Security Advisory

CVE-2019-6809: Modicon Invalid Data Read DoS

Last updated:
  • CVE-2019-6809

CVE-2019-6809 is a denial-of-service flaw in Schneider Electric Modicon M580, M340, Quantum and Premium controllers: reading invalid data from the controller over the network triggers an uncaught exception that can stop it. NVD, Schneider and CISA all score it 7.5. Fixes are M580 SV4.20, M340 SV3.60, Quantum v3.60 and Premium v3.20.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-6809 · Source: NVD

Affected components

ComponentCPEVersion range
Schneider Electric Modicon M580 (BMEP*, BMEH*)cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:*Affected: versions prior to v2.90 (SEVD-2019-134-11 v14.0.0, NVD CPE). Remediation: firmware SV4.20 or later with EcoStruxure Control Expert v16.0, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01)
Schneider Electric Modicon M340 CPU (BMXP34*)cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:*Affected: versions prior to v3.10 (SEVD-2019-134-11, NVD CPE). Remediation: firmware SV3.60 or later with Control Expert v16.0 or later (SEVD-2019-134-11, ICSA-25-114-01)
Schneider Electric Modicon Quantum (140CPU65150, 140CPU65160, 140CPU65260, 140CPU65860, 140CPU67060, 140CPU67160, 140CPU67260, 140CPU67261, 140CPU67861)cpe:2.3:o:schneider-electric:modicon_quantum_firmware:*:*:*:*:*:*:*:*Versions prior to v3.60; fixed in v3.60 (SEVD-2019-134-11 v3.0.0 onward, ICSA-25-114-01); NVD CPE has no version limit. End of life as of 2026-11-20
Schneider Electric Modicon Premium (TSXP57*, TSXH57*)cpe:2.3:o:schneider-electric:modicon_premium_firmware:*:*:*:*:*:*:*:*Versions prior to v3.20; fixed in v3.20 through Schneider customer support (SEVD-2019-134-11, ICSA-25-114-01); NVD CPE has no version limit. End of life as of 2026-11-20

What does this mean for affected devices?

NVD carries Schneider Electric's description: a "CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware versions prior to V2.90), Modicon M340 (firmware versions prior to V3.10), Modicon Premium (all versions), Modicon Quantum (all versions), which could cause a possible denial of service when reading invalid data from the controller." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), with CVSS v2 7.8. NVD classes the weakness as CWE-755 (improper handling of exceptional conditions); the Schneider CNA and CISA use CWE-248. The record was published on 2019-09-17 and is PUBLISHED on CVE.org (NVD, CVE record).

What is known about the trigger?

Schneider publishes only the outline: reading invalid data from the controller causes an uncaught exception and a possible denial of service, and the CVSS vector marks it as a network attack. CVE-2019-6809 was one of four CVEs Schneider added to SEVD-2019-134-11 in version 2.0.0 (13 August 2019), alongside CVE-2019-6828, CVE-2019-6829 and CVE-2019-6830, and the notice credits Jared Rittle of Cisco Talos and Gao Jian of nsfocus for this group. Neither the NVD nor the CVE.org record links a Talos report for it. The scores agree on an unauthenticated network attack with availability impact only.

Which Modicon firmware is affected, and what fixes it?

Controller Affected (SEVD-2019-134-11 v14.0.0, CISA CSAF) Fix
Modicon M580 (BMEP*, BMEH*) prior to v2.90 SV4.20 with Control Expert v16.0
Modicon M340 CPU (BMXP34*) prior to v3.10 SV3.60 with Control Expert v16.0 or later
Modicon Quantum (140CPU65150 to 140CPU67861) prior to v3.60 v3.60
Modicon Premium (TSXP57*, TSXH57*) prior to v3.20 v3.20 from Schneider customer support

The CVE description and NVD's CPE still say "all versions" for Quantum and Premium, because the record was published before Schneider's version 3.0.0 (10 December 2019) added Quantum v3.60 and Premium v3.20 as fixes. CISA's ICSA-25-114-01 CSAF (Update A, 23 April 2026) lists those as fixed and scores CVSS v3.1 7.5 and CVSS v4.0 8.7. Unlike CVE-2019-6807, this CVE does not list MC80, Momentum or the PLC Simulator.

How do you fix or mitigate it?

