CVE-2018-7843 is a denial-of-service flaw in Schneider Electric Modicon M580, M340, Quantum and Premium controllers: an unauthenticated UMAS memory block read with an invalid size or offset over Modbus port 502 puts the CPU into a non-recoverable fault that stops the process and needs a power cycle. NVD, Schneider and CISA all score it 7.5. Fixes: M580 SV4.20, M340 SV3.60, Quantum v3.60, Premium v3.20.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

3.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-7843 · Source: NVD

Affected components

ComponentCPEVersion range
Schneider Electric Modicon M580 (BMEP*, BMEH*)cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:*Affected: versions prior to v2.80 (SEVD-2019-134-11 v14.0.0 affected-products table). Remediation: firmware SV4.20 or later with EcoStruxure Control Expert v16.0, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01)
Schneider Electric Modicon M340 CPU (BMXP34*)cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:*Affected: versions prior to v3.10 (SEVD-2019-134-11 v14.0.0). Remediation: firmware SV3.60 or later with Control Expert v16.0 or later, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01)
Schneider Electric Modicon Quantum (140CPU65150, 140CPU65160, 140CPU65260, 140CPU65860, 140CPU67060, 140CPU67160, 140CPU67260, 140CPU67261, 140CPU67861)cpe:2.3:o:schneider-electric:modicon_quantum_firmware:*:*:*:*:*:*:*:*Versions prior to v3.60; fixed in v3.60 (SEVD-2019-134-11, ICSA-25-114-01). End of life as of 2026-11-19
Schneider Electric Modicon Premium (TSXP57*, TSXH57*)cpe:2.3:o:schneider-electric:modicon_premium_firmware:*:*:*:*:*:*:*:*Versions prior to v3.20; fixed in v3.20, available through Schneider customer support (SEVD-2019-134-11, ICSA-25-114-01). End of life as of 2026-11-19

What does this mean for affected devices?

NVD carries Schneider Electric's description: a "CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service when reading memory blocks with an invalid data size or with an invalid data offset in the controller over Modbus." NVD's Primary score is CVSS v3.1 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, with CVSS v2 5.0. NVD classes the weakness as CWE-125 (out-of-bounds read), while Schneider, Talos and CISA use CWE-248. The record was published on 2019-05-22, and the CVE.org record is PUBLISHED with Schneider Electric as CNA (NVD, CVE record).

What happens on the controller?

Cisco Talos found the flaw in a Modicon M580 BMEP582040 on firmware SV2.70 and published it as TALOS-2018-0738 on 10 June 2019. The UMAS command MEMORY_BLOCK_READ (Modbus function code 0x5A, UMAS function code 0x20) takes a block ID, a data size and an offset. By setting the size or offset so that the read runs past the end of a block, an unauthenticated client on port 502 can push the CPU into a non-recoverable fault. Talos gives two proofs of concept: reading block 0x8032 or 0x8033 with a data size of at least one byte, and reading block 0x00 with an offset of at least 0x2fff. In the fault state all remote communication stops, the process logic stops executing, and the controller needs a physical power cycle. Talos notes the technique applies to almost every block ID.

How do Schneider, CISA and NVD score it?

All three agree on 7.5 with availability impact only. Schneider's notice SEVD-2019-134-11 (version 14.0.0, 8 September 2026) gives CVSS v3.1 7.5 and CVSS v4.0 8.7 (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N). CISA republished the notice as ICSA-25-114-01 with the same scores and CWE-248, and Talos scores it CVSS v3.0 7.5. The only difference is the CWE label.

Which Modicon firmware fixes it?

Controller Affected (SEVD-2019-134-11 table) Fixed version in the notice and CISA CSAF
Modicon M580 (BMEP*, BMEH*) prior to v2.80 SV4.20 with Control Expert v16.0
Modicon M340 CPU (BMXP34*) prior to v3.10 SV3.60 with Control Expert v16.0 or later
Modicon Quantum (140CPU65150 to 140CPU67861) prior to v3.60 v3.60
Modicon Premium (TSXP57*, TSXH57*) prior to v3.20 v3.20 from Schneider customer support

The notice's revision history shows the Quantum and Premium fixes for CVE-2018-7843 were added in version 3.0.0 (10 December 2019), and version 2.0.0 corrected the M340 release from 3.01 to 3.10. The M580 and M340 remediation is three steps: update Control Expert and firmware, set an application password and the new firmware version in the project, then rebuild and transfer every project. The fixed product status in CISA's CSAF file lists M580 4.20, M340 3.60, Quantum 3.60 and Premium 3.20. Quantum and Premium are end of life as of 2026-11-19; Schneider tells owners to firewall port 502/TCP, configure the Access Control List and migrate to M580.

Our UMAS protocol security guide covers UMAS function codes and detection, and the input handling fix guide covers unchecked size and offset fields. The same notice lists CVE-2018-7842 (session ID brute force), CVE-2018-7846, CVE-2018-7847 and CVE-2019-6808; unlike CVE-2018-7843, those have no fix on Quantum and Premium. The same Talos research also produced the memory over-read CVE-2018-7845 and the UMAS 0x6d crash CVE-2018-7852.

