CVE-2019-6808 is an improper access control flaw in Schneider Electric Modicon M580, M340, Quantum and Premium controllers that lets an unauthenticated attacker overwrite configuration over Modbus and run code. NVD scores it 9.8, Schneider 10.0. Schneider names M580 SV4.20 and M340 SV3.60 with Control Expert v16.0 as the remediation; Quantum and Premium get no fix as of 2026-11-19.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
8.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-6808 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Modicon M580 (BMEP*, BMEH*, excluding M580 CPU Safety) | cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v2.90 (SEVD-2019-134-11 v14.0.0 affected-products table). Remediation: firmware SV4.20 or later with EcoStruxure Control Expert v16.0, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon M340 CPU (BMXP34*) | cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v3.10 (SEVD-2019-134-11 v14.0.0). Remediation: firmware SV3.60 or later with Control Expert v16.0 or later, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon Quantum and Quantum Safety | cpe:2.3:o:schneider-electric:modicon_quantum_firmware:*:*:*:*:*:*:*:* | All versions; end of life, no fix; mitigate with port 502/TCP firewalling and the Access Control List, migrate to M580 (SEVD-2019-134-11, ICSA-25-114-01). NVD's CPE configuration lists Quantum firmware up to and including 3.60 |
| Schneider Electric Modicon Premium (TSXP57*, TSXH57*) | cpe:2.3:o:schneider-electric:modicon_premium_firmware:*:*:*:*:*:*:*:* | All versions; end of life, no fix; mitigate with port 502/TCP firewalling and the Access Control List, migrate to M580 (SEVD-2019-134-11, ICSA-25-114-01). NVD's CPE configuration lists Premium firmware up to and including 3.20 |
What does this mean for affected devices?
NVD carries Schneider Electric's description: "A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a remote code execution by overwriting configuration settings of the controller over Modbus." NVD's Primary score is CVSS v3.1 9.8 (critical), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CWE-306 (missing authentication for critical function); its CVSS v2 score is 7.5. The CVE.org record is PUBLISHED with Schneider Electric as CNA (NVD, CVE record).
How do Schneider and NVD score it?
Schneider's notice SEVD-2019-134-11 (version 14.0.0, 8 September 2026) scores it CVSS v3.1 10.0, vector AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H, and CVSS v4.0 10.0, with CWE-284. The changed scope is the difference from NVD's 9.8. CISA's republication ICSA-25-114-01 uses Schneider's 10.0 and CWE-284.
What did the researchers show?
Cisco Talos published the finding as TALOS-2019-0771 on 10 June 2019. Talos tested the PLC simulator in Unity Pro L V13.0 and EcoStruxure Control Expert V14.0, which opens port 502 on all interfaces when simulation starts. A sequence of six UMAS commands (take reservation, initialize upload, upload blocks, function code 0x6D, end upload, release reservation) programs a new strategy without authentication. Talos replaced the strategy logic with shellcode, recalculated the integrity checks, and gained code execution when the simulator was switched to start mode. Talos scores it 10.0. Schneider's notice assigns the CVE to the M580, M340, Quantum and Premium controllers; its PLC Simulator column is empty for this CVE.
Which firmware fixes it?
The affected table lists M580 versions prior to v2.90, M340 prior to v3.10, and all versions of Quantum, Quantum Safety and Premium. The remediation section, and the fixed product status in CISA's CSAF file, name M580 firmware SV4.20 and M340 SV3.60 with Control Expert v16.0, followed by setting an application password, rebuilding and transferring each project. NVD's CPE configuration bounds Quantum at 3.60 and Premium at 3.20, but Schneider lists every Quantum and Premium version as affected with no fix as of 2026-11-19. For those, Schneider advises blocking port 502/TCP, configuring the Access Control List and migrating to M580. On M580, it also advises memory protection tied to a physical input.
Our UMAS protocol security guide walks through the program-transfer sequence and how to spot it on the network. The same notice covers CVE-2018-7842 and CVE-2018-7846; the earlier Modicon Modbus replay finding is CVE-2017-6034. The authentication bypass fix guide covers the missing-authentication pattern.
