is to disable IEC 61850 when it is not used, and otherwise to limit MMS on TCP port 102 to the relevant upper networks. For CVE-2019-18247, firewall rules can block incoming traffic to TCP port 7001 from outside the network, and on Relion 650 version 1.3 SPA over TCP/IP can be disabled if unused. The descriptions of CVE-2021-35535 differ: the CVE record calls the result a denial of service, while CISA's ICSA-21-336-05 says the older VxWorks is susceptible to URGENT/11 and allows remote code execution before the operating system loads. ABB's 2NGA001147 distinguishes two fixes for CVE-2021-22283: "Fix 1" limits concurrent MMS file handles and "Fix 2" changes MMS server initialization and solves the problem completely.
PCM600, the Windows engineering tool for Relion relays, has its own advisories:
- CVE-2021-22278, Update Manager certificate check. PCM600 2.7 to 2.10; an administrator-level attacker could install untrusted packages signed with crafted certificates. Fixed in Update Manager 2.4.21218.1; otherwise ABB says to check that the update server is https://toolupdate.fi.abb.com. ABB and NVD 6.7; ABB says it cannot be exploited remotely.
- CVE-2022-2513, IED credentials in cleartext. IED Connectivity Packages store relay credentials in cleartext in the PCM600 database, logs and exported backups. CISA's ICSA-22-333-02 (Update A, 23 July 2024) lists PCM600 2.11 and earlier and fixes it in PCM600 v2.11 Hotfix 20240426, after which backups must be re-imported and re-exported. Hitachi Energy 7.1; NVD 5.5.
- CVE-2026-15952, Scheduler Service permissions. ABB's 2NGA003170 of 28 September 2026 says the ABBPCMSchedulerService runs as LocalSystem while local PCM600 users can change its configuration, so a local authenticated user can run commands as SYSTEM in PCM600 2.14 and older. No fixed version is named; the workaround is to run the service under the same Windows account used for PCM600. ABB 6.4 (v3.1), 7.1 (v4.0); NVD Deferred with no score as of 2026-11-23. CISA's ICSA-26-274-03 republishes it with a second PCM600 CVE for path traversal in project archives.
A stolen PCM600 backup gives relay passwords to anyone who reads it, so the hard-coded credentials guide on credential storage applies to engineering files as much as to firmware.
Are ABB AC500, 800xA, RTU500 or Relion vulnerabilities exploited in the wild?
None of the CVEs in this guide is in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries, with no ABB or Hitachi Energy vendor entry). ABB's AC500, Relion 630 and PCM600 Update Manager advisories say ABB had received no reports of exploitation when they were issued, and CISA's ICSA-24-354-01 for CVE-2023-6711 says no known public exploitation specifically targeting it had been reported.
FIRST EPSS scores dated 2026-11-22, the latest as of 2026-11-23:
| CVE | Product | EPSS | Percentile |
|---|---|---|---|
| CVE-2011-5007 | CoDeSys web server on AC500 firmware before V2.1.4 | 0.72714 | 0.995 |
| CVE-2023-0286 | OpenSSL in RTU500 CMU firmware | 0.61757 | 0.992 |
| CVE-2010-2965 | VxWorks WDB on end-of-life RTU500 firmware | 0.57544 | 0.991 |
| CVE-2020-24686 | AC500 V2 web visualization | 0.02607 | 0.858 |
| CVE-2018-20720 | Relion 630 | 0.02470 | 0.849 |
| CVE-2020-8479 | 800xA Central Licensing System | 0.02259 | 0.834 |
| CVE-2019-18253 | Relion 670 | 0.01980 | 0.811 |
| CVE-2020-8481 | 800xA Central Licensing System | 0.01855 | 0.797 |
| CVE-2020-24685 | AC500 V2 | 0.01627 | 0.768 |
| CVE-2021-27196 | Relion, REB500, RTU500 | 0.01575 | 0.761 |
| CVE-2022-31805 | AC500 V2 (CODESYS V2) | 0.01062 | 0.655 |
| CVE-2021-35533 | RTU500 BCI IEC 104 | 0.00950 | 0.621 |
| CVE-2026-8065 | End-of-life RTU500 | 0.00494 | 0.433 |
| CVE-2026-1773 | RTU500 IEC 104 | 0.00446 | 0.396 |
| CVE-2026-15952 | PCM600 | 0.00094 | 0.006 |
The top three are third-party code (CoDeSys, OpenSSL, VxWorks), and two of them only matter on firmware that is a decade or more old. EPSS predicts exploitation activity; it does not say how easy a relay is to reach from inside a substation. Rank by reachability first, as the KEV and EPSS prioritization guide explains: an RTU500 on end-of-life firmware with its update endpoint reachable from the WAN matters more than any score.
