Security Advisory

CVE-2019-6807: Modicon UMAS System Bits Write DoS

Last updated:
  • CVE-2019-6807

CVE-2019-6807 is a denial-of-service flaw in Schneider Electric Modicon controllers: two unauthenticated UMAS write-system-bits commands over Modbus port 502 put the CPU into a non-recoverable fault that stops the process until a power cycle. NVD, Schneider and CISA all score it 7.5. Fixes include M580 SV4.20, M340 SV3.60, Quantum v3.60, Premium v3.20 and MC80 v1.80.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

2.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-6807 · Source: NVD

Affected components

ComponentCPEVersion range
Schneider Electric Modicon M580 (BMEP*, BMEH*)cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:*Affected: versions prior to v2.90 (SEVD-2019-134-11 v14.0.0, NVD CPE). Remediation: firmware SV4.20 or later with EcoStruxure Control Expert v16.0, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01)
Schneider Electric Modicon M340 CPU (BMXP34*)cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:*Affected: versions prior to v3.10 (SEVD-2019-134-11, NVD CPE). Remediation: firmware SV3.60 or later with Control Expert v16.0 or later (SEVD-2019-134-11, ICSA-25-114-01)
Schneider Electric Modicon MC80 (BMKC8020301)—Versions prior to v1.80; fixed in v1.80 with Control Expert v16.0 or later (SEVD-2019-134-11 v7.0.0 onward, ICSA-25-114-01); not in NVD's CPE configuration
Schneider Electric Modicon Momentum Unity M1E Processor (171CBU*)—Affected-products table: prior to sv2.6; remediation: firmware sv2.90 with Control Expert v16.2 HF003 (SEVD-2019-134-11, ICSA-25-114-01); not in NVD's CPE configuration
Schneider Electric Modicon Quantum (140CPU65150, 140CPU65160, 140CPU65260, 140CPU65860, 140CPU67060, 140CPU67160, 140CPU67260, 140CPU67261, 140CPU67861)cpe:2.3:o:schneider-electric:modicon_quantum_firmware:*:*:*:*:*:*:*:*Versions prior to v3.60; fixed in v3.60 (SEVD-2019-134-11, ICSA-25-114-01). End of life as of 2026-11-20
Schneider Electric Modicon Premium (TSXP57*, TSXH57*)cpe:2.3:o:schneider-electric:modicon_premium_firmware:*:*:*:*:*:*:*:*Versions prior to v3.20; fixed in v3.20 through Schneider customer support (SEVD-2019-134-11, ICSA-25-114-01). End of life as of 2026-11-20
PLC Simulator in Schneider Electric EcoStruxure Control Expert—Versions prior to v15.1; fixed in Control Expert v15.1 (SEVD-2019-134-11, ICSA-25-114-01)

What does this mean for affected devices?

NVD carries Schneider Electric's description: a "CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a possible denial of service when writing sensitive application variables to the controller over Modbus." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), with CVSS v2 5.0. NVD classes the weakness as CWE-755 (improper handling of exceptional conditions); Schneider, CISA and Talos use CWE-248. The record was published on 2019-05-22 and is PUBLISHED on CVE.org (NVD, CVE record).

What does the attack look like on the wire?

Cisco Talos reported it as TALOS-2019-0770, public on 10 June 2019, against a Modicon M580 BMEP582040 on firmware SV2.70. Two UMAS "write system bits and blocks" commands (Modbus function code 0x5A, UMAS function code 0x23), each followed by a "read PLC info" request, put the CPU into a non-recoverable fault. No authentication is needed. In that state all remote communication stops, process logic stops executing, and the controller needs a physical power cycle. Talos scores it CVSS v3.0 7.5, CWE-248.

Which Modicon products and firmware are affected?

Product Affected (SEVD-2019-134-11 v14.0.0) Fix in the notice and CISA CSAF
Modicon M580 (BMEP*, BMEH*) prior to v2.90 SV4.20 with Control Expert v16.0
Modicon M340 CPU (BMXP34*) prior to v3.10 SV3.60 with Control Expert v16.0 or later
Modicon MC80 (BMKC8020301) prior to v1.80 v1.80 with Control Expert v16.0 or later
Modicon Momentum Unity M1E (171CBU*) prior to sv2.6 (table); remediation section names sv2.90 sv2.90 with Control Expert v16.2 HF003
Modicon Quantum (140CPU65150 to 140CPU67861) prior to v3.60 v3.60
Modicon Premium (TSXP57*, TSXH57*) prior to v3.20 v3.20 from Schneider customer support
PLC Simulator in EcoStruxure Control Expert prior to v15.1 Control Expert v15.1

The notice's revision history shows how the scope grew: version 2.0.0 (13 August 2019) added the M340 fix, 3.0.0 (10 December 2019) the Quantum and Premium fixes, 7.0.0 (13 September 2022) added MC80 and the PLC Simulator, and 9.0.0 (14 March 2023) the Momentum fix. CISA's ICSA-25-114-01 CSAF (Update A, 23 April 2026) carries the same product status and scores CVSS v3.1 7.5 and CVSS v4.0 8.7. NVD's CPE covers M580 before 2.90, M340 before 3.10 and Quantum and Premium without a version limit, but not MC80, Momentum or the simulator.

How do you fix or mitigate it?

