CVE-2018-7842 is an authentication bypass in Schneider Electric Modicon M580, M340, Quantum and Premium controllers: an attacker on Modbus port 502 can brute-force the one-byte UMAS session ID of a logged-in engineering user and run privileged commands without the project password. NVD scores it 9.8, Schneider 7.5. Schneider lists M580 before v2.90 and M340 before v3.10 as affected and points to SV4.20 and SV3.60 as current remediation; Quantum and Premium get no fix.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
35.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-7842 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Modicon M580 (BMEP*, BMEH*, excluding M580 CPU Safety) | cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v2.90 (SEVD-2019-134-11 v14.0.0 affected-products table). Remediation: firmware SV4.20 or later with EcoStruxure Control Expert v16.0, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon M340 CPU (BMXP34*) | cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v3.10 (SEVD-2019-134-11 v14.0.0). Remediation: firmware SV3.60 or later with Control Expert v16.0 or later, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon Quantum and Quantum Safety | cpe:2.3:o:schneider-electric:modicon_quantum_firmware:*:*:*:*:*:*:*:* | All versions; end of life, no fix; mitigate with port 502/TCP firewalling and the Access Control List, migrate to M580 (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon Premium (TSXP57*, TSXH57*) | cpe:2.3:o:schneider-electric:modicon_premium_firmware:*:*:*:*:*:*:*:* | All versions; end of life, no fix; mitigate with port 502/TCP firewalling and the Access Control List, migrate to M580 (SEVD-2019-134-11, ICSA-25-114-01) |
What does this mean for affected devices?
NVD carries Schneider Electric's description: a "CWE-290: Authentication Bypass by Spoofing vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause an elevation of privilege by conducting a brute force attack on Modbus parameters sent to the controller." NVD's Primary score is CVSS v3.1 9.8 (critical), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CWE-290; its CVSS v2 score is 7.5. The record was published on 2019-05-22, and the CVE.org record is PUBLISHED with Schneider Electric as CNA (NVD, CVE record).
How does the attack work on the controller?
Cisco Talos found the flaw in a Modicon M580 BMEP582040 on firmware SV2.70 and published it as TALOS-2018-0741 on 10 June 2019. The M580 uses the UMAS requests TAKE_PLC_RESERVATION and RELEASE_PLC_RESERVATION to decide which client may run privileged commands. When a project has a password, the client must send it to get an elevated session ID. Talos found that the session ID is one byte, so there are only 256 values. While a legitimate user holds a reservation, most often Unity Pro, an attacker on port 502 can loop through all 256 values until the controller answers with response code 0xFE, then run privileged commands such as reading the password-protected program without knowing the password.
How do Schneider and NVD score it?
Schneider's notice SEVD-2019-134-11 (version 14.0.0, 8 September 2026) scores it CVSS v3.1 7.5, vector AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N, and CVSS v4.0 8.7, with confidentiality impact only. Talos also gives 7.5. NVD's 9.8 assumes full integrity and availability impact as well. CISA republished the notice as ICSA-25-114-01 with the same 7.5 score and CWE-290.
Which Modicon firmware fixes it?
The notice's affected-products table lists M580 versions prior to v2.90, M340 versions prior to v3.10, and all versions of Quantum, Quantum Safety and Premium. The remediation section, and the fixed product status in CISA's CSAF file, now point to M580 firmware SV4.20 and M340 firmware SV3.60, with EcoStruxure Control Expert v16.0. The fix has three steps: update software and firmware, set an application password and the new firmware version in the project, then rebuild and transfer every project. Firmware alone does not close the gap if the project has no password.
Quantum and Premium are end of life and get no fix as of 2026-11-19. Schneider tells owners to firewall port 502/TCP, configure the Access Control List and migrate to M580. Our UMAS protocol security guide covers the reservation mechanism and detection rules, and the authentication bypass fix guide covers the CWE-290 pattern. The sister finding CVE-2018-7846 uses the same brute force to end sessions; the older protocol-level findings are CVE-2017-6032 and CVE-2017-6034.
