Security Advisory

CVE-2018-7856: Modicon UMAS Memory Write DoS

Last updated:
  • CVE-2018-7856

CVE-2018-7856 is a denial-of-service flaw in Schneider Electric Modicon M580, M340, Quantum and Premium controllers: an unauthenticated UMAS memory block write with large offset and size values over Modbus port 502 puts the CPU into a non-recoverable fault that needs a power cycle. NVD, Schneider and CISA all score it 7.5. Fixes are M580 SV4.20, M340 SV3.60, Quantum v3.60 and Premium v3.20.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-7856 · Source: NVD

Affected components

ComponentCPEVersion range
Schneider Electric Modicon M580 (BMEP*, BMEH*)cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:*Affected: versions prior to v2.80 (SEVD-2019-134-11 v14.0.0, ICSA-25-114-01; NVD CPE says before 2.90). Remediation: firmware SV4.20 or later with EcoStruxure Control Expert v16.0, application password, rebuild and transfer
Schneider Electric Modicon M340 CPU (BMXP34*)cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:*Affected: versions prior to v3.10 (SEVD-2019-134-11, NVD CPE). Remediation: firmware SV3.60 or later with Control Expert v16.0 or later (SEVD-2019-134-11, ICSA-25-114-01)
Schneider Electric Modicon Quantum (140CPU65150, 140CPU65160, 140CPU65260, 140CPU65860, 140CPU67060, 140CPU67160, 140CPU67260, 140CPU67261, 140CPU67861)cpe:2.3:o:schneider-electric:modicon_quantum_firmware:-:*:*:*:*:*:*:*Versions prior to v3.60; fixed in v3.60 (SEVD-2019-134-11, ICSA-25-114-01); NVD CPE has no version. End of life as of 2026-11-20
Schneider Electric Modicon Premium (TSXP57*, TSXH57*)cpe:2.3:o:schneider-electric:modicon_premium_firmware:-:*:*:*:*:*:*:*Versions prior to v3.20; fixed in v3.20 through Schneider customer support (SEVD-2019-134-11, ICSA-25-114-01); NVD CPE has no version. End of life as of 2026-11-20

What does this mean for affected devices?

NVD carries Schneider Electric's description: a "CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a possible denial of Service when writing invalid memory blocks to the controller over Modbus." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), with CVSS v2 5.0. NVD classes the weakness as CWE-754 (improper check for unusual or exceptional conditions); Schneider, CISA and Talos use CWE-248. The record was published on 2019-05-22 and is PUBLISHED on CVE.org (NVD, CVE record).

What does the attack look like on the wire?

Cisco Talos reported it as TALOS-2019-0767, public on 10 June 2019, against a Modicon M580 BMEP582040 on firmware SV2.70. A UMAS memory block write (Modbus function code 0x5A, UMAS function code 0x21) to one of the blocks 0x10, 0x15, 0x2a, 0x2b, 0x2e, 0x2f, 0x32, 0x33, 0x40 or 0x42, with large offset and size values, puts the CPU into a non-recoverable fault. No authentication is needed. In that state all remote communication stops, process logic stops executing, and the controller needs a physical power cycle. Talos scores it CVSS v3.0 7.5, CWE-248.

Which Modicon firmware is affected, and what fixes it?

Controller Affected (SEVD-2019-134-11 v14.0.0, CISA CSAF) Fix
Modicon M580 (BMEP*, BMEH*) prior to v2.80 SV4.20 with Control Expert v16.0
Modicon M340 CPU (BMXP34*) prior to v3.10 SV3.60 with Control Expert v16.0 or later
Modicon Quantum (140CPU65150 to 140CPU67861) prior to v3.60 v3.60
Modicon Premium (TSXP57*, TSXH57*) prior to v3.20 v3.20 from Schneider customer support

The notice's revision history shows the M340 fix arrived in v3.10 "earlier than expected" (version 2.0.0, 13 August 2019) and the Quantum and Premium fixes in version 3.0.0 (10 December 2019). CISA's ICSA-25-114-01 CSAF (Update A, 23 April 2026) lists the same ranges and scores CVSS v3.1 7.5 and CVSS v4.0 8.7. NVD's CPE differs in two places: it puts the M580 bound at versions before 2.90 rather than 2.80, and it lists Quantum and Premium firmware with no version, so a CPE match will not tell you whether a Quantum on v3.60 or a Premium on v3.20 is fixed.

How do you fix or mitigate it?

On M580 and M340 the SEVD-2019-134-11 remediation has three steps: update EcoStruxure Control Expert and the controller firmware, set an application password and the new firmware version in each project, then rebuild and transfer every project. If you cannot update, SEVD-2019-134-11 lists the same mitigations for every Modicon family: set an application password in the project properties, segment the network and firewall all unauthorized access to port 502/TCP, and configure the controller's Access Control List. For M580 it adds IPsec through a BMENOC or BMENUA0100 module and CPU memory protection tied to a physical input (not available on Hot Standby CPUs); for M580 and M340 it also suggests an external VPN firewall such as the Belden EAGLE40-07. Quantum and Premium are end of life as of 2026-11-20; Schneider advises migrating to M580.