CVE-2018-7843 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.03161, the 88.2nd percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.

Evidence

  • NVD (read 2026-11-19): status Modified; published 2019-05-22; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 5.0; CWE-125 (NVD); CPE modicon_m580, m340, quantum and premium firmware without version limit; references SEVD-2019-134-11 and TALOS-2018-0738. — NVD
  • Schneider Electric SEVD-2019-134-11 v14.0.0 (published 2019-05-14, updated 2026-09-08), read 2026-11-19: CVE-2018-7843 CWE-248, CVSS v3.1 7.5, CVSS v4.0 8.7; affected M580 prior to v2.80, M340 prior to v3.10, Quantum prior to v3.60, Premium prior to v3.20; remediation M580 SV4.20, M340 SV3.60, Quantum v3.60, Premium v3.20 via customer support; Quantum and Premium end of life; revision 3.0.0 (2019-12-10) added the Premium and Quantum fix; credits Jared Rittle (Cisco Talos) and Gao Jian (nsfocus). — Schneider Electric SEVD-2019-134-11
  • CISA ICSA-25-114-01 CSAF (Update A, current release 2026-04-23), read 2026-11-19: CVE-2018-7843 CWE-248, CVSS v3.1 7.5, v4.0 8.7; known affected M580 prior to v2.80, M340 prior to v3.10, Quantum prior to v3.60, Premium prior to v3.20; fixed M580 4.20, M340 3.60, Quantum 3.60, Premium 3.20. — CISA CSAF ICSA-25-114-01
  • Cisco Talos TALOS-2018-0738 (public 2019-06-10), read 2026-11-19: denial of service in the UMAS MEMORY_BLOCK_READ function (Modbus 0x5A, UMAS 0x20) of Modicon M580 BMEP582040 SV2.70; reading blocks 0x8032/0x8033 or block 0x00 with offset at least 0x2fff causes a non-recoverable fault needing a power cycle; CVSS v3.0 7.5, CWE-248; vendor patched 2019-05-14. — Cisco Talos
  • CVE record (checked 2026-11-19): state PUBLISHED, CNA Schneider Electric, published 2019-05-22; no CNA CVSS metric; references SEVD-2019-134-11 and TALOS-2018-0738. — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-19. — CISA KEV
  • EPSS 0.03161, percentile 0.88242, dataset 2026-11-18, read 2026-11-19. — FIRST EPSS

Related advisories

Sources

  1. NVD: CVE-2018-7843
  2. CVE.org record CVE-2018-7843 (CNA: Schneider Electric)
  3. Schneider Electric Security Notification SEVD-2019-134-11: Multiple Vulnerabilities in Modicon Controller Products (v14.0.0, 8 September 2026; PDF)
  4. CISA ICS Advisory ICSA-25-114-01: Schneider Electric Modicon Controllers (Update A)
  5. CISA CSAF record for ICSA-25-114-01
  6. Cisco Talos TALOS-2018-0738: Schneider Electric Modicon M580 UMAS memory block read denial-of-service vulnerability
  7. CISA Known Exploited Vulnerabilities catalog
  8. FIRST EPSS score for CVE-2018-7843

Frequently asked questions

Which firmware fixes CVE-2018-7843?

Modicon M580 SV4.20 with EcoStruxure Control Expert v16.0, M340 SV3.60, Quantum v3.60 and Premium v3.20, which Schneider supplies through customer support. On M580 and M340, also set an application password and rebuild and transfer every project (per Schneider SEVD-2019-134-11 and CISA ICSA-25-114-01).

How do I protect a controller I cannot update?

Set up network segmentation and a firewall that blocks all unauthorized access to port 502/TCP, and configure the controller's Access Control List. For M580 and M340, Schneider also lists an application password, IPsec through a BMENOC or BMENUA0100 module, or an external VPN firewall. Quantum and Premium are end of life and Schneider advises migrating to M580 (per Schneider SEVD-2019-134-11).

What does an attacker need, and what is the impact?

Network access to Modbus port 502 and no credentials. A UMAS MEMORY_BLOCK_READ request with an oversized length or offset puts the CPU into a non-recoverable fault: remote communication and process logic stop until the controller is power cycled (per Cisco Talos TALOS-2018-0738).

Why does NVD list CWE-125 when Schneider lists CWE-248?

NVD classes the root cause as an out-of-bounds read, the read past the end of a memory block, while Schneider, CISA and Talos label the result, an uncaught exception that faults the CPU. The CVSS score is 7.5 in all of them (per NVD, Schneider SEVD-2019-134-11 and CISA ICSA-25-114-01).

Is CVE-2018-7843 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18). Talos published proof-of-concept code in 2019, and FIRST EPSS gives it 0.03161, the 88.2nd percentile, in the 2026-11-18 dataset (per CISA KEV, Cisco Talos and FIRST EPSS).