CVE-2018-7842 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.35039, the 98.5th percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: CWE-290 authentication bypass by spoofing in all versions of M580, M340, Quantum and Premium, elevation of privilege by brute force on Modbus parameters; NVD Primary CVSS v3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, v2 7.5; CPE configuration lists all firmware versions of the four product lines; published 2019-05-22. Read 2026-11-19 (NVD API data fetched 2026-11-19). — NVD
- CVE.org record state PUBLISHED, CNA Schneider Electric (schneider), published 2019-05-22; references SEVD-2019-134-11 and TALOS-2018-0741; no CNA CVSS metric in the record. Checked 2026-11-19. — CVE.org
- SEVD-2019-134-11 v14.0.0 (8 September 2026): CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N, CVSS v4.0 8.7, CWE-290; affected M580 prior to v2.90, M340 prior to v3.10, Quantum, Quantum Safety and Premium all versions; remediation M580 SV4.20 and M340 SV3.60 with Control Expert v16.0, application password, rebuild and transfer; Quantum/Premium end of life, firewall port 502 and Access Control List; credits Jared Rittle (Cisco Talos), Pavel Nesterov and Artem Zinenko (Kaspersky ICS CERT). Read 2026-11-19. — Schneider Electric SEVD-2019-134-11
- ICSA-25-114-01 (Update A, current release 2026-04-23) is a verbatim CISA republication of SEVD-2019-134-11; for CVE-2018-7842: CVSS v3.1 7.5, CWE-290, fixed products M580 firmware 4.20 and M340 firmware 3.60, Quantum, Quantum Safety and Premium carry the CSAF remediation category for no fix. Read 2026-11-19 from the CSAF file. — CISA ICSA-25-114-01 (CSAF)
- TALOS-2018-0741 (10 June 2019): improper authentication in UMAS PLC reservation of M580 BMEP582040 SV2.70; one-byte session ID (256 values) brute-forced while a legitimate session is held; response code 0xFE marks a valid session; password-protected strategy can be read; Talos CVSS v3.0 7.5; vendor patched 2019-05-14. Read 2026-11-19. — Cisco Talos TALOS-2018-0741
- Not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). Checked 2026-11-19. — CISA KEV
- EPSS 0.35039, percentile 0.98468, dataset 2026-11-18. Read 2026-11-19. — FIRST EPSS

Related advisories
Sources
- NVD: CVE-2018-7842
- CVE.org record CVE-2018-7842 (CNA: Schneider Electric)
- Schneider Electric Security Notification SEVD-2019-134-11: Multiple Vulnerabilities in Modicon Controller Products (v14.0.0, 8 September 2026; PDF)
- CISA ICS Advisory ICSA-25-114-01: Schneider Electric Modicon Controllers (Update A)
- CISA CSAF record for ICSA-25-114-01
- Cisco Talos TALOS-2018-0741: Schneider Electric Modicon M580 UMAS improper authentication (CVE-2018-7842)
- CISA Known Exploited Vulnerabilities catalog
- FIRST EPSS score for CVE-2018-7842
Frequently asked questions
Which Modicon firmware versions does Schneider list for CVE-2018-7842?
The affected table names M580 versions prior to v2.90, M340 prior to v3.10, and all Quantum, Quantum Safety and Premium versions. The remediation section points to M580 SV4.20 and M340 SV3.60 with EcoStruxure Control Expert v16.0 (per Schneider SEVD-2019-134-11 v14.0.0).
Is a firmware update enough to fix CVE-2018-7842?
No. Schneider's remediation also requires setting an application password and the new firmware version in each Control Expert project, then rebuilding and transferring all projects to the controllers (per Schneider SEVD-2019-134-11).
How does the brute force against the UMAS session work?
The M580 session ID is one byte, so an attacker can try all 256 values while a legitimate user holds a reservation; a 0xFE response marks a valid session, which then runs privileged commands such as reading a password-protected program (per Cisco Talos TALOS-2018-0741).
Why does NVD score CVE-2018-7842 higher than Schneider?
NVD's CVSS v3.1 vector rates confidentiality, integrity and availability all high for 9.8, while Schneider's vector rates confidentiality high only, for 7.5; CISA's republication uses Schneider's 7.5 (per NVD and CISA ICSA-25-114-01).
Is CVE-2018-7842 in the CISA KEV catalog?
No, not as of 2026-11-19 (catalog version 2026.11.18). FIRST EPSS gives it 0.35039, the 98.5th percentile, in the 2026-11-18 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?