Security Advisory

CVE-2023-6711: Hitachi Energy RTU500 IEC-104 Overflow

Last updated:
  • CVE-2023-6711

CVE-2023-6711 is a buffer overflow in the SCI and HCI IEC 60870-5-104 components of Hitachi Energy RTU500 series remote terminal units: crafted messages are not validated properly and end in a reboot of the RTU500 CMU. NVD scores it 7.5, Hitachi Energy and CISA 5.9. Eight CMU firmware branches are affected, fixed from 12.0.15 to 13.5.2.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

0.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-6711 · Source: NVD

Affected components

ComponentCPEVersion range
Hitachi Energy RTU500 series CMU firmware (SCI and HCI IEC 60870-5-104)cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*12.0.1-12.0.14, 12.2.1-12.2.11, 12.4.1-12.4.11, 12.6.1-12.6.9, 12.7.1-12.7.6, 13.2.1-13.2.6, 13.4.1-13.4.3 and 13.5.1; fixed in 12.0.15, 12.2.12, 12.4.12, 12.6.10, 12.7.7, 13.2.7, 13.4.4 and 13.5.2 (CISA ICSA-24-354-01, NVD)

What does this mean for affected devices?

CVE-2023-6711 affects the IEC 60870-5-104 code of Hitachi Energy's RTU500 series remote terminal units, in both its SCI and its HCI IEC 60870-5-104 components. NVD's description says "specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU" (NVD). Both NVD and Hitachi Energy record the weakness as CWE-120, a classic buffer overflow.

NVD gives its own Primary CVSS v3.1 score of 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. Hitachi Energy, as CNA, scores it 5.9 (medium) with high attack complexity (AC:H), and CISA's advisory uses the same 5.9; our IEC 60870-5-104 security guide quotes that 5.9 from the CSAF file. The two scores agree on the impact, a CMU reboot with no data exposure, and differ only on how hard the crafted messages are to send.

Which RTU500 firmware is affected, and what fixes it?

Eight CMU firmware branches, each with its own fixed build. CISA's CSAF copy of ICSA-24-354-01, published 2024-12-19, lists the affected ranges and fixes:

  • 12.0.1 to 12.0.14: fixed in 12.0.15.
  • 12.2.1 to 12.2.11: fixed in 12.2.12.
  • 12.4.1 to 12.4.11: fixed in 12.4.12.
  • 12.6.1 to 12.6.9: fixed in 12.6.10.
  • 12.7.1 to 12.7.6: fixed in 12.7.7.
  • 13.2.1 to 13.2.6: fixed in 13.2.7.
  • 13.4.1 to 13.4.3: fixed in 13.4.4.
  • 13.5.1: fixed in 13.5.2.

NVD's CPE configuration, checked 2026-11-17, uses the same branch ends with exclusive upper bounds. NVD published the CVE on 2023-12-19 with a reference to Hitachi Energy's advisory 8DBD000184, which CISA's advisory titles "DoS Vulnerability in Hitachi Energy's RTU500 series products"; CISA republished it as ICSA-24-354-01 on 2024-12-19.

Why does the SCI and HCI scope matter?

NVD and CISA name both IEC-104 interface functions of the RTU500, SCI and HCI, and describe no precondition such as TLS or a licence feature. Any RTU500 on an affected branch that speaks IEC-104 through either function runs the vulnerable parsing code, so every network path that reaches its IEC-104 ports needs the same segmentation. The guide's table of RTU500 IEC-104 advisories shows this CVE next to later RTU500 findings such as CVE-2026-1773, and the same product line also bundles third-party libraries with their own CVEs, for example CVE-2026-6653 in libxml2. For the weakness class, see our memory corruption fix guide.

CVE-2023-6711 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13); CISA's advisory said no known public exploitation had been reported to it. FIRST EPSS gives it 0.00669, the 53rd percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).

To fix it, update each CMU to the fixed build for its branch listed above. Until then, Hitachi Energy recommends following its "Remote Terminal Units Security Deployment Guideline": no direct internet connection, a firewall with a minimal number of exposed ports between the process control network and other networks, and physical protection of the units.

How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.

Evidence

  • NVD description: SCI and HCI IEC 60870-5-104 components, crafted messages not validated, buffer overflow and reboot of the RTU500 CMU. NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; Hitachi Energy Secondary 5.9 AC:H; CWE-120; CPE ranges ending 12.0.15.0, 12.2.12.0, 12.4.12.0, 12.6.10.0, 12.7.7.0, 13.2.7.0, 13.4.4.0 exclusive plus 13.5.1.0; published 2023-12-19; reference 8DBD000184. — NVD
  • CSAF ICSA-24-354-01 (2024-12-19): CVSS 3.1 5.9; affected ranges and per-branch vendor fixes 12.0.15, 12.2.12, 12.4.12, 12.6.10, 12.7.7, 13.2.7, 13.4.4, 13.5.2; RTU Security Deployment Guideline; advisory titled DoS Vulnerability in Hitachi Energy's RTU500 series products; no known public exploitation reported. — CISA ICSA-24-354-01 (CSAF)
  • Not in the CISA KEV catalog, version 2026.11.13, checked 2026-11-17. — CISA KEV
  • EPSS 0.00669, percentile 0.52544, dataset 2026-11-16. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-24-354-01: Hitachi Energy RTU500 series CMU
  3. CISA CSAF: ICSA-24-354-01 (machine-readable advisory)
  4. Hitachi Energy Cybersecurity Advisory 8DBD000184
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Why do NVD and Hitachi Energy give CVE-2023-6711 different scores?

NVD scores it 7.5 with low attack complexity; Hitachi Energy and CISA score it 5.9 with high attack complexity. Both vectors describe the same availability-only impact, a CMU reboot (per NVD and CISA ICSA-24-354-01).

Which RTU500 firmware fixes CVE-2023-6711?

The fix depends on the branch: 12.0.15, 12.2.12, 12.4.12, 12.6.10, 12.7.7, 13.2.7, 13.4.4 or 13.5.2 (per CISA ICSA-24-354-01).

Does CVE-2023-6711 need a special configuration?

No precondition such as TLS or a licence feature is described. NVD and CISA name the SCI and HCI IEC 60870-5-104 components, so an RTU500 using IEC-104 in either direction runs the affected code (per NVD and CISA ICSA-24-354-01).

Is CVE-2023-6711 in the CISA KEV catalog?

No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.00669, the 53rd percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).