How should ABB AC500, 800xA, RTU500 and Relion systems be hardened?
The steps below come from ABB's and Hitachi Energy's advisories and CISA's republications:
Update AC500 V2 to 2.8.6 and AC500 V3 to 3.8.0, through Automation Builder 2.6.0 and 2.8.0 respectively, and set a level 1 PLC password on V2 and online user management with strong passwords on V3. Move AC500 V2 engineering to "Tcp/Ip" on port 1201if port 1200 is reachable, and disable web visualization where the PLC can be reached from untrusted networks. Set Automation Builder project securityto "Integrity check" (the default from 2.8.1) or "Encryption" for projects with AC500 V2 or SM560-S application files. Bring 800xA to a release with fixed CLS and 800xA Base, for example System 800xA 6.1.1.2 (800xA Base 6.1.1-3) or 6.2.0.0, and AC 800M firmware at 6.0.0-4, 6.1.1-2 or later. Enable IPsec on the client/server network, harden DCOM for the OPC Server for AC 800M, and keep the AC 800M HI Access Enable key off outside maintenance. Update RTU500 CMU firmware per branchto at least 12.7.8, 13.7.8 or 13.8.2 for the 2026 IEC 104 flaw, and replace or upgrade any CMU on 11.x or earlier to 12.7.8 or 13.9.1. Disable unused BCI, HCI and SCI IEC 104 functions and IEC 62351 options, and follow Hitachi Energy's Remote Terminal Units Security Deployment Guideline. Update Relion firmware per seriesand disable unused IEC 61850 and SPA over TCP/IP. Limit MMS on TCP 102 to the station level and block TCP 7001 from outside the substation network. Protect PCM600 hosts and filesUpdate the Update Manager to 2.4.21218.1 or later, install PCM600 v2.11 Hotfix 20240426 or later and re-export backups, run the Scheduler Service under the PCM600 user account, and restrict access to PCMI, PCMP, PCMA and PCMT files. SegmentABB's recommendations repeat the same baseline: no direct internet connection, a firewall with a minimal number of open ports between control and other networks, no engineering software on general-purpose networks, VPNs for remote access, and scanning removable media.
How do you check which firmware and release an ABB system runs?
ABB and Hitachi Energy fix per branch, so record each device in detail:
AC500:record V2 or V3, the CPU type (for example PM573-ETH) and firmware; V2 below 2.8.6 and V3 below 3.8.0 are in scope of the advisories above. Automation Builder:record the version on every engineering PC and the project "Security" setting. 800xA:record the System 800xA release, the 800xA Base level (for example 6.1.1-3), the CLS build (for example 6.1.01000.502) and AC 800M controller firmware separately. RTU500:record the CMU firmware branch and build (for example 13.7.7), which 104 functions (BCI, HCI, SCI) are configured, and whether IEC 62351-3 or -5 is enabled. Relion and PCM600:record series and full revision (for example 670 2.2.4.2), the PCM600 version and hotfix, the Update Manager version and the Connectivity Package versions. Do not rely on CPE matching aloneAs of 2026-11-23 NVD has no score of its own for CVE-2024-3036, CVE-2024-5000, CVE-2024-12429, CVE-2025-7745, CVE-2026-8065 and CVE-2026-15952, and its CPE for CVE-2021-35533 lists only three branch numbers. Read the advisory, as the IEC 62443-2-3 patch management guide describes.
How do you monitor ABB PLC, RTU and relay networks?
Start with a baseline of which hosts talk to each PLC, RTU, relay and 800xA server, on which ports, and alert on changes:
- New hosts connecting to AC500 V2 on ports 1200 or 1201, or to any PLC web server, since most AC500 flaws need a network message from someone.
