CVE-2019-6828 is an uncaught-exception flaw in Schneider Electric Modicon controllers: reading specific coils and registers over Modbus can stop the PLC, a denial of service. NVD and Schneider both score it 7.5. Schneider fixed it in M580 V2.90, M340 V3.10, Quantum V3.60 and Premium V3.20; Quantum and Premium are end of life.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
1.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-6828 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Modicon M580 CPU (BMEP*, BMEH*) | cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:* | Before V2.90 (SEVD-2019-134-11; NVD CPE excludes 2.90). The current remediation in the notice is SV4.20 with Control Expert V16.0 |
| Schneider Electric Modicon M340 CPU (BMXP34*) | cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:* | Before V3.10 (SEVD-2019-134-11; NVD CPE excludes 3.10). The current remediation in the notice is SV3.60 with Control Expert V16.0 |
| Schneider Electric Modicon Quantum (140CPU65150/65160, 65260, 65860, 67060, 67160, 67260, 67261, 67861) | cpe:2.3:o:schneider-electric:modicon_quantum_firmware:*:*:*:*:*:*:*:* | Before V3.60; fixed in V3.60 (SEVD-2019-134-11, CISA ICSA-25-114-01). NVD CPE has no version limit |
| Schneider Electric Modicon Premium (TSXP57*, TSXH57*) | cpe:2.3:o:schneider-electric:modicon_premium_firmware:*:*:*:*:*:*:*:* | Before V3.20; V3.20 from Schneider customer support (SEVD-2019-134-11). NVD CPE has no version limit |
What does this mean for affected devices?
NVD carries the Schneider Electric description: "A CWE-248: Uncaught Exception vulnerability exists Modicon M580 (firmware version prior to V2.90), Modicon M340 (firmware version prior to V3.10), Modicon Premium (all versions), and Modicon Quantum (all versions), which could cause a possible denial of service when reading specific coils and registers in the controller over Modbus." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), the same as Schneider's, and NVD classes the weakness as CWE-755 (improper handling of exceptional conditions) where Schneider uses CWE-248. The record was published on 2019-09-17 (NVD, CVE record).
Which Modicon controllers and firmware are affected?
| Controller (Schneider wording) | Affected | Fixed |
|---|---|---|
| Modicon M580 (BMEP*, BMEH*) | before V2.90 | V2.90; the notice now points to SV4.20 |
| Modicon M340 (BMXP34*) | before V3.10 | V3.10; the notice now points to SV3.60 |
| Modicon Quantum (140CPU65150/65160, 65260, 65860, 67060, 67160, 67260, 67261, 67861) | before V3.60 | V3.60 |
| Modicon Premium (TSXP57*, TSXH57*) | before V3.20 | V3.20, from customer support |
Schneider added CVE-2019-6828 to SEVD-2019-134-11 in version 2.0.0 (13 August 2019) and added the Quantum and Premium fixes in version 3.0.0 (10 December 2019). The current version 14.0.0 (8 September 2026) keeps those rows. CISA's ICSA-25-114-01 CSAF (Update A, 2026-04-23) lists the same affected ranges and marks Quantum V3.60 and Premium V3.20 as fixed. NVD's CPE configuration still marks every Quantum and Premium firmware version as vulnerable, so a scanner that matches on CPE alone can flag a patched Quantum or Premium CPU.
How would an attacker trigger it?
The attacker needs to reach the controller's Modbus service, normally 502/tcp. Both scores assume network access with no privileges and no user interaction. Schneider describes the trigger only as reading specific coils and registers in the controller, so a firewall rule that allows any Modbus client through to the PLC does not stop it. The impact is availability only: Schneider's notice warns of a possible loss of availability of the controller.
How do you fix or mitigate it?