Our UMAS protocol security guide covers UMAS function codes and how to spot them on the wire, and the Modbus protocol security guide covers port 502 exposure. The same Talos research produced the UMAS crashes CVE-2019-6807, CVE-2018-7843 and CVE-2018-7852 and the memory over-read CVE-2018-7845; CVE-2019-6809 and CVE-2019-6808 are in the same notice.

CVE-2018-7856 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.01582, the 76.1st percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-20): status Modified; published 2019-05-22; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 5.0; CWE-754 (NVD); CPE modicon_m580_firmware before 2.90, modicon_m340_firmware before 3.10, modicon_quantum_firmware and modicon_premium_firmware version '-'; references SEVD-2019-134-11 and TALOS-2019-0767. — NVD
  • CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider Electric, published 2019-05-22; no CNA CVSS metric; references SEVD-2019-134-11 and TALOS-2019-0767. — CVE.org
  • Schneider Electric SEVD-2019-134-11 v14.0.0 (updated 2026-09-08), read 2026-11-20: CVE-2018-7856 CWE-248, CVSS v3.1 7.5, v4.0 8.7, denial of service when writing invalid memory blocks over Modbus; affected M580 prior to v2.80, M340 prior to v3.10, Quantum prior to v3.60, Premium prior to v3.20; remediation M580 SV4.20, M340 SV3.60, Quantum v3.60, Premium v3.20; v2.0.0 added the M340 v3.10 fix (earlier than expected), v3.0.0 the Quantum and Premium fix; credits Jared Rittle (Cisco Talos) and Gao Jian (nsfocus). — Schneider Electric SEVD-2019-134-11
  • CISA ICSA-25-114-01 CSAF (Update A, current release 2026-04-23), read 2026-11-20: CVE-2018-7856 CWE-248, CVSS v3.1 7.5, v4.0 8.7; known affected M580 prior to v2.80, M340 prior to v3.10, Quantum prior to v3.60, Premium prior to v3.20; fixed M580 4.20, M340 3.60, Quantum 3.60, Premium 3.20. — CISA CSAF ICSA-25-114-01
  • Cisco Talos TALOS-2019-0767 (public 2019-06-10), read 2026-11-20: UMAS memory block write (Modbus 0x5A, UMAS 0x21) denial of service on Modicon M580 BMEP582040 SV2.70; affected blocks 0x10, 0x15, 0x2a, 0x2b, 0x2e, 0x2f, 0x32, 0x33, 0x40, 0x42 with large offset and size; non-recoverable fault needing a power cycle; unauthenticated; CVSS v3.0 7.5, CWE-248. — Cisco Talos
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
  • EPSS 0.01582, percentile 0.76061, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories

Sources

  1. NVD: CVE-2018-7856
  2. CVE.org record CVE-2018-7856 (CNA: Schneider Electric)
  3. Schneider Electric Security Notification SEVD-2019-134-11: Multiple Vulnerabilities in Modicon Controller Products (v14.0.0, 8 September 2026; PDF)
  4. CISA ICS Advisory ICSA-25-114-01: Schneider Electric Modicon Controllers (Update A)
  5. CISA CSAF record for ICSA-25-114-01
  6. Cisco Talos TALOS-2019-0767: Schneider Electric Modicon M580 UMAS memory block write denial-of-service vulnerability
  7. CISA Known Exploited Vulnerabilities catalog
  8. FIRST EPSS score for CVE-2018-7856

Frequently asked questions

Which firmware fixes CVE-2018-7856?

Modicon M580 SV4.20 with EcoStruxure Control Expert v16.0, M340 SV3.60, Quantum v3.60 and Premium v3.20, which Schneider supplies through customer support. On M580 and M340, also set an application password and rebuild and transfer every project (per Schneider SEVD-2019-134-11 and CISA ICSA-25-114-01).

What does an attacker need, and what is the impact?

Network access to Modbus port 502 and no credentials. A UMAS memory block write to one of ten known block numbers with large offset and size values faults the CPU: remote communication and process logic stop until a power cycle (per Cisco Talos TALOS-2019-0767).

Why does NVD's M580 range differ from Schneider's?

NVD's CPE marks M580 firmware before 2.90 as affected, while Schneider's notice and the CISA CSAF list versions prior to v2.80 for this CVE. Either way, Schneider's remediation for M580 is SV4.20 (per NVD, SEVD-2019-134-11 and ICSA-25-114-01).

How do I protect a Quantum or Premium I cannot update?

Firewall all unauthorized access to port 502/TCP, configure the Access Control List and set an application password. Both families are end of life and Schneider advises migrating to M580 (per Schneider SEVD-2019-134-11).