Security Advisory

CVE-2026-1773: Hitachi Energy RTU500 IEC-104 U-Frame DoS

Last updated:
  • CVE-2026-1773

CVE-2026-1773 is a denial-of-service flaw in Hitachi Energy RTU500 series remote terminal units: an invalid IEC 60870-5-104 U-format frame can take the unit down when IEC-104 bi-directional functionality is configured. NVD scores it 7.5. IEC 62351-3 TLS mitigates but does not remediate it; CMU firmware 12.7.8, 13.7.8 and 13.8.2 fix it.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

0.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2026-1773 · Source: NVD

Affected components

ComponentCPEVersion range
Hitachi Energy RTU500 series CMU firmware (IEC 60870-5-104 bi-directional functionality)—12.7.1-12.7.7 (fixed in 12.7.8); 13.5.1-13.5.4, 13.6.1-13.6.2 and 13.7.1-13.7.7 (fixed in 13.7.8 or later); 13.8.1 (fixed in 13.8.2) (CISA ICSA-26-062-03)
Hitachi Energy RTU520, RTU530, RTU540 and RTU560 firmware (NVD CPE)cpe:2.3:o:hitachienergy:rtu540_firmware:*:*:*:*:*:*:*:*same ranges as above in NVD's CPE configuration (NVD)

What does this mean for affected devices?

CVE-2026-1773 is a denial-of-service flaw in the IEC 60870-5-104 stack of Hitachi Energy's RTU500 series remote terminal units. NVD's description reads: "Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation" (NVD). U-format frames are the unnumbered control frames of IEC-104, STARTDT, STOPDT and TESTFR, which every session uses to start, stop and test the link.

NVD gives its own Primary CVSS v3.1 score of 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H: network-reachable, no privileges, no user interaction, availability impact only. Hitachi Energy, as CNA, gives a CVSS v4.0 score of 8.7 and records the weakness as CWE-184, an incomplete list of disallowed inputs.

Which RTU500 firmware is affected, and what fixes it?

Five CMU firmware ranges. CISA's CSAF copy of ICSA-26-062-03, a verbatim republication of Hitachi Energy PSIRT advisory 8DBD000237 at revision 5 (2026-10-20), lists them:

  • 12.7.1 to 12.7.7: update to 12.7.8, added as a fixed version on 2026-09-29.
  • 13.5.1 to 13.5.4, 13.6.1 to 13.6.2 and 13.7.1 to 13.7.7: update to 13.7.8 "or latest".
  • 13.8.1: update to 13.8.2, added as a fixed version on 2026-05-26.

NVD's CPE configuration, checked 2026-11-17, applies the same ranges to the RTU520, RTU530, RTU540 and RTU560 firmware. The same advisory also covers CVE-2026-1772, an RTU500 web interface flaw that lets an unprivileged user read user management information, and two libexpat CVEs that only matter when IEC 61850 is configured.

Why is IEC 62351-3 only a mitigation here?

Hitachi Energy states that 62351-3 "does not remediate the vulnerability but mitigates the risk of exploitation." TLS limits which peers can open an IEC-104 session with the RTU, but the advisory names no change to how U-format frames are handled, so the fix is still the firmware update. Our IEC 60870-5-104 security guide quotes this advisory under "Treating TLS as a patch" and lists bidirectional mode as a configuration that has to be recorded next to the firmware version. Earlier RTU500 IEC-104 findings, such as CVE-2023-6711 and CVE-2022-4608, are listed on the same page. For the weakness class, see our input handling fix guide.

CVE-2026-1773 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.00453, the 40th percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).

To fix it, update each CMU to 12.7.8, 13.7.8 or later, or 13.8.2, depending on its branch. Until then, check whether IEC 60870-5-104 bi-directional functionality is configured at all; units without it are outside this CVE's scope. Where it is needed, enable IEC 62351-3 and follow the advisory's general mitigation factors: no direct internet connection and a firewall with a minimal number of exposed ports.

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD description: potential denial of service on reception of invalid U-format frame; only if IEC 60870-5-104 bi-directional functionality configured; IEC 62351-3 mitigates but does not remediate. NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; Hitachi Energy CVSS v4.0 8.7; CWE-184; CPE rtu520/530/540/560 firmware 12.7.1-12.7.7, 13.5.1-13.5.4, 13.6.1-13.6.2, 13.7.1 to before 13.7.8, 13.8.1; published 2026-02-24. — NVD
  • CSAF ICSA-26-062-03 revision 5 (2026-10-20), verbatim republication of Hitachi Energy PSIRT 8DBD000237: known affected 12.7.1-12.7.7, 13.5.1-13.5.4, 13.6.1-13.6.2, 13.7.1-13.7.7, 13.8.1; fixes 12.7.8, 13.7.8 or latest, 13.8.2; revision 3 (2026-05-26) added 13.8.2, revision 4 (2026-09-29) added 12.7.8; also covers CVE-2026-1772, CVE-2024-8176, CVE-2025-59375. — CISA ICSA-26-062-03 (CSAF)
  • Not in the CISA KEV catalog, version 2026.11.13, checked 2026-11-17. — CISA KEV
  • EPSS 0.00453, percentile 0.3986, dataset 2026-11-16. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-26-062-03: Hitachi Energy RTU500 Product
  3. CISA CSAF: ICSA-26-062-03 (machine-readable advisory)
  4. Hitachi Energy PSIRT advisory 8DBD000237
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which RTU500 configuration exposes CVE-2026-1773?

Only an RTU500 with IEC 60870-5-104 bi-directional functionality configured. Units that use IEC-104 without bi-directional mode are outside its scope (per NVD and CISA ICSA-26-062-03).

Does enabling IEC 62351-3 TLS fix CVE-2026-1773?

No. The advisory says 62351-3 "does not remediate the vulnerability but mitigates the risk of exploitation"; the firmware update is the fix (per CISA ICSA-26-062-03).

Which firmware fixes CVE-2026-1773?

CMU firmware 12.7.8 for the 12.7 branch, 13.7.8 or later for 13.5 to 13.7, and 13.8.2 for 13.8.1 (per CISA ICSA-26-062-03).

Is CVE-2026-1773 in the CISA KEV catalog?

No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.00453, the 40th percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).