Version 5.0.0 of the notice (12 October 2020) added remediation steps for M580 and M340 that apply to this CVE, and the current notice spells them out in three steps: update Control Expert (V16.0 or later) and the controller firmware (M580 SV4.20 or later, M340 SV3.60 or later); set an application password and the new firmware version in the project; then rebuild all projects and transfer them to the controllers. Where you cannot update, Schneider lists blocking unauthorized access to 502/tcp with segmentation and a firewall, configuring the controller's Access Control List, IPsec through a BMENOC module or a VPN to the engineering workstation, and, on the M580, CPU memory protection bound to a physical input. Quantum and Premium have reached end of life; Schneider recommends migrating them to the M580.
Our Modicon UMAS protocol guide covers the controller families and their notices, and the Modbus protocol security guide covers filtering 502/tcp. The same notice lists the denial-of-service flaws CVE-2019-6807, CVE-2019-6809 and CVE-2018-7843; CVE-2021-22779 is a later Modbus authentication bypass on the same controllers.
CVE-2019-6828 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.01526, the 75.2nd percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-20): status Modified; published 2019-09-17; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 7.8; CWE-755 (NVD), CWE-248 (Schneider); CPE: M580 firmware before 2.90, M340 firmware before 3.10, Premium and Quantum firmware with no version limit; reference SEVD-2019-134-11. — NVD
- Schneider SEVD-2019-134-11 v14.0.0 (published 2019-05-14, updated 2026-09-08), read 2026-11-20: CVE-2019-6828 CVSS v3.1 7.5, CVSS v4.0 8.7, CWE-248, denial of service when reading specific coils and registers over Modbus; affected M580 before v2.90, M340 before v3.10, Quantum before v3.60, Premium before v3.20; CVE added in v2.0.0 (2019-08-13), Premium and Quantum fix in v3.0.0 (2019-12-10), M580/M340 remediation steps in v5.0.0 (2020-10-12); current remediation M580 SV4.20 and M340 SV3.60 with Control Expert V16.0, application password, rebuild and transfer; mitigations: firewall 502/tcp, ACL, IPsec/VPN, M580 memory protection; Quantum and Premium end of life, migrate to M580. — Schneider Electric SEVD-2019-134-11
- CISA ICSA-25-114-01 CSAF (Update A, current release 2026-04-23), read 2026-11-20: CVE-2019-6828 CWE-248, CVSS v3 7.5; known affected M580 before v2.90, M340 before v3.10, listed Quantum CPUs before v3.60, Premium before v3.20; fixed M580 4.20, M340 3.60, Quantum 3.60, Premium 3.20. — CISA CSAF ICSA-25-114-01
- CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider Electric, published 2019-09-17; CNA CWE-248; affected M580 before V2.90, M340 before V3.10, Premium and Quantum all versions. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries, released 2026-11-18), checked 2026-11-20. — CISA KEV
- EPSS 0.01526, percentile 0.7523, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2019-6828?
Modicon M580 V2.90, M340 V3.10, Quantum V3.60 and Premium V3.20 (Premium via Schneider customer support). The current SEVD-2019-134-11 points M580 users to SV4.20 and M340 users to SV3.60 with Control Expert V16.0, an application password and a rebuilt project.
Why does my scanner still flag a Quantum on V3.60?
NVD's CPE configuration for CVE-2019-6828 marks every Modicon Quantum and Premium firmware version as vulnerable. Schneider's notice and the CISA ICSA-25-114-01 CSAF list Quantum V3.60 and Premium V3.20 as fixed, so check the installed firmware version against the vendor notice.
Does an attacker need credentials?
No. Both NVD and Schneider score it with no privileges and no user interaction over the network. The attacker only needs to reach the Modbus service of the controller, normally 502/tcp, and read specific coils and registers.
What can I do on an end-of-life Premium or Quantum?
Install the fixed firmware if you can, block unauthorized access to 502/tcp with segmentation and a firewall, and configure the Access Control List as described in the controller manual. Schneider recommends migrating both families to the Modicon M580.
Questions about this page?