CVE-2017-2681 is a PROFINET DCP denial-of-service flaw in Siemens industrial devices: crafted DCP packets sent on the local Ethernet segment to one device, such as an S7 CPU, SCALANCE switch or SINAMICS drive, stop it until someone restarts it. NVD and Siemens both score it 6.5. Siemens lists fixes per product in SSA-293562; some products have none.
Vulnerability summary
CVSS base score
6.5
Medium severity
EPSS score (FIRST)
0.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-2681 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC S7-1500 CPU family and S7-1500 Software Controller | cpe:2.3:o:siemens:simatic_s7-1500_firmware:*:*:*:*:*:*:*:* | All versions before V2.1; fixed in V2.1 (Siemens SSA-293562) |
| Siemens SIMATIC S7-1200 CPU family (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-1200_firmware:*:*:*:*:*:*:*:* | All versions before V4.2.1; fixed in V4.2.1 (Siemens SSA-293562) |
| Siemens SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-300_firmware:*:*:*:*:*:*:*:* | All versions before V3.X.14; fixed in V3.X.14 (Siemens SSA-293562) |
| Siemens SIMATIC S7-400 PN/DP V6, S7-400 H V6, S7-400 PN/DP V7 and S7-410 CPU families | cpe:2.3:o:siemens:simatic_s7-400_firmware:*:*:*:*:*:*:*:* | PN/DP V6 before V6.0.6; H V6 before V6.0.7; PN/DP V7 before V7.0.2; S7-410 before V8.2 (Siemens SSA-293562) |
| Siemens SCALANCE X-200, X-200IRT, X-300/X408, X414, XM-400, XR-500, W-700 and M-800 families | cpe:2.3:o:siemens:scalance_x200_firmware:*:*:*:*:*:*:*:* | X-200 before V5.2.2; X-200IRT before V5.4.0; X-300/X408 before V4.1.0 (update to V4.1.2); X414 before V3.10.2; XM-400 and XR-500 before V6.1 (update to V6.2); W-700 before V6.1 (update to V6.3.1); M-800 before V4.03 (update to V5.00) (Siemens SSA-293562) |
| Siemens SINAMICS drives with PROFINET (G110M, G120, G130, G150, S110, S120, S150, V90, DCM, DCP) and SIMOTION | cpe:2.3:o:siemens:sinamics_s120_firmware:*:*:*:*:*:*:*:* | Fixed per model, for example G120(C/P/D) w. PN V4.7 SP6 HF3, S120 V4.7 HF27 or V4.8 HF4, V90 w. PN V1.01, SIMOTION V4.5 HF1 (Siemens SSA-293562) |
| Siemens SIMATIC HMI Comfort, Multi and Mobile Panels (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_hmi_comfort_panels:*:*:*:*:*:*:*:* | All versions before V15.1; fixed in V15.1 (Siemens SSA-293562) |
| Siemens products with no fix: IE/AS-i Link PN IO, CP 343-1 Advanced, CP 443-1 OPC UA, CP 1243-1 DNP3 and IEC, ET200ecoPN modules, ET 200S, ET 200M, ET 200pro IM 154-3/154-4 PN HF, ET 200SP IM 155-6 PN BA, Teleservice Adapters, SIRIUS M200D and 3RW44 PN | — | All versions; Siemens lists no fix as of 2026-11-20 and recommends VPN between cells (Siemens SSA-293562) |
What does this mean for affected devices?
NVD carries the Siemens description: "Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected." NVD's Primary score is CVSS v3.1 6.5 (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), the same as Siemens', which adds CVSS v4.0 7.1; both class it CWE-400 (uncontrolled resource consumption). The record was published on 2017-05-11 (NVD, CVE record).
How does it differ from CVE-2017-2680?
Siemens ProductCERT SSA-293562 (first published 2017-05-08, V3.6 of 2024-09-10) covers two DCP flaws. CVE-2017-2680 is triggered by DCP broadcast packets; CVE-2017-2681 by DCP packets sent to one product. Every product entry in the current advisory lists both CVEs, with the same fix, and Siemens' V3.6 revision notes that it "clarified and updated impact of CVE-2017-2681 to the individual products". Either way the attacker needs direct Layer 2 access to the segment, which is why the attack vector is adjacent network rather than network.
Which products are affected and which firmware fixes them?
The advisory lists more than 120 product entries. A selection of fixed versions from SSA-293562:
| Product (Siemens wording) | Affected | Fix |
|---|---|---|
| SIMATIC S7-1500 CPU family, S7-1500 Software Controller | before V2.1 | V2.1 |
| SIMATIC S7-1200 CPU family | before V4.2.1 | V4.2.1 |
| SIMATIC S7-300 CPU family | before V3.X.14 | V3.X.14 |
| SIMATIC S7-400 PN/DP V6 / H V6 / PN/DP V7 | before V6.0.6 / V6.0.7 / V7.0.2 | same versions |
| SCALANCE X-200 / X-300 and X408 | before V5.2.2 / V4.1.0 | V5.2.2 / V4.1.2 |
| SCALANCE M-800 (incl. S615, MUM-800, RM1224) | before V4.03 | V5.00 |
| SINAMICS G120(C/P/D) w. PN | before V4.7 SP6 HF3 | V4.7 SP6 HF3 |
| SIMATIC HMI Comfort, Multi and Mobile Panels | before V15.1 | V15.1 |
Siemens lists no fix for the IE/AS-i Link PN IO, CP 343-1 Advanced, CP 443-1 OPC UA, CP 1243-1 DNP3 and IEC, the ET200ecoPN modules, ET 200S, ET 200M, ET 200pro IM 154-3 and IM 154-4 PN HF, ET 200SP IM 155-6 PN BA, the Teleservice Adapters (successor: SCALANCE M-800) and the SIRIUS M200D and 3RW44 PN starters. CISA republished the advisory as ICSA-17-129-02, now at Update V (CSAF). NVD's CPE ranges do not always match the vendor's fix version; for the SCALANCE X-300, for example, NVD ends at 4.1.0 while Siemens points to V4.1.2.