CVE-2019-6808 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.08161, the 95.0th percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: CWE-284 improper access control in all versions of M580, M340, Quantum and Premium, remote code execution by overwriting configuration over Modbus; NVD Primary CVSS v3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, v2 7.5; NVD Primary CWE-306; CPE: M580 before 2.90, M340 before 3.10, Quantum up to 3.60, Premium up to 3.20; published 2019-05-22. Read 2026-11-19 (NVD API data fetched 2026-11-19). — NVD
- CVE.org record state PUBLISHED, CNA Schneider Electric (schneider), published 2019-05-22; references SEVD-2019-134-11 and TALOS-2019-0771; no CNA CVSS metric in the record. Checked 2026-11-19. — CVE.org
- SEVD-2019-134-11 v14.0.0 (8 September 2026): CVSS v3.1 10.0 AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H, CVSS v4.0 10.0, CWE-284; affected M580 prior to v2.90, M340 prior to v3.10, Quantum, Quantum Safety and Premium all versions, PLC Simulator column empty; remediation M580 SV4.20 and M340 SV3.60 with Control Expert v16.0, application password, rebuild and transfer; Quantum/Premium end of life, firewall port 502 and Access Control List; M580 memory protection via physical input; revision 1.2.0 (12 July 2019) updated mitigations for this CVE. Read 2026-11-19. — Schneider Electric SEVD-2019-134-11
- ICSA-25-114-01 (Update A) republishes SEVD-2019-134-11; for CVE-2019-6808: CVSS v3.1 10.0, CWE-284, fixed products M580 firmware 4.20 and M340 firmware 3.60, Quantum, Quantum Safety and Premium carry the CSAF remediation category for no fix. Read 2026-11-19 from the CSAF file. — CISA ICSA-25-114-01 (CSAF)
- TALOS-2019-0771 (10 June 2019): remote code execution in UMAS strategy programming of the Unity Pro PLC simulator; tested Unity Pro L V13.0 and EcoStruxure Control Expert V14.0; simulator opens 0.0.0.0:502; six-command upload sequence; shellcode in modified strategy runs when simulator enters start mode; Talos CVSS v3.0 10.0, CWE-284; vendor patched 2019-05-14. Read 2026-11-19. — Cisco Talos TALOS-2019-0771
- Not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). Checked 2026-11-19. — CISA KEV
- EPSS 0.08161, percentile 0.94965, dataset 2026-11-18. Read 2026-11-19. — FIRST EPSS

Related advisories
Sources
- NVD: CVE-2019-6808
- CVE.org record CVE-2019-6808 (CNA: Schneider Electric)
- Schneider Electric Security Notification SEVD-2019-134-11: Multiple Vulnerabilities in Modicon Controller Products (v14.0.0, 8 September 2026; PDF)
- CISA ICS Advisory ICSA-25-114-01: Schneider Electric Modicon Controllers (Update A)
- CISA CSAF record for ICSA-25-114-01
- Cisco Talos TALOS-2019-0771: Schneider Electric UnityPro PLC simulator remote code execution (CVE-2019-6808)
- CISA Known Exploited Vulnerabilities catalog
- FIRST EPSS score for CVE-2019-6808
Frequently asked questions
Which Modicon controllers are affected by CVE-2019-6808?
M580 versions prior to v2.90, M340 prior to v3.10, and all versions of Quantum, Quantum Safety and Premium; the remediation is M580 SV4.20 and M340 SV3.60 with Control Expert v16.0 (per Schneider SEVD-2019-134-11 v14.0.0).
What did Cisco Talos test for CVE-2019-6808?
Talos tested the PLC simulator in Unity Pro L V13.0 and Control Expert V14.0, which listens on port 502; a six-command UMAS sequence loaded a modified strategy whose shellcode ran when the simulator started (per Cisco Talos TALOS-2019-0771).
How do you mitigate CVE-2019-6808 where no update is possible?
Set an application password, segment the network and firewall port 502/TCP, configure the Access Control List, and on M580 run with memory protection tied to a physical input; Quantum and Premium owners should migrate to M580 (per Schneider SEVD-2019-134-11).
Why does Schneider score CVE-2019-6808 at 10.0 and NVD at 9.8?
Schneider's CVSS v3.1 vector marks the scope as changed (S:C), which raises the score to 10.0; NVD's vector keeps the scope unchanged (S:U) for 9.8 (per Schneider SEVD-2019-134-11 and NVD).
Is CVE-2019-6808 in the CISA KEV catalog?
No, not as of 2026-11-19 (catalog version 2026.11.18). FIRST EPSS gives it 0.08161, the 95.0th percentile, in the 2026-11-18 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?