Security Advisory

CVE-2018-7799: Schneider SESU DLL Hijacking

Last updated:
  • CVE-2018-7799

CVE-2018-7799 is a DLL hijacking flaw (CWE-427) in Schneider Electric Software Update (SESU), the update client bundled with many Schneider engineering tools. Before V2.2.0, an attacker who can place a specific DLL file on the workstation could run arbitrary code. NVD scores it 7.8. SESU V2.2.0 fixes it.

Vulnerability summary

CVSS base score

7.8

High severity

EPSS score (FIRST)

2.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-7799 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric Software Update (SESU)cpe:2.3:a:schneider-electric:software_update_utility:*:*:*:*:*:*:*:*All versions prior to V2.2.0; fixed in V2.2.0
AVEVA Vijeo Citect and Citect SCADA (with SESU installed)—Citect SCADA 2015, 2016 and 7.40, Vijeo Citect 2015 and 7.40 per CISA ICSA-18-331-01; upgrade SESU

What does this mean for affected devices?

Schneider's notice SEVD-2018-298-01, released on 25 October 2018 and revised to V1.2 on 11 December 2018, says "a DLL hijacking vulnerability exists which could allow an attacker to execute arbitrary code on the targeted system when placing a specific DLL file." SESU is the tool that tells users when updated Schneider software is available. It is an optional install with a long list of products, among them Unity Pro, Unity Loader, SoMachine, SoMachine Basic, SoMove, Vijeo Designer, Vijeo XD, Vijeo Citect, PowerSCADA Expert 7.40 to 8.2 and the Floating License Manager, so it can be present wherever those engineering tools are installed.

How severe is CVE-2018-7799?

NVD's Primary score is CVSS v3.0 7.8, AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H, and its Primary CVSS v2 score is 9.3, AV:N/AC:M/Au:N/C:C/I:C/A:C (NVD). Schneider and CISA also arrive at 7.8, but with a different vector, AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H: they assume a local user with low privileges instead of user interaction. NVD maps the flaw to CWE-427, uncontrolled search path element, as does CISA.

What is the fix?

Update SESU to V2.2.0. Schneider says SESU itself notifies users of the update, which can also be downloaded directly. CISA's ICSA-18-305-02 (Update A, 6 November 2018) repeats that fix. CISA's AVEVA advisory ICSA-18-331-01 of 27 November 2018 lists the same CVE for Citect SCADA 2015, 2016 and 7.40 and Vijeo Citect 2015 and 7.40, where AVEVA asks users to download and install the latest SESU. Both advisories add Schneider's general advice to keep control networks behind firewalls, never connect programming software to other networks and scan removable media.

The Schneider EcoStruxure HMI and SCADA software guide groups this with other Windows workstation flaws. Related pages are the Operator Terminal Expert DLL-loading flaw CVE-2022-41666, the Vijeo Designer privilege escalation CVE-2024-8306 and AVEVA Plant SCADA's CVE-2023-1256. The KEV and EPSS prioritization guide explains how to weigh its relatively high EPSS percentile.

Is CVE-2018-7799 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0279, the 87th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2018-11-02, status Modified; NVD Primary CVSS v3.0 7.8 AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 9.3 AV:N/AC:M/Au:N/C:C/I:C/A:C; CWE-427 (NVD Primary); CPE schneider-electric:software_update_utility versions before 2.2.0. — NVD
  • Schneider SEVD-2018-298-01 V1.2 (25 October 2018, updated 11 December 2018, PDF read 2026-11-28): SESU all versions prior to V2.2.0 affected; optional install with listed products (Unity Pro, Unity Loader, SoMachine, SoMove, Vijeo Designer, Vijeo XD, Vijeo Citect, PowerSCADA Expert v7.40-8.2, Floating License Manager and others); CVSS v3 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; remediation SESU 2.2.0 via SESU notification or direct download. — Schneider Electric
  • CISA ICSA-18-305-02 Update A CSAF (2018-11-01, updated 2018-11-06): CWE-427, CVSS v3 7.8 PR:L/UI:N, SESU all versions prior to v2.2.0, fix version 2.2.0. CISA ICSA-18-331-01 (2018-11-27): AVEVA Citect SCADA 2015, 2016, v7.40 and Vijeo Citect 2015, v7.40; upgrade to latest SESU. — CISA
  • CVE.org record (read 2026-11-28): assigner Schneider Electric, problem type 'DLL hijacking vulnerability', affected SESU all versions prior to V2.2.0; no CNA CVSS metric. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.02794, percentile 0.87170, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2018-298-01 V1.2: Schneider Electric Software Update (SESU)
  3. CISA ICSA-18-305-02: Schneider Electric Software Update (SESU) (CSAF)
  4. CISA ICSA-18-331-01: AVEVA Vijeo Citect and Citect SCADA (CSAF)
  5. CVE.org record (JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which SESU version fixes CVE-2018-7799?

Version 2.2.0. Schneider's SEVD-2018-298-01 says all SESU versions before V2.2.0 are affected; SESU notifies users of the update, and it can also be downloaded directly from Schneider.

Why do Citect SCADA advisories mention this CVE?

SESU ships alongside Vijeo Citect and Citect SCADA. CISA's ICSA-18-331-01 lists Citect SCADA 2015, 2016 and 7.40 and Vijeo Citect 2015 and 7.40, and AVEVA asks those users to install the latest SESU.

Why do NVD and Schneider use different vectors?

Both reach CVSS v3 7.8. NVD assumes no privileges but user interaction (PR:N/UI:R); Schneider and CISA assume a local user with low privileges and no interaction (PR:L/UI:N). NVD's older CVSS v2 score is 9.3.

Is CVE-2018-7799 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0279, the 87th percentile, in the 2026-11-27 dataset.