CVE-2018-7832 is an improper input validation flaw (CWE-20) in Schneider Electric's Pro-face GP-Pro EX HMI design software, version 4.08 and earlier, that could make the program launch an arbitrary executable when it starts. NVD scores it 8.8 and CISA and Schneider score it 9.0 (CVSS v3.0). Version 4.08.200 fixes it.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
2.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-7832 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Pro-face GP-Pro EX | cpe:2.3:a:schneider-electric:pro-face_gp-pro_ex:*:*:*:*:*:*:*:* | 4.08 and earlier (NVD CPE up to and including 4.08); fixed in 4.08.200 |
What does this mean for affected devices?
Schneider Electric's notice SEVD-2018-354-02, published on 20 December 2018, describes "a CWE-20 Improper Input Validation vulnerability" in Pro-face GP-Pro EX v4.08 and previous versions "which could cause the execution arbitrary executable when GP-Pro EX is launched". CISA's ICSA-19-003-01, released on 3 January 2019, adds that successful exploitation could let an attacker modify code to launch an arbitrary executable when the program starts.
How severe is CVE-2018-7832?
NVD's Primary score is CVSS v3.0 8.8, AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, with CVSS v2 6.5 (NVD). Schneider and CISA give CVSS v3.0 9.0, AV:N/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H: they assume user interaction but a changed scope, which raises the score. All three vectors require low privileges. The CVE.org record carries Schneider's description without a CVSS block. CISA lists the energy sector and worldwide deployment and says no known public exploits specifically target this flaw. Schneider credits Yu Quiang of ADLab of Venustech.
What is the fix?
Schneider produced GP-Pro EX version 4.08.200, published on the Pro-face download site, and both the notice and the CISA advisory point to it as the fix. GP-Pro EX builds screens for Pro-face HMI panels, so update every engineering workstation that runs it; the notice gives no workaround besides Schneider's general recommendations, such as keeping control networks behind firewalls and never connecting programming software to networks other than the one it is meant for.
The Schneider EcoStruxure HMI and SCADA software guide covers the Pro-face line, including the older GP-Pro EX FTP login CVE-2015-7921 and the Pro-Server EX overflow CVE-2012-3797. For patch order, the KEV and EPSS prioritization guide explains how to rank workstation flaws like this one.
Is CVE-2018-7832 exploited?
It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.02196, the 83.2nd percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): published 2018-12-24, status Modified; NVD Primary CVSS v3.0 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 6.5; CWE-20 (NVD); CPE pro-face_gp-pro_ex up to and including 4.08. — NVD
- CISA ICSA-19-003-01 CSAF (read 2026-11-28): released 2019-01-03; CVE-2018-7832 CWE-20 CVSS v3.0 9.0 AV:N/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H; affected GP-Pro EX 4.08 and prior; fix 4.08.200; energy sector, worldwide; no known public exploits specifically target it. — CISA ICSA-19-003-01
- Schneider SEVD-2018-354-02 (20 December 2018, read 2026-11-28): GP-Pro EX v4.08 and previous; CVSS v3.0 9.0; fix in V4.08.200; credited to Yu Quiang (ADLab of Venustech); general security recommendations. — Schneider Electric
- CVE.org record (read 2026-11-28): assigner Schneider Electric, problem type Improper Input Validation, product GP-Pro EX v4.08 and previous versions, no CVSS metric in the CNA container. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.02196, percentile 0.83217, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which GP-Pro EX version fixes CVE-2018-7832?
Version 4.08.200, per Schneider SEVD-2018-354-02 and CISA ICSA-19-003-01. GP-Pro EX 4.08 and all earlier versions are affected.
Why is the CISA score higher than NVD's?
CISA and Schneider use CVSS v3.0 9.0 with user interaction required and a changed scope. NVD's CVSS v3.0 8.8 vector has no user interaction and an unchanged scope. Both require low privileges over the network.
Who reported CVE-2018-7832?
Schneider credits Yu Quiang of ADLab of Venustech. CISA's advisory, released 3 January 2019, notes that no known public exploits specifically target the vulnerability.
Is CVE-2018-7832 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.02196, the 83.2nd percentile, in the 2026-11-27 dataset.
Questions about this page?