CVE-2024-8306 is an improper privilege management flaw (CWE-269) in Schneider Electric Vijeo Designer, the configuration software for Harmony and Magelis HMI panels. A non-admin user on the workstation could tamper with Vijeo Designer binaries to gain higher privileges. NVD and Schneider score it 7.8. Vijeo Designer V6.3 SP1 and Machine Expert v2.3 fix it.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
0.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2024-8306 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Vijeo Designer | cpe:2.3:a:schneider-electric:vijeo_designer:*:*:*:*:*:*:*:* | Versions prior to V6.3 SP1; fixed in V6.3 SP1 (via SESU) |
| Schneider Electric EcoStruxure Machine Expert with the Vijeo Designer optional component | cpe:2.3:a:schneider-electric:vijeo_designer_embedded_in_ecostruxure_machine_expert:*:*:*:*:*:*:*:* | Versions prior to v2.3; fixed in Machine Expert v2.3 (Vijeo Designer 6.3.2.16) |
What does this mean for affected devices?
Schneider's notice SEVD-2024-254-01, first published on 10 September 2024 and revised to v2.0.0 on 8 July 2025, says the flaw "could cause unauthorized access, loss of confidentiality, integrity and availability of the workstation when non-admin authenticated user tries to perform privilege escalation by tampering with the binaries." Vijeo Designer builds the projects that run on Harmony and Magelis HMI panels, and it also ships as an optional component of EcoStruxure Machine Expert. Schneider credits Charit Misra of Applied Risk (DNV Cyber). CISA republished the notice as ICSA-25-014-02, now at Update A.
How severe is CVE-2024-8306?
NVD's Primary score is CVSS v3.1 7.8, AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H (NVD), the same score and vector as Schneider and CISA. Schneider classifies it as CWE-269; NVD records NVD-CWE-noinfo. The attacker needs an authenticated, non-admin account on the engineering workstation.
Which versions are affected and what is the fix?
Affected are Vijeo Designer versions before V6.3 SP1 and EcoStruxure Machine Expert before v2.3 when the Vijeo Designer optional component is installed. Vijeo Designer V6.3 SP1 fixes the standalone product and is delivered through Schneider Electric Software Update (SESU). The July 2025 revision added the Machine Expert fix: v2.3, from the Schneider Electric Software Installer, ships Vijeo Designer 6.3.2.16. Until updated, Schneider asks owners to limit authenticated user access to the workstation, apply User Account Control practices, and remove the write permission for "Everyone" on the Vijeo-Runtime folder under the Vijeo Designer 6.3 installation directory.
The Schneider EcoStruxure HMI and SCADA software guide covers Vijeo Designer and Machine Expert together. Other Vijeo Designer pages are the hard-coded credentials flaw CVE-2020-7501 and the Harmony HMI FTP path traversal CVE-2021-22704; the update client itself had the DLL hijacking flaw CVE-2018-7799. The OT security guide for small manufacturers covers least-privilege accounts on engineering workstations.
Is CVE-2024-8306 exploited?
It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0026, the 11th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): published 2024-09-11, status Analyzed; NVD Primary CVSS v3.1 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; Schneider Secondary CVSS v3.1 7.8 same vector; CWE-269 (Schneider), NVD-CWE-noinfo (NVD); CPE vijeo_designer before 6.3 and 6.3, vijeo_designer_embedded_in_ecostruxure_machine_expert all versions. — NVD
- Schneider SEVD-2024-254-01 v2.0.0 (10 September 2024, revised 8 July 2025, PDF and Schneider CSAF read 2026-11-28): affected Vijeo Designer prior to v6.3 SP1 and Machine Expert with Vijeo Designer component prior to v2.3; CWE-269, CVSS v3.1 7.8; fixes Vijeo Designer V6.3 SP1 via SESU, Machine Expert v2.3 with Vijeo Designer 6.3.2.16 via Software Installer; mitigations limit workstation access, UAC, remove Everyone write permission on Vijeo-Runtime folder; credit Charit Misra, Applied Risk (DNV Cyber). — Schneider Electric
- CISA ICSA-25-014-02 (Update A) CSAF (read 2026-11-28, current revision 3.0.0 of 2026-11-18 correcting encoding): CWE-269, CVSS v3.1 7.8; same affected versions, fixes and mitigations as the Schneider notice. — CISA
- CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-269, CVSS v3.1 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; affected Vijeo Designer prior to V6.3 SP1 and Vijeo Designer embedded in EcoStruxure Machine Expert all versions (as recorded). — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.00263, percentile 0.11189, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which versions fix CVE-2024-8306?
Vijeo Designer V6.3 SP1, delivered through SESU, and EcoStruxure Machine Expert v2.3, which ships Vijeo Designer 6.3.2.16. Schneider added the Machine Expert fix in the July 2025 revision of SEVD-2024-254-01.
What is the workaround?
Schneider asks owners to limit who can log on to the workstation, apply User Account Control practices and remove the write permission for "Everyone" on the Vijeo-Runtime folder of the Vijeo Designer 6.3 installation.
Does the CVE.org record match the fix?
Not fully. As of 2026-11-28 the CVE.org record lists Vijeo Designer embedded in Machine Expert as affected in all versions, while Schneider's July 2025 revision and CISA's Update A name Machine Expert v2.3 as the fix.
Is CVE-2024-8306 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0026, the 11th percentile, in the 2026-11-27 dataset.
Questions about this page?