- MMS on TCP 102 to Relion relays from anything other than the station computer and gateway, which fits CVE-2019-18253 and CVE-2021-27196.
- Traffic to TCP 7001 on Relion 650 and 670 from outside the substation network (CVE-2019-18247).
- Any UDP 17185 traffic to an RTU500, which fits the VxWorks debug service on end-of-life firmware.
- Unexpected IEC 104 peers for RTU500 CMUs and large or unscheduled transfers to RTU and relay web interfaces, which fit the firmware update and file upload flaws.
Flow records show who connected to which port and when, not which MMS or IEC 104 function was invoked. Map alerts to MITRE ATT&CK for ICS techniques such as denial of service, firmware modification and remote services. For the Modbus side of AC500, the Modbus protocol guide covers function code monitoring.
Worked example: what does a review of a distribution utility find?
Synthetic example, not a real site. A utility runs a water treatment plant on AC500 PLCs and a substation with Relion relays and an RTU500 reporting to the control center.
| Observation | Why it matters | Action |
|---|---|---|
| AC500 V2 PM573-ETH on firmware 2.8.4, Automation Builder on port 1200 | CVE-2020-24685 stops the PLC; CVE-2022-3192 on port 1200 | Update to 2.8.6; switch to "Tcp/Ip" on port 1201; set a level 1 password |
| Automation Builder 2.7 projects without project security set | CVE-2025-3394 and CVE-2025-3395 | Set "Integrity check" or "Encryption"; move to 2.8.1 or later |
| RTU500 CMU on 13.7.5 with bidirectional IEC 104 | CVE-2026-1773 | Update to 13.7.8; enable IEC 62351-3 as a mitigation |
| A spare RTU500 on 11.x firmware reachable from the WAN | CVE-2026-8065 and CVE-2010-2965 on end-of-life firmware | Upgrade to 12.7.8 or 13.9.1 or replace; block UDP 17185 |
| Relion 670 2.2.3.2 with SPA over TCP enabled and unused | CVE-2021-35535 and CVE-2022-3864 apply to 2.2.3 builds | Update to 2.2.3.7; disable SPA over TCP/IP |
| PCM600 2.11 without the 2024 hotfix; backups on a shared drive | CVE-2022-2513 exposes IED credentials in backups | Install Hotfix 20240426, re-export backups, restrict access |
Where does passive monitoring fit in an ABB review?
A passive capture shows who talks to PLCs, RTUs, relays and servers without logging in to anything. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from a mirror-port recording and builds a host-by-port inventory at connection level, including hosts using TCP 102, TCP 7001, ports 1200 and 1201, Modbus TCP and web ports, and lists remote-access sessions that cross from outside the private address range. It does not decode MMS, SPA or IEC 60870-5-104 messages or read firmware versions from traffic, so those come from the asset list. For that list, Device & Firmware Security identifies components and versions and matches them against NVD, CISA KEV, FIRST EPSS and CISA ICS advisories. An engineer reviews every AI-drafted, cited report before it is sent.
What are the common pitfalls?
- Treating RTU500 and Relion 670 as ABB-only: their newer advisories are Hitachi Energy's, while Relion 615 and PCM600 advisories are ABB's.
- Updating AC500 V2 to 2.8.6 and assuming CVE-2022-31805 is fixed; ABB says it is not, so network separation is the control.
- Patching 800xA servers but not AC 800M controller firmware, or the reverse.
- Leaving an end-of-life RTU500 CMU in service because it still reports, when the 2026 advisory offers no fix below 12.7.8.
- Trusting one score: CISA gives CVE-2019-18247 5.3 where NVD gives 7.5, and ABB gives CVE-2020-8479 9.3 where NVD gives 9.8.
- Forgetting that PCM600 backups and Automation Builder projects hold relay credentials, user management and application files: engineering files need their own access control, not only the devices.
