CVE-2018-7846 is a trust boundary violation in Schneider Electric Modicon M580, M340, Quantum and Premium controllers: by brute-forcing a one-byte UMAS session token over Modbus port 502, an unauthenticated attacker can end the session of the user holding the controller reservation. NVD scores it 9.8, Schneider 5.3. Schneider names M580 SV4.20 and M340 SV3.60 as the remediation.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
29.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-7846 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Modicon M580 (BMEP*, BMEH*, excluding M580 CPU Safety) | cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v2.90 (SEVD-2019-134-11 v14.0.0 affected-products table). Remediation: firmware SV4.20 or later with EcoStruxure Control Expert v16.0, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon M340 CPU (BMXP34*) | cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:* | Affected: versions prior to v3.10 (SEVD-2019-134-11 v14.0.0). Remediation: firmware SV3.60 or later with Control Expert v16.0 or later, application password, rebuild and transfer (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon Quantum and Quantum Safety | cpe:2.3:o:schneider-electric:modicon_quantum_firmware:*:*:*:*:*:*:*:* | All versions; end of life, no fix; mitigate with port 502/TCP firewalling and the Access Control List, migrate to M580 (SEVD-2019-134-11, ICSA-25-114-01) |
| Schneider Electric Modicon Premium (TSXP57*, TSXH57*) | cpe:2.3:o:schneider-electric:modicon_premium_firmware:*:*:*:*:*:*:*:* | All versions; end of life, no fix; mitigate with port 502/TCP firewalling and the Access Control List, migrate to M580 (SEVD-2019-134-11, ICSA-25-114-01) |
What does this mean for affected devices?
NVD carries Schneider Electric's description: "A CWE-501: Trust Boundary Violation vulnerability on connection to the Controller exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum and Modicon Premium which could cause unauthorized access by conducting a brute force attack on Modbus protocol to the controller." NVD's Primary score is CVSS v3.1 9.8 (critical), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, and its CVSS v2 score is 5.0. NVD's Primary weakness is CWE-668 (exposure of resource to wrong sphere), while Schneider gives CWE-501. The CVE.org record is PUBLISHED with Schneider Electric as CNA (NVD, CVE record).
What happens on the controller?
Cisco Talos reported the flaw as TALOS-2018-0735 on 10 June 2019, tested on a Modicon M580 BMEP582040 with firmware SV2.70. The M580 tracks which client holds the UMAS reservation for privileged commands with a session token that is one byte long, so there are only 256 values. Talos looped through every value inside a RELEASE_PLC_RESERVATION command (Modbus function code 0x5A, UMAS function code 0x11) on port 502 and could disconnect any user holding an elevated session, without authenticating. Talos warns that the controller could enter a fault state if a strategy download is running at that moment, and that a disconnected HMI may no longer be able to control the device.
Why do the scores differ so much?
Schneider's notice SEVD-2019-134-11 (version 14.0.0, 8 September 2026) scores it CVSS v3.1 5.3 (medium), vector AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L, and CVSS v4.0 6.9. Talos also gives 5.3 with CWE-501. That reflects a session drop, not program access. NVD rates every impact high for 9.8. CISA's republication ICSA-25-114-01 carries Schneider's 5.3.
Which firmware fixes it?
The notice's affected table lists M580 versions prior to v2.90, M340 prior to v3.10 and all versions of Quantum, Quantum Safety and Premium. The remediation section, and the fixed product status in CISA's CSAF file, now name M580 firmware SV4.20 and M340 SV3.60 with EcoStruxure Control Expert v16.0. After the update, set an application password and the new firmware version in each project, then rebuild and transfer it. Quantum and Premium are end of life with no fix as of 2026-11-19; Schneider advises blocking port 502/TCP, configuring the Access Control List and migrating to M580.
Our UMAS protocol security guide explains reservations and lists the alerts worth writing, such as bursts of release requests from an unknown host. CVE-2018-7842 uses the same session brute force to run privileged commands, and CVE-2017-6032 is the earlier Modicon Modbus brute-force finding. For the general fix pattern, see the authentication bypass fix guide.
