Security Advisory

CVE-2022-41666: Operator Terminal Expert DLL Signature

Last updated:
  • CVE-2022-41666

CVE-2022-41666 is a missing cryptographic signature check (CWE-347) in Schneider Electric EcoStruxure Operator Terminal Expert and its Pro-face twin, Pro-face BLUE. A user with local privileges on the engineering workstation could load a malicious DLL and run code. NVD scores it 7.8 and Schneider 7.0. V3.3 Service Pack 1 fixes it.

Vulnerability summary

CVSS base score

7.8

High severity

EPSS score (FIRST)

0.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-41666 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric EcoStruxure Operator Terminal Expertcpe:2.3:a:schneider-electric:ecostruxure_operator_terminal_expert:*:*:*:*:*:*:*:*V3.3 Hotfix 1 or prior; fixed in V3.3 Service Pack 1
Pro-face BLUEcpe:2.3:a:schneider-electric:pro-face_blue:*:*:*:*:*:*:*:*V3.3 Hotfix 1 or prior; fixed in V3.3 Service Pack 1

What does this mean for affected devices?

Schneider's notice SEVD-2022-284-01 of 11 October 2022 describes "a CWE-347: Improper Verification of Cryptographic Signature vulnerability" "that allows adversaries with local user privileges to load a malicious DLL which could lead to execution of malicious code." Operator Terminal Expert and Pro-face BLUE are the HMI configuration tools for Harmony and Pro-face operator panels, and the notice says the loss of availability, integrity and confidentiality hits the workstation where the software or its runtime is installed. It is one of six flaws in the notice, all credited to Noam Moshe and Amir Preminger of Claroty.

How severe is CVE-2022-41666?

NVD's Primary score is CVSS v3.1 7.8, AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H (NVD). Schneider, the CNA, scores it 7.0, AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H, rating attack complexity high; the CVE.org record carries that 7.0. NVD lists no CWE of its own; the CWE-347 label is Schneider's. Both scores require a local account on the workstation.

Which versions are affected and what is the fix?

Affected are Operator Terminal Expert V3.3 Hotfix 1 or prior and Pro-face BLUE V3.3 Hotfix 1 or prior. V3.3 Service Pack 1 of each product fixes this flaw and the five others in the notice, including the path traversal CVE-2022-41667. The update is on Schneider's and Pro-face's download pages and also arrives through Schneider Electric Software Update (SESU). Owners who cannot update should use the software only on a trusted workstation in a secure network environment and harden it with antivirus, current operating system patches, strong password policies and application allowlisting.

The Schneider EcoStruxure HMI and SCADA software guide lists the Operator Terminal Expert flaws side by side. Other DLL and privilege issues on the same kind of workstation are the SESU DLL hijacking CVE-2018-7799 and the Vijeo Designer privilege escalation CVE-2024-8306; the network-reachable Ethernet Download flaw in the same product is CVE-2020-28221. The OT security guide for small manufacturers covers workstation hardening.

Is CVE-2022-41666 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0018, the 4th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2022-11-04, status Modified; NVD Primary CVSS v3.1 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; Schneider Secondary CVSS v3.1 7.0 AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H; CWE-347 (Schneider, no NVD Primary CWE); CPE ecostruxure_operator_terminal_expert before 3.3 and 3.3, pro-face_blue before 3.3 and 3.3. — NVD
  • Schneider SEVD-2022-284-01 (11 October 2022, PDF and Schneider CSAF read 2026-11-28): affected Operator Terminal Expert V3.3 Hotfix 1 or prior and Pro-face BLUE V3.3 Hotfix1 or prior; six CVEs CVE-2022-41666 to -41671, each CVSS v3.1 7.0; fix V3.3 Service Pack 1 of each product, also via SESU; mitigations (secure network, trusted workstation, hardening); credit Noam Moshe and Amir Preminger (Claroty). — Schneider Electric
  • CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-347, CVSS v3.1 7.0 AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H; affected Operator Terminal Expert and Pro-face BLUE V3.3 up to and including Hotfix 1. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.0018, percentile 0.04447, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2022-284-01: EcoStruxure Operator Terminal Expert and Pro-face BLUE
  3. CVE.org record (JSON)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which version fixes CVE-2022-41666?

V3.3 Service Pack 1 of EcoStruxure Operator Terminal Expert and of Pro-face BLUE, per Schneider's SEVD-2022-284-01. The same update fixes CVE-2022-41667 to CVE-2022-41671 and is also delivered through SESU.

Can it be exploited over the network?

Not directly. Both NVD and Schneider use a local attack vector with low privileges: the attacker needs a local user account on the engineering workstation to plant the DLL.

Why is the NVD score higher than Schneider's?

Schneider rates attack complexity high, giving 7.0. NVD rates it low, giving 7.8. Everything else in the two vectors is the same.

Is CVE-2022-41666 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0018, the 4th percentile, in the 2026-11-27 dataset.