This guide draws on ABB cybersecurity advisories 3ADR010645, 3ADR010667, 3ADR011162, 3ADR011377, 3ADR011407, 3ADR011432, 2PAA121230, 2PAA121231, 7PAA000908, 7PAA001499, 7PAA013309, 1MRS758909, 2NGA001142, 2NGA001147 and 2NGA003170 and ABB's alerts and notifications list; CISA ICS advisories ICSA-12-320-01, ICSA-19-330-01, ICSA-19-330-02, ICSA-20-154-04, ICSA-21-336-04, ICSA-21-336-05, ICSA-21-336-07, ICSA-22-074-01, ICSA-22-333-02, ICSA-23-068-05, ICSA-23-143-02, ICSA-23-220-02, ICSA-24-177-01, ICSA-24-354-01, ICSA-25-128-02, ICSA-25-133-04, ICSA-26-062-03, ICSA-26-274-03 and ICSA-26-279-06 and their CSAF records; CVE.org and NVD records; the CISA KEV catalog; and FIRST EPSS data. KEV and EPSS facts are as of 2026-11-23. It is general information, not a substitute for the vendor advisory or a check of your exact firmware and release levels.
Put this guide to work
Frequently asked questions
Which AC500 firmware fixes the published ABB PLC vulnerabilities?
For AC500 V2, ABB's advisory 3ADR011162 of 28 March 2023 says firmware 2.8.6, available from Automation Builder 2.6.0, fixes eleven of its twelve CVEs, including the port 1200 denial of service CVE-2022-3192, but not the unprotected password transport CVE-2022-31805. Earlier, firmware 2.8.5 fixed the crafted-packet stop CVE-2020-24685, released first for the PM573-ETH and PM583-ETH. The Modbus TCP buffer overread CVE-2025-7745 affects 2.5.2 and earlier and is fixed in 2.5.3, which ABB says was released in 2016. For AC500 V3, ABB's advisory 3ADR011377 of 7 January 2025 says firmware 3.8.0, available from Automation Builder 2.8.0, fixes five CVEs, including the OPC UA crash CVE-2024-5000 and the memory card flaws CVE-2024-12429 and CVE-2024-12430.
Are RTU500 and Relion 670 still ABB products?
The CVE records show the split. Hitachi Energy is the CVE Numbering Authority for the RTU500 series, the Relion 670, 650 and SAM600-IO series and the PCM600 IED Connectivity Packages, and CISA titles its RTU500 advisories from 2021 on as Hitachi Energy. CVE-2021-27196 still names Hitachi ABB Power Grids, and CISA's 2019 Relion 670 advisories are titled ABB. ABB remains the CNA for AC500, Automation Builder, System 800xA, the Relion 611, 615, 620 and REX640 relays and PCM600 itself, whose 2026 Scheduler Service advisory 2NGA003170 is an ABB document. Check both vendors' advisory lists for a mixed ABB and Hitachi Energy substation.
Are any ABB AC500, 800xA, RTU500 or Relion vulnerabilities in the CISA KEV catalog?
No. As of 2026-11-23, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.20, 1,790 entries) has no entry with ABB or Hitachi Energy as the vendor, and none of the CVEs in this guide is listed. The highest FIRST EPSS scores dated 2026-11-22 are for older or third-party code: 0.72714 for CVE-2011-5007 in the CoDeSys web server on early AC500 firmware, 0.61757 for OpenSSL CVE-2023-0286 and 0.57544 for the VxWorks debug agent CVE-2010-2965 on end-of-life RTU500 firmware. ABB-specific CVEs from 2020 on score 0.027 or less.
Which network ports do the ABB and CISA advisories name?
CISA names TCP port 102 for IEC 61850 MMS on Relion 670 (ICSA-19-330-01) and TCP port 7001 for SPA over TCP/IP on Relion 650 and 670 (ICSA-19-330-02). ABB names port 1200 for the 'ABB Tcp/Ip Level 2 AC' engineering protocol on AC500 V2 and port 1201 for the plain 'Tcp/Ip' protocol that avoids CVE-2022-3192. CISA's ICSA-12-320-01 names TCP port 8080 for the CoDeSys web server flaw CVE-2011-5007, and ICSA-26-279-06 names UDP port 17185 for the VxWorks WDB debug service on end-of-life RTU500 firmware. Other ports, such as those for IEC 60870-5-104 or the 800xA CSLib protocol, are not given in these advisories.
