CVE-2018-7852 is a denial-of-service flaw in Schneider Electric Modicon M580, M340, Quantum and Premium controllers: an unauthenticated UMAS request with an invalid private command parameter, sent over Modbus port 502, can halt the CPU until it is power cycled. NVD and Schneider both score it 7.5. Schneider names M580 SV4.20, M340 SV3.60, Quantum v3.60 and Premium V3.20 as fixed; Quantum Safety gets no fix.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
3.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-7852 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Modicon M580 (BMEP*, BMEH*, excluding M580 CPU Safety) | cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v2.80 per the SEVD-2019-134-11 v14.0.0 table (its revision log records a correction to 2.90). Remediation: firmware SV4.20 or later with EcoStruxure Control Expert v16.0, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon M340 CPU (BMXP34*) | cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v3.01 (SEVD-2019-134-11 v14.0.0). Remediation: firmware SV3.60 or later with Control Expert v16.0 or later, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon Quantum (140CPU65150, 140CPU65160, 140CPU65260, 140CPU65860, 140CPU67060, 140CPU67160, 140CPU67260, 140CPU67261, 140CPU67861) | cpe:2.3:o:schneider-electric:modicon_quantum_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v3.60. Fixed: Quantum firmware v3.60 (SEVD-2019-134-11 v14.0.0, ICSA-25-114-01 CSAF). End of life; Schneider also advises port 502/TCP firewalling, the Access Control List and migration to M580 |
| Schneider Electric Modicon Quantum Safety | cpe:2.3:o:schneider-electric:modicon_quantum_firmware:*:*:*:*:*:*:*:* | All versions; end of life, no fix; mitigate with port 502/TCP firewalling and the Access Control List, migrate to M580 (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon Premium (TSXP57*, TSXH57*) | cpe:2.3:o:schneider-electric:modicon_premium_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v3.20. Fixed: Premium firmware V3.20, obtained through Schneider Electric customer support (SEVD-2019-134-11 v14.0.0, ICSA-25-114-01 CSAF). End of life; migration to M580 advised |
What does this mean for affected devices?
NVD carries Schneider Electric's description: a "CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service when an invalid private command parameter is sent to the controller over Modbus." NVD's Primary score is CVSS v3.1 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, with CWE-755; its CVSS v2 score is 5.0. CISA-ADP adds a Secondary CVSS v3.1 score with the same 7.5 vector, lists CWE-248, and its SSVC entry rates exploitation as proof of concept and the attack as automatable. The record was published on 2019-05-22, and the CVE.org record is PUBLISHED with Schneider Electric as CNA (NVD, CVE record).
What does the crash look like on the controller?
Cisco Talos found the flaw in a Modicon M580 BMEP582040 on firmware SV2.70 and published it as TALOS-2019-0763 on 10 June 2019. The report groups several crashes in UMAS function code 0x6d, carried inside Modbus function code 0x5a on port 502. Unauthenticated requests with certain subcodes, for example subcode 0x00 with sub-subcode 0x80, put the CPU into a non-recoverable fault: remote communication stops, the process logic stops executing, and the controller needs a physical power cycle. Another variant (sub-subcode 0xf9) stops execution and removes the loaded program, which then has to be restored from Unity Pro. Talos scores it CVSS v3.0 7.5 with CWE-248.
Which Modicon firmware fixes it?
Schneider's notice SEVD-2019-134-11 (version 14.0.0, 8 September 2026) scores it CVSS v3.1 7.5 and CVSS v4.0 8.7. Its affected-products table lists M580 versions prior to v2.80, M340 prior to v3.01, Quantum prior to v3.60, Premium prior to v3.20 and every Quantum Safety version; the revision log for version 2.0.0 records a correction of the M580 release for this CVE from 2.80 to 2.90, while the current table still reads v2.80. The remediation section points to M580 SV4.20 and M340 SV3.60 with EcoStruxure Control Expert v16.0, plus an application password and a rebuild and transfer of every project. Quantum firmware v3.60 and Premium firmware V3.20 are listed as fixed; Quantum Safety has no fix and is end of life, so Schneider advises firewalling port 502/TCP, the Access Control List and migration to M580. CISA's CSAF file for ICSA-25-114-01 carries the same fixed versions.
How do I reduce exposure before patching?
Block port 502/TCP from every host that is not an engineering workstation or HMI, and alert on UMAS function code 0x6d from unexpected sources. Our UMAS protocol security guide covers detection, and the input handling fix guide covers the unchecked-parameter pattern behind this crash. The sibling flaws from the same Talos research are the memory read crash CVE-2018-7843 and the memory over-read CVE-2018-7845; other UMAS findings in the same notice are CVE-2018-7842 and CVE-2018-7847.
