Security Advisory

CVE-2022-4608: Hitachi Energy RTU500 IEC-104 TLS Restart

Last updated:
  • CVE-2022-4608

CVE-2022-4608 is a stack overflow in the HCI IEC 60870-5-104 function of Hitachi Energy RTU500 series remote terminal units: with IEC 62351-3 TLS configured, an RTU-initiated update of session parameters after the session resumption interval expires restarts the CMU. NVD scores it 7.5. CISA lists CMU firmware 13.3.1 and 13.3.2 as affected, fixed in 13.3.3 or 13.4.1.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

0.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-4608 · Source: NVD

Affected components

ComponentCPEVersion range
Hitachi Energy RTU500 series CMU firmware (HCI IEC 60870-5-104 with IEC 62351-3)cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*13.3.1 and 13.3.2, fixed in 13.3.3 or 13.4.1 (CISA ICSA-23-220-02); NVD CPE also lists 13.3.3 and 13.4.1 as vulnerable

What does this mean for affected devices?

CVE-2022-4608 sits in the HCI IEC 60870-5-104 function of Hitachi Energy's RTU500 series, the remote terminal units that carry telecontrol traffic between substation equipment and a utility's control center. NVD's description says the flaw "can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3", the TLS profile for IEC-104. Once the session resumption interval expires, "an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow" (NVD).

NVD gives its own Primary CVSS v3.1 score of 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, the same score and vector Hitachi Energy submitted as CNA. The impact is availability only: the control module (CMU) restarts, and the telecontrol link drops while it does. NVD records CWE-787 (out-of-bounds write); CISA's advisory classes it as CWE-121, stack-based buffer overflow.

Which RTU500 firmware is affected, and what fixes it?

CMU firmware 13.3.1 and 13.3.2, according to CISA. CISA's machine-readable CSAF copy of ICSA-23-220-02, published 2023-08-08, lists "RTU500 series CMU: >= 13.3.1 | <= 13.3.2" as affected and states that "Hitachi Energy recommends users update to CMU Firmware versions 13.3.3 or 13.4.1." NVD's CPE configuration, checked 2026-11-17, marks 13.3.1, 13.3.2, 13.3.3 and 13.4.1 all as vulnerable, so a scanner that matches on NVD's CPE list will flag 13.3.3 and 13.4.1 units that CISA names as the fixed builds. Read the firmware version from each CMU and compare it with Hitachi Energy's advisory 8DBD000121, which CISA cites as its source.

CISA's advisory also gives the configuration workaround: "A possible mitigation is to disable the HCI IEC 60870-5-104 function or its IEC 62351-3 and IEC 62351-5 features if they are not used." By default, the HCI IEC 60870-5-104 and its IEC 62351-3 or IEC 62351-5 support are disabled, so an RTU500 that never had TLS switched on for its HCI interface is outside this CVE's scope.

How does this relate to CVE-2022-2502?

Both CVEs come from the same advisory and both are stack overflows that restart the CMU, but each needs a different security feature turned on. CVE-2022-2502 needs IEC 62351-5 application-layer security with the separately ordered "Advanced security" licence; CVE-2022-4608 needs IEC 62351-3 TLS. Our IEC 60870-5-104 security guide lists the pair as a reminder that the features meant to secure IEC-104 add their own code to test, including session resumption expiry and renegotiation in the TLS layer. The IEC 62351 guide explains what 62351-3 does protect. For the weakness class, see our memory corruption fix guide.

CVE-2022-4608 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13), and CISA's advisory reported no known public exploits specifically targeting it. FIRST EPSS gives it 0.00712, the 54th percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).

To fix it, update affected CMUs to firmware 13.3.3 or 13.4.1 or later. Until then, disable IEC 62351-3 on the HCI IEC 60870-5-104 interface if it is unused, and keep the RTU off the internet and behind a firewall with minimal exposed ports, as the advisory recommends.

How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.

Evidence

  • NVD description: exploitable only if HCI 60870-5-104 is configured with IEC 62351-3 support; after session resumption interval expiry an RTU500-initiated session parameter update causes a restart from a stack overflow. NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; CWE-787; CPE rtu500_firmware 13.3.1, 13.3.2, 13.3.3, 13.4.1. — NVD
  • CSAF ICSA-23-220-02 (2023-08-08): CWE-121; known affected RTU500 series CMU >= 13.3.1 <= 13.3.2; vendor fix CMU firmware 13.3.3 or 13.4.1; HCI IEC 60870-5-104 and its 62351-3/-5 support disabled by default; source Hitachi Energy advisory 8DBD000121; no known public exploits. — CISA ICSA-23-220-02 (CSAF)
  • Not in the CISA KEV catalog, version 2026.11.13, checked 2026-11-17. — CISA KEV
  • EPSS 0.00712, percentile 0.54182, dataset 2026-11-16. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-23-220-02: Hitachi Energy RTU500 series
  3. CISA CSAF: ICSA-23-220-02 (machine-readable advisory)
  4. Hitachi Energy Cyber Security Advisory 8DBD000121
  5. NVD (companion CVE-2022-2502)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which RTU500 configuration exposes CVE-2022-4608?

Only an RTU500 whose HCI IEC 60870-5-104 interface is configured with IEC 62351-3 (TLS) support. The HCI IEC 60870-5-104 function and its 62351-3 support are disabled by default (per NVD and CISA ICSA-23-220-02).

Which firmware fixes CVE-2022-4608?

CISA lists CMU firmware 13.3.1 and 13.3.2 as affected and recommends 13.3.3 or 13.4.1. NVD's CPE list also marks 13.3.3 and 13.4.1 as vulnerable, so check the version on each CMU against Hitachi Energy advisory 8DBD000121 (per CISA ICSA-23-220-02 and NVD).

What happens to the RTU when CVE-2022-4608 triggers?

The CMU restarts after a stack overflow, so telecontrol traffic over IEC-104 stops until it is back up. NVD scores the impact as availability only, 7.5 (per NVD).

Is CVE-2022-4608 in the CISA KEV catalog?

No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.00712, the 54th percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).