Sources
- ABB: Cyber security alerts and notifications
- ABB 3ADR011162: AC500 V2 Cyber Security Advisory (CVE-2022-3192, CVE-2022-31805 and others)
- ABB 3ADR010667: AC500 V2 unauthenticated crafted packet vulnerability (CVE-2020-24685)
- ABB 3ADR010645: AC500 V2 webserver denial of service vulnerability (CVE-2020-24686)
- ABB 3ADR011432: AC500 V2 buffer overread on Modbus protocol (CVE-2025-7745)
- ABB 3ADR011377: AC500 V3 multiple vulnerabilities
- ABB 3ADR011407: Automation Builder vulnerabilities in user management and access control
- ABB 2PAA121231: Multiple vulnerabilities in ABB Central Licensing System
- ABB 2PAA121230: Central Licensing System vulnerabilities, impact on System 800xA, Compact HMI and Control Builder Safe
- ABB 7PAA001499: AC 800M MMS denial of service vulnerability (CVE-2021-22277)
- ABB 7PAA000908: OPC Server for AC 800M remote code execution vulnerability (CVE-2021-22284)
- ABB 7PAA013309: 800xA Base 6.0.x, 6.1.x CSLib communication DoS vulnerability (CVE-2024-3036)
- ABB 1MRS758909: Terminal reboot vulnerability in Relion 630 series
- ABB 2NGA001147: MMS file transfer vulnerability impact on Distribution Automation products (CVE-2021-22283)
- ABB 2NGA001142: Certificate verification vulnerability in Update Manager of PCM600
- ABB 2NGA003170: PCM600 Scheduler Service privilege escalation vulnerability (CVE-2026-15952)
- CISA CSAF: ICSA-12-320-01 ABB AC500 PLC Webserver CoDeSys Vulnerability
- CISA CSAF: ICSA-25-133-04 ABB Automation Builder (Update A)
- CISA CSAF: ICSA-20-154-04 ABB Central Licensing System
- CISA CSAF: ICSA-22-074-01 ABB OPC Server for AC 800M
- CISA CSAF: ICSA-24-177-01 ABB 800xA Base (Update A)
- CISA CSAF: ICSA-21-336-04 Hitachi Energy RTU500 series BCI
- CISA CSAF: ICSA-23-220-02 Hitachi Energy RTU500 series
- CISA CSAF: ICSA-23-143-02 Hitachi Energy's RTU500 Series Product (Update B)
- CISA CSAF: ICSA-24-354-01 Hitachi Energy RTU500 series CMU
- CISA CSAF: ICSA-26-062-03 Hitachi Energy RTU500 Product (Update A)
- CISA CSAF: ICSA-26-279-06 Hitachi Energy RTU500
- CISA CSAF: ICSA-19-330-01 ABB Relion 670 Series
- CISA CSAF: ICSA-19-330-02 ABB Relion 650 and 670 Series
- CISA CSAF: ICSA-21-336-05 Hitachi Energy Relion 670/650/SAM600-IO
- CISA CSAF: ICSA-23-068-05 Hitachi Energy Relion 670, 650 and SAM600-IO Series
- CISA CSAF: ICSA-21-336-07 Hitachi Energy PCM600 Update Manager
- CISA CSAF: ICSA-22-333-02 Hitachi Energy IED Connectivity Packages and PCM600 Products (Update A)
- CISA CSAF: ICSA-26-274-03 ABB Protection and Control IED Manager PCM600
- NVD: CVE-2020-24685 (AC500 V2 crafted packet stops the PLC)
- NVD: CVE-2022-3192 (AC500 V2 port 1200 denial of service)
- NVD: CVE-2025-3394 (Automation Builder user management)
- NVD: CVE-2020-8481 (Central Licensing System information disclosure)
- NVD: CVE-2021-22277 (AC 800M MMS denial of service)
- NVD: CVE-2021-35533 (RTU500 BCI IEC 60870-5-104 reboot)
- NVD: CVE-2026-8065 (RTU500 end-of-life firmware update authentication bypass)
- NVD: CVE-2019-18253 (Relion 670 path traversal)
- NVD: CVE-2021-27196 (IEC 61850 reboot in Relion, REB500 and RTU500)
- NVD: CVE-2022-2513 (PCM600 IED Connectivity Package cleartext credentials)
- CVE.org: CVE-2026-15952 record (ABB PCM600 Scheduler Service)
- CISA Known Exploited Vulnerabilities catalog
- FIRST: Exploit Prediction Scoring System (EPSS)