CVE-2018-7852 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.03473, the 89.3rd percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: CWE-248 uncaught exception (description) in all versions of M580, M340, Quantum and Premium, denial of service via an invalid private command parameter over Modbus; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H with CWE-755, v2 5.0; CISA-ADP Secondary CVSS v3.1 7.5 (same vector) with CWE-248 and SSVC exploitation poc, automatable yes, technical impact partial; published 2019-05-22. Read 2026-11-19 (NVD API data fetched 2026-11-19). — NVD
- CVE.org record state PUBLISHED, CNA Schneider Electric (schneider), published 2019-05-22; references SEVD-2019-134-11 and TALOS-2019-0763; no CNA CVSS metric; CISA-ADP container present. Checked 2026-11-19. — CVE.org
- SEVD-2019-134-11 v14.0.0 (8 September 2026): CVSS v3.1 7.5 A:H, CVSS v4.0 8.7, CWE-248; affected M580 prior to v2.80, M340 prior to v3.01, Quantum prior to v3.60, Quantum Safety all versions, Premium prior to v3.20; revision 2.0.0 (13 August 2019) changed the M580 release for this CVE from 2.80 to 2.90; revision 3.0.0 (10 December 2019) added the Premium and Quantum fix; remediation M580 SV4.20, M340 SV3.60, Quantum v3.60, Premium V3.20; Quantum Safety end of life with port 502 firewalling and Access Control List. Read 2026-11-19. — Schneider Electric SEVD-2019-134-11
- ICSA-25-114-01 (Update A, current release 2026-04-23) CSAF: CVE-2018-7852 CVSS v3.1 7.5, CWE-248; fixed products M580 firmware 4.20, M340 3.60, Quantum 3.60 (nine CPU references) and Premium 3.20; Quantum Safety all versions known affected with mitigation only. Read 2026-11-19 from the CSAF file. — CISA ICSA-25-114-01 (CSAF)
- TALOS-2019-0763 (10 June 2019): multiple denial-of-service issues in UMAS function code 0x6d on M580 BMEP582040 SV2.70; unauthenticated requests cause a non-recoverable fault requiring a power cycle, one variant removes the loaded program; Talos CVSS v3.0 7.5, CWE-248; vendor patched 2019-05-14. Read 2026-11-19. — Cisco Talos TALOS-2019-0763
- Not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). Checked 2026-11-19. — CISA KEV
- EPSS 0.03473, percentile 0.89321, dataset 2026-11-18. Read 2026-11-19. — FIRST EPSS

Related advisories
Sources
- NVD: CVE-2018-7852
- CVE.org record CVE-2018-7852 (CNA: Schneider Electric)
- Schneider Electric Security Notification SEVD-2019-134-11: Multiple Vulnerabilities in Modicon Controller Products (v14.0.0, 8 September 2026; PDF)
- CISA ICS Advisory ICSA-25-114-01: Schneider Electric Modicon Controllers (Update A)
- CISA CSAF record for ICSA-25-114-01
- Cisco Talos TALOS-2019-0763: Schneider Electric Modicon M580 UMAS function code 0x6d denial of service (CVE-2018-7852)
- CISA Known Exploited Vulnerabilities catalog
- FIRST EPSS score for CVE-2018-7852
Frequently asked questions
Which Modicon firmware fixes CVE-2018-7852?
Schneider lists M580 SV4.20 and M340 SV3.60 with EcoStruxure Control Expert v16.0, an application password and a rebuild and transfer of each project, plus Quantum firmware v3.60 and Premium firmware V3.20 from customer support (per Schneider SEVD-2019-134-11 v14.0.0 and the ICSA-25-114-01 CSAF).
What if a controller cannot be updated, such as a Quantum Safety CPU?
Quantum Safety has no fix because it is end of life. Schneider advises network segmentation with a firewall that blocks unauthorized access to port 502/TCP, the Access Control List, and migration to M580 (per Schneider SEVD-2019-134-11).
What happens to the controller when the flaw is triggered?
In the main variants the CPU enters a non-recoverable fault: remote communication and process logic stop and a physical power cycle is needed; one variant removes the loaded program (per Cisco Talos TALOS-2019-0763).
Why does NVD list CWE-755 while Schneider lists CWE-248?
NVD's own analysis maps the flaw to CWE-755, improper handling of exceptional conditions, while Schneider, Talos and CISA-ADP use CWE-248, uncaught exception; all three CVSS v3.1 scores are 7.5 with availability impact only (per NVD and Schneider SEVD-2019-134-11).
Is CVE-2018-7852 in the CISA KEV catalog?
No, not as of 2026-11-19 (catalog version 2026.11.18). FIRST EPSS gives it 0.03473, the 89.3rd percentile, in the 2026-11-18 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?