On M580 and M340 the remediation is three steps: update EcoStruxure Control Expert and the controller firmware, set an application password and the new firmware version in each project, then rebuild and transfer every project. Version 5.0.0 of the notice (12 October 2020) made those extra steps a requirement for this CVE. If you cannot update, SEVD-2019-134-11 lists the same mitigations for every Modicon family: set an application password in the project properties, segment the network and firewall all unauthorized access to port 502/TCP, and configure the controller's Access Control List. For M580 it adds IPsec through a BMENOC or BMENUA0100 module and CPU memory protection tied to a physical input (not available on Hot Standby CPUs); for M580 and M340 it also suggests an external VPN firewall such as the Belden EAGLE40-07. Quantum and Premium are end of life as of 2026-11-20; Schneider advises migrating to M580.

Our UMAS protocol security guide covers UMAS function codes and how to spot them on the wire, and the Modbus protocol security guide covers port 502 exposure. The same notice covers the UMAS crashes CVE-2018-7856, CVE-2018-7843, CVE-2018-7845 and CVE-2018-7852, and CVE-2018-7842, which has no fix on Quantum and Premium.

CVE-2019-6809 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.01757, the 78.4th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-20): status Modified; published 2019-09-17; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 7.8; CWE-755 (NVD), CWE-248 (Schneider); CPE modicon_m580_firmware before 2.90, modicon_m340_firmware before 3.10, modicon_premium_firmware and modicon_quantum_firmware without version limit; reference SEVD-2019-134-11 only. — NVD
  • CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider Electric, published 2019-09-17; CWE-248; affected M580 prior to V2.90, M340 prior to V3.10, Premium and Quantum all versions; no CNA CVSS metric; reference SEVD-2019-134-11. — CVE.org
  • Schneider Electric SEVD-2019-134-11 v14.0.0 (updated 2026-09-08), read 2026-11-20: CVE-2019-6809 CWE-248, CVSS v3.1 7.5, v4.0 8.7, denial of service when reading invalid data from the controller; affected M580 prior to v2.90, M340 prior to v3.10, Quantum prior to v3.60, Premium prior to v3.20; added in v2.0.0 (2019-08-13) with CVE-2019-6828/6829/6830; Quantum and Premium fix in v3.0.0 (2019-12-10); additional remediation steps in v5.0.0 (2020-10-12); credits Jared Rittle (Cisco Talos) and Gao Jian (nsfocus). — Schneider Electric SEVD-2019-134-11
  • CISA ICSA-25-114-01 CSAF (Update A, current release 2026-04-23), read 2026-11-20: CVE-2019-6809 CWE-248, CVSS v3.1 7.5, v4.0 8.7; known affected M580 prior to v2.90, M340 prior to v3.10, Quantum prior to v3.60, Premium prior to v3.20; fixed M580 4.20, M340 3.60, Quantum 3.60, Premium 3.20. — CISA CSAF ICSA-25-114-01
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
  • EPSS 0.01757, percentile 0.78446, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories

Sources

  1. NVD: CVE-2019-6809
  2. CVE.org record CVE-2019-6809 (CNA: Schneider Electric)
  3. Schneider Electric Security Notification SEVD-2019-134-11: Multiple Vulnerabilities in Modicon Controller Products (v14.0.0, 8 September 2026; PDF)
  4. CISA ICS Advisory ICSA-25-114-01: Schneider Electric Modicon Controllers (Update A)
  5. CISA CSAF record for ICSA-25-114-01
  6. CISA Known Exploited Vulnerabilities catalog
  7. FIRST EPSS score for CVE-2019-6809

Frequently asked questions

Which firmware fixes CVE-2019-6809?

Modicon M580 SV4.20 with EcoStruxure Control Expert v16.0, M340 SV3.60, Quantum v3.60 and Premium v3.20, which Schneider supplies through customer support. On M580 and M340, also set an application password and rebuild and transfer every project (per Schneider SEVD-2019-134-11 and CISA ICSA-25-114-01).

Why does NVD still say all Quantum and Premium versions are affected?

The CVE record was published on 2019-09-17, before Schneider's notice version 3.0.0 (10 December 2019) added Quantum v3.60 and Premium v3.20 as fixes. As of 2026-11-20 the NVD description and CPE were not updated to match (per NVD and SEVD-2019-134-11).

Is there a public proof of concept?

Neither the NVD nor the CVE.org record links one. Schneider credits Jared Rittle of Cisco Talos and Gao Jian of nsfocus for the group of CVEs that includes CVE-2019-6809 (per SEVD-2019-134-11).

How do I protect a controller I cannot update?

Firewall all unauthorized access to port 502/TCP, configure the controller's Access Control List and set an application password. For M580, Schneider also lists IPsec modules and CPU memory protection; Quantum and Premium are end of life and Schneider advises migrating to M580 (per SEVD-2019-134-11).