Security Advisory

CVE-2018-4843: Siemens PROFINET DCP Response DoS

Last updated:
  • CVE-2018-4843

CVE-2018-4843 is a PROFINET DCP flaw in Siemens controllers: an attacker on the same Ethernet segment answers a device's DCP request with a crafted packet, and the requesting S7-300, S7-400 or S7-1500 CPU or communication processor stops until a manual restart. NVD scores it 6.1 (CVSS v2). Siemens SSA-592007 lists 45 entries.

Vulnerability summary

CVSS base score

6.1

Medium severity

EPSS score (FIRST)

0.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-4843 · Source: NVD

Affected components

ComponentCPEVersion range
Siemens SIMATIC S7-1500 CPU family and S7-1500 Software Controllercpe:2.3:o:siemens:simatic_s7-1500_firmware:*:*:*:*:*:*:*:*before V1.7.0 (NVD, Siemens SSA-592007)
Siemens SIMATIC S7-300 PN/DP CPUs and ET 200pro/ET 200S PN/DP CPUscpe:2.3:o:siemens:simatic_s7-300_firmware:*:*:*:*:*:*:*:*before V3.2.16; CPU 314C-2 PN/DP before V3.3.16 (SSA-592007)
Siemens SIMATIC S7-400 and S7-410 CPUs—PN/DP V6 before V6.0.7; H V6 before V6.0.9; PN/DP V7 before V7.0.3; S7-410 before V8.1 (SSA-592007)
Siemens SIMATIC CP 443-1 and CP 443-1 Advancedcpe:2.3:o:siemens:simatic_cp_443-1_firmware:*:*:*:*:*:*:*:*before V3.3 (SSA-592007)
Siemens SINUMERIK 828D and SIMATIC WinAC RTX (F) 2010—SINUMERIK 828D before V4.7 SP6 HF1; WinAC RTX before 2010 SP3 (SSA-592007)
Siemens SIMATIC CP 343-1, CP 343-1 Advanced, Softnet PROFINET IO for PC-based Windows systemscpe:2.3:o:siemens:simatic_cp_343-1_firmware:*:*:*:*:*:*:*:*all versions; no fix, mitigation only (SSA-592007)

What does this mean for affected devices?

CVE-2018-4843 turns PROFINET discovery against the device that asks. Siemens describes it this way: "Responding to a PROFINET DCP request with a specially crafted PROFINET DCP packet could cause a denial of service condition of the requesting system." The attacker must be "located on the same Ethernet segment (OSI Layer 2) as the targeted device", and "A manual restart is required to recover the system" (Siemens SSA-592007). Controllers and communication processors send DCP requests to find their IO devices, so a rogue host that answers those requests can stop them.

NVD's Primary score is CVSS v2 only: 6.1, vector AV:A/AC:L/Au:N/C:N/I:N/A:C, with CWE-20 (improper input validation). The CVSS v3.1 score of 6.5 that Siemens supplies, CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, is recorded as Secondary (NVD). Siemens' temporal vector in its CSAF file adds E:P, its rating for exploit code maturity as proof of concept, and revision 12 of 2023-05-09 "reviewed CVSS score and description".

SSA-592007 was first published on 2018-03-20 and lists 45 product entries. CISA republished it as ICSA-18-079-02 with the same 45 entries (CSAF). Fixed versions:

  • SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS) and S7-1500 Software Controller: V1.7.0.
  • SIMATIC S7-300 PN/DP CPUs (315-2, 317-2, 319-3 and their F/T variants) and ET 200pro IM154-8 / ET 200S IM151-8 PN/DP CPUs: V3.2.16; CPU 314C-2 PN/DP: V3.3.16.
  • SIMATIC S7-400 PN/DP V6: V6.0.7; S7-400 H V6: V6.0.9; S7-400 PN/DP V7 CPUs: V7.0.3; S7-410: V8.1.
  • SIMATIC CP 443-1 and CP 443-1 Advanced: V3.3. SINUMERIK 828D: V4.7 SP6 HF1. WinAC RTX (F) 2010: SP3 plus BIOS and Windows updates.

Siemens lists no fix for SIMATIC CP 343-1, CP 343-1 Advanced (both incl. SIPLUS variants) and Softnet PROFINET IO for PC-based Windows systems. For all products its mitigation is to "Use VPN for protecting network communication between cells."

Our PROFINET protocol security guide puts this CVE next to the DCP flood bugs CVE-2020-28400 and CVE-2017-2680. Its monitoring advice applies directly: alert on DCP responses from MAC addresses that are not known PROFINET devices. For segmentation, see our Purdue model guide.

CVE-2018-4843 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.00543, the 46.2nd percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • Crafted DCP response to a DCP request causes DoS of the requesting system; same Ethernet segment; manual restart required; 45 product entries, 3 with no fix; VPN between cells; revision 12 (2023-05-09) reviewed CVSS score and description. — Siemens ProductCERT SSA-592007
  • CVSS 3.1 vector with E:P/RL:O/RC:C temporal metrics; fixed versions per product. — Siemens ProductCERT SSA-592007 (CSAF)
  • NVD Primary CVSS v2 6.1 (AV:A/AC:L/Au:N/C:N/I:N/A:C); Siemens CVSS 3.1 6.5 Secondary; CWE-20. — NVD
  • ICSA-18-079-02 (Update D, revision 12) lists 45 entries for CVE-2018-4843. — CISA ICSA-18-079-02 (CSAF)
  • Not in the KEV catalog as of 2026-11-17 (catalog version 2026.11.13). — CISA KEV
  • EPSS 0.00543 (46.2nd percentile), dataset 2026-11-16, read 2026-11-17. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-592007: Denial of Service Vulnerability in Industrial Products
  3. Siemens ProductCERT SSA-592007 (CSAF)
  4. CISA ICSA-18-079-02: Siemens SIMATIC, SINUMERIK, and PROFINET IO (CSAF)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which device is attacked in CVE-2018-4843?

The device that sent the DCP request. An attacker on the same Ethernet segment replies with a crafted DCP packet, and the requesting Siemens controller or communication processor goes into a denial-of-service state until a manual restart (per Siemens SSA-592007).

Why does NVD show 6.1 and Siemens 6.5 for CVE-2018-4843?

NVD's Primary score is CVSS v2 (6.1). The 6.5 figure is Siemens' CVSS v3.1 score, which NVD records as Secondary (per NVD and SSA-592007).

Which products have no fix for CVE-2018-4843?

SIMATIC CP 343-1, CP 343-1 Advanced (incl. SIPLUS variants) and Softnet PROFINET IO for PC-based Windows systems. Siemens recommends VPNs between cells (per SSA-592007).

Is CVE-2018-4843 in the CISA KEV catalog?

No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.00543, the 46.2nd percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).