CVE-2018-7846 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.29575, the 98.2nd percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: CWE-501 trust boundary violation on connection to the controller in all versions of M580, M340, Quantum and Premium, unauthorized access by brute force on Modbus; NVD Primary CVSS v3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, v2 5.0; NVD Primary CWE-668; published 2019-05-22. Read 2026-11-19 (NVD API data fetched 2026-11-19). — NVD
- CVE.org record state PUBLISHED, CNA Schneider Electric (schneider), published 2019-05-22; references SEVD-2019-134-11 and TALOS-2018-0735; no CNA CVSS metric in the record. Checked 2026-11-19. — CVE.org
- SEVD-2019-134-11 v14.0.0 (8 September 2026): CVSS v3.1 5.3 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L, CVSS v4.0 6.9, CWE-501; affected M580 prior to v2.90, M340 prior to v3.10, Quantum, Quantum Safety and Premium all versions; remediation M580 SV4.20 and M340 SV3.60 with Control Expert v16.0, application password, rebuild and transfer; Quantum/Premium end of life, firewall port 502 and Access Control List. Read 2026-11-19. — Schneider Electric SEVD-2019-134-11
- ICSA-25-114-01 (Update A) republishes SEVD-2019-134-11; for CVE-2018-7846: CVSS v3.1 5.3, CWE-501, fixed products M580 firmware 4.20 and M340 firmware 3.60, Quantum, Quantum Safety and Premium carry the CSAF remediation category for no fix. Read 2026-11-19 from the CSAF file. — CISA ICSA-25-114-01 (CSAF)
- TALOS-2018-0735 (10 June 2019): M580 BMEP582040 SV2.70; one-byte session tokens; looping all 256 values in RELEASE_PLC_RESERVATION (0x5A, session, 0x11) disconnects any user with an elevated session; device could enter a fault state during a strategy download; HMI control could be prevented; Talos CVSS v3.0 5.3, CWE-501. Read 2026-11-19. — Cisco Talos TALOS-2018-0735
- Not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). Checked 2026-11-19. — CISA KEV
- EPSS 0.29575, percentile 0.98225, dataset 2026-11-18. Read 2026-11-19. — FIRST EPSS

Related advisories
Sources
- NVD: CVE-2018-7846
- CVE.org record CVE-2018-7846 (CNA: Schneider Electric)
- Schneider Electric Security Notification SEVD-2019-134-11: Multiple Vulnerabilities in Modicon Controller Products (v14.0.0, 8 September 2026; PDF)
- CISA ICS Advisory ICSA-25-114-01: Schneider Electric Modicon Controllers (Update A)
- CISA CSAF record for ICSA-25-114-01
- Cisco Talos TALOS-2018-0735: Schneider Electric Modicon M580 UMAS release reservation denial of service (CVE-2018-7846)
- CISA Known Exploited Vulnerabilities catalog
- FIRST EPSS score for CVE-2018-7846
Frequently asked questions
What can an attacker do with CVE-2018-7846?
Without authenticating, they can disconnect any user holding an elevated UMAS session; a controller may enter a fault state if a program download is running, and a disconnected HMI may lose control of the device (per Cisco Talos TALOS-2018-0735).
Which Modicon controllers are affected by CVE-2018-7846?
M580 versions prior to v2.90, M340 prior to v3.10, and all versions of Quantum, Quantum Safety and Premium. Remediation is M580 SV4.20 and M340 SV3.60 with Control Expert v16.0 (per Schneider SEVD-2019-134-11 v14.0.0).
What should owners of Quantum and Premium controllers do?
These controllers are end of life and have no fix. Schneider advises network segmentation with a firewall blocking unauthorized access to port 502/TCP, the Access Control List, and migration to M580 (per Schneider SEVD-2019-134-11).
Is CVE-2018-7846 in the CISA KEV catalog?
No, not as of 2026-11-19 (catalog version 2026.11.18). FIRST EPSS gives it 0.29575, the 98.2nd percentile, in the 2026-11-18 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?