On M580, M340, MC80 and Momentum the SEVD-2019-134-11 remediation has three steps: update Control Expert and the controller firmware, set an application password and the new firmware version in each project, then rebuild and transfer every project. For the PLC Simulator, Schneider notes that Modbus network connections are off by default and that the default panel option keeps the simulator local. If you cannot update, SEVD-2019-134-11 lists the same mitigations for every Modicon family: set an application password in the project properties, segment the network and firewall all unauthorized access to port 502/TCP, and configure the controller's Access Control List. For M580 it adds IPsec through a BMENOC or BMENUA0100 module and CPU memory protection tied to a physical input (not available on Hot Standby CPUs); for M580 and M340 it also suggests an external VPN firewall such as the Belden EAGLE40-07. Quantum and Premium are end of life as of 2026-11-20; Schneider advises migrating to M580.

Our UMAS protocol security guide covers UMAS function codes and how to spot them on the wire, and the Modbus protocol security guide covers port 502 exposure. For other UMAS crashes from the same Talos research see CVE-2018-7856, CVE-2019-6809, CVE-2018-7843 and CVE-2018-7852; CVE-2019-6808 in the same notice has no fix on Quantum and Premium.

CVE-2019-6807 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.02236, the 83.2nd percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-20): status Modified; published 2019-05-22; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 5.0; CWE-755 (NVD); CPE modicon_m580_firmware before 2.90, modicon_m340_firmware before 3.10, modicon_quantum_firmware and modicon_premium_firmware without version limit; references SEVD-2019-134-11 and TALOS-2019-0770. — NVD
  • CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider Electric, published 2019-05-22; no CNA CVSS metric; references SEVD-2019-134-11 and TALOS-2019-0770. — CVE.org
  • Schneider Electric SEVD-2019-134-11 v14.0.0 (published 2019-05-14, updated 2026-09-08), read 2026-11-20: CVE-2019-6807 CWE-248, CVSS v3.1 7.5, CVSS v4.0 8.7; affected M580 prior to v2.90, M340 prior to v3.10, MC80 prior to v1.80, Momentum M1E prior to sv2.6, Quantum prior to v3.60, Premium prior to v3.20, PLC Simulator prior to v15.1; remediation M580 SV4.20, M340 SV3.60, Momentum sv2.90, Quantum v3.60, Premium v3.20, Control Expert v15.1; revisions 2.0.0, 3.0.0, 7.0.0, 9.0.0 as described; credits Jared Rittle (Cisco Talos) and Gao Jian (nsfocus). — Schneider Electric SEVD-2019-134-11
  • CISA ICSA-25-114-01 CSAF (Update A, current release 2026-04-23), read 2026-11-20: CVE-2019-6807 CWE-248, CVSS v3.1 7.5, v4.0 8.7; known affected and fixed products as in SEVD-2019-134-11, including MC80 v1.80 and Momentum firmware 2.90 fixed; PLC Simulator mitigation (local-only default panel, Modbus disabled by default). — CISA CSAF ICSA-25-114-01
  • Cisco Talos TALOS-2019-0770 (public 2019-06-10), read 2026-11-20: UMAS write system bits and blocks (Modbus 0x5A, UMAS 0x23) denial of service on Modicon M580 BMEP582040 SV2.70; two commands each followed by read PLC info cause a non-recoverable fault needing a power cycle; unauthenticated; CVSS v3.0 7.5, CWE-248. — Cisco Talos
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
  • EPSS 0.02236, percentile 0.83175, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories

Sources

  1. NVD: CVE-2019-6807
  2. CVE.org record CVE-2019-6807 (CNA: Schneider Electric)
  3. Schneider Electric Security Notification SEVD-2019-134-11: Multiple Vulnerabilities in Modicon Controller Products (v14.0.0, 8 September 2026; PDF)
  4. CISA ICS Advisory ICSA-25-114-01: Schneider Electric Modicon Controllers (Update A)
  5. CISA CSAF record for ICSA-25-114-01
  6. Cisco Talos TALOS-2019-0770: Schneider Electric Modicon M580 UMAS write system bits and blocks denial-of-service vulnerability
  7. CISA Known Exploited Vulnerabilities catalog
  8. FIRST EPSS score for CVE-2019-6807

Frequently asked questions

Which firmware fixes CVE-2019-6807?

Modicon M580 SV4.20, M340 SV3.60, MC80 v1.80, Momentum Unity M1E sv2.90, Quantum v3.60 and Premium v3.20 (from Schneider customer support), plus EcoStruxure Control Expert v15.1 for the PLC Simulator (per Schneider SEVD-2019-134-11 and CISA ICSA-25-114-01).

What does an attacker need, and what happens?

Network access to Modbus port 502 and no credentials. Two UMAS write system bits and blocks commands, each followed by a read PLC info request, fault the CPU: remote communication and process logic stop until a power cycle (per Cisco Talos TALOS-2019-0770).

Will an NVD CPE match find my MC80 or Momentum controller?

No. As of 2026-11-20 NVD's CPE covers only M580, M340, Quantum and Premium. Schneider added MC80 and the PLC Simulator in notice version 7.0.0 (September 2022) and a Momentum fix in 9.0.0 (March 2023) (per NVD and SEVD-2019-134-11).

How do I protect a Quantum or Premium I cannot update?

Firewall all unauthorized access to port 502/TCP, configure the Access Control List and set an application password. Both families are end of life and Schneider advises migrating to M580 (per Schneider SEVD-2019-134-11).