How do you mitigate it where there is no fix?
Siemens' workaround is to "Use VPN for protecting network communication between cells", together with its general advice to protect network access. Because the packets travel at Layer 2, keep PROFINET in its own cell, do not bridge it to office or remote-access networks, and control which ports an engineering laptop can plug into. Affected devices do not recover by themselves, so plan for a manual restart after an outage.
Our PROFINET protocol security guide explains DCP and lists this advisory, and the input-handling fix guide covers resource exhaustion as a class. Other DCP pages are CVE-2018-4843, CVE-2020-28400 and the Beckhoff TwinCAT flaw CVE-2019-5637. For the S7-300, CVE-2018-16561 needs firmware V3.X.16, which also covers this CVE.
CVE-2017-2681 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.00906, the 60.6th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-20): status Modified; published 2017-05-11; NVD Primary CVSS v3.1 6.5 CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 6.1; Siemens Secondary CVSS v3.1 6.5 and v4.0 7.1; CWE-400 (NVD and Siemens); CPE configuration covers S7-1200 before 4.2.1, S7-1500 before 2.1, S7-300 before 3.3.17, S7-400 before 6.0.6, SCALANCE X-200 before 5.2.2, X-300 before 4.1.0, M-800 before 4.03, HMI panels before 15.1 and further Siemens products; references SSA-293562. — NVD
- Siemens SSA-293562 V3.6 (published 2017-05-08, updated 2024-09-10), read 2026-11-20: CVE-2017-2681 DCP packets sent to an affected product on Layer 2 cause denial of service, human interaction to recover, PROFIBUS not affected; CVSS v3.1 6.5, v4.0 7.1, CWE-400; every product entry affected by CVE-2017-2680 and CVE-2017-2681; fixes include S7-1500 V2.1, S7-1200 V4.2.1, S7-300 V3.X.14, S7-400 PN/DP V6 V6.0.6, H V6 V6.0.7, PN/DP V7 V7.0.2, S7-410 V8.2, SCALANCE X-200 V5.2.2, X-300 V4.1.2, M-800 V5.00, G120 V4.7 SP6 HF3, HMI panels V15.1; no fix for IE/AS-i Link PN IO, CP 343-1 Advanced, CP 443-1 OPC UA, CP 1243-1 DNP3/IEC, ET200ecoPN, ET 200S, ET 200M, ET 200pro IM 154-3/154-4 PN HF, ET 200SP IM 155-6 PN BA, Teleservice Adapters, SIRIUS M200D and 3RW44 PN; workaround: use VPN between cells; V3.6 clarified impact of CVE-2017-2681 per product. — Siemens ProductCERT SSA-293562
- CISA ICSA-17-129-02 CSAF (Siemens PROFINET DCP, Update V, version 27, current release 2024-09-10), read 2026-11-20: CVE-2017-2681 CWE-400, CVSS v3.1 6.5. — CISA CSAF ICSA-17-129-02
- CVE record (checked 2026-11-20): state PUBLISHED, CNA Siemens, published 2017-05-11; CNA CVSS v3.1 6.5 and v4.0 7.1, CWE-400. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries, released 2026-11-18), checked 2026-11-20. — CISA KEV
- EPSS 0.00906, percentile 0.60592, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
What is the difference between CVE-2017-2680 and CVE-2017-2681?
CVE-2017-2680 is triggered by crafted PROFINET DCP broadcast packets; CVE-2017-2681 by crafted DCP packets sent to one product. Siemens SSA-293562 lists both CVEs on every product entry with the same fix version, so one update closes both.
Can CVE-2017-2681 be exploited from the internet?
Not directly. Siemens and NVD both describe Layer 2 access to the local Ethernet segment as the precondition, and the CVSS attack vector is adjacent network. The attacker needs a device on the PROFINET segment, for example a compromised engineering laptop or a bridged remote-access link.
Which S7 CPU firmware fixes it?
S7-1500 V2.1, S7-1200 V4.2.1, S7-300 V3.X.14, S7-400 PN/DP V6 V6.0.6, S7-400 H V6 V6.0.7, S7-400 PN/DP V7 V7.0.2 and S7-410 V8.2, per Siemens SSA-293562.
What should I do for products without a fix?
Siemens lists no fix as of 2026-11-20 for products such as the ET 200M, ET 200S, CP 343-1 Advanced, IE/AS-i Link PN IO and the Teleservice Adapters. Its workaround is to use VPN between cells and protect network access; for the Teleservice Adapters it names the SCALANCE M-800 family as successor.
Questions about this page?