CVE-2017-2680 is a PROFINET DCP denial-of-service flaw in Siemens industrial devices: crafted DCP broadcast packets on the local Ethernet segment stop S7 CPUs, SCALANCE switches, SINAMICS drives and ET 200 modules until someone restarts them. NVD scores it 6.5. Siemens lists 126 affected entries in SSA-293562, 28 with no fix.
Vulnerability summary
CVSS base score
6.5
Medium severity
EPSS score (FIRST)
1.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-2680 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC S7-1500 CPU family and S7-1500 Software Controller | cpe:2.3:o:siemens:simatic_s7-1500_firmware:*:*:*:*:*:*:*:* | before V2.1 (Siemens SSA-293562) |
| Siemens SIMATIC S7-1200, S7-300 and S7-400 CPU families | — | S7-1200 before V4.2.1; S7-300 before V3.X.14; S7-400 PN/DP V6 before V6.0.6, H V6 before V6.0.7, PN/DP V7 before V7.0.2 (SSA-293562) |
| Siemens SCALANCE X-200, X-300/X408 and M-800 (incl. S615, RM1224) | — | X-200 before V5.2.2; X-300/X408 before V4.1.2; M-800 before V5.00 (SSA-293562) |
| Siemens SINAMICS drives and SIMATIC HMI panels with PROFINET | cpe:2.3:o:siemens:sinamics_g120\(c\/p\/d\)_w._pn_firmware:*:*:*:*:*:*:*:* | G120(C/P/D) before V4.7 SP6 HF3; HMI Comfort/Multi/Mobile Panels before V15.1; medium-voltage GH150/GL150/GM150/SL150/SM120 per SSA-546832 |
| Siemens ET 200M, ET 200S, ET200ecoPN, CP 343-1 Advanced and 24 more entries | — | no fix; mitigation only (SSA-293562) |
| Siemens HMI Extension Units PROFINET, CP 1242-7, CP 1243-7, CP 1243-8, CP 1626 | — | Extension Units before V01.01.01; CP 124x before V2.1.82; CP 1626 before V1.1 (SSA-284673) |
What does this mean for affected devices?
CVE-2017-2680 is the broadcast half of the 2017 Siemens PROFINET DCP disclosure. NVD's description reads: "Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected." NVD scores it 6.5 (medium), vector CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, records CWE-400 (uncontrolled resource consumption) and lists 209 CPE match entries across Siemens controllers, drives, switches and HMIs (NVD).
The main source is Siemens ProductCERT SSA-293562, first published 2017-05-08 and at revision 27 since 2024-09-10. It covers CVE-2017-2680 together with the companion CVE-2017-2681, where the crafted DCP packets are sent to one product rather than broadcast. Both CVEs carry the same 126 product entries, the same fixes and the same 6.5 score. CISA republished it as ICSA-17-129-02 (CSAF). Fixed versions include:
- SIMATIC S7-1500 CPU family and S7-1500 Software Controller: V2.1. S7-1200 CPU family: V4.2.1. S7-300 CPU family: V3.X.14.
- SIMATIC S7-400 PN/DP V6: V6.0.6; S7-400 H V6: V6.0.7; S7-400 PN/DP V7: V7.0.2.
- SCALANCE X-200: V5.2.2; X-300 and X408: V4.1.2; M-800 family (incl. S615, MUM-800 and RM1224): V5.00.
- SINAMICS G120(C/P/D) with PROFINET: V4.7 SP6 HF3; SIMATIC HMI Comfort, Multi and Mobile Panels: V15.1.
Siemens lists no fix for 28 entries, including the ET 200M, ET 200S and ET200ecoPN modules, ET 200pro IM 154-3/154-4 PN HF, ET 200SP IM 155-6 PN BA, SIMATIC CP 343-1 Advanced, CP 443-1 OPC UA, CP 1243-1 DNP3 and IEC, IE/AS-i Link PN IO, the Teleservice Adapters and SIRIUS M200D and 3RW44 PN starters. Its mitigation for those is to "Use VPN for protecting network communication between cells."
Two later Siemens advisories add devices for CVE-2017-2680 only. SSA-284673 (2018-01-18, V1.1 of 2019-02-12; CISA ICSA-18-023-02, CSAF) fixes the HMI Extension Units 12" to 22" PROFINET in V01.01.01, the CP 1242-7 GPRS V2, CP 1243-7 LTE/US and CP 1243-8 in V2.1.82, and the CP 1626 in V1.1. SSA-546832 (2018-05-03, V1.2 of 2020-02-10) covers medium-voltage SINAMICS GH150, GL150, GM150, SL150 and SM120 drives, with fixes in V4.7 hotfixes or V4.8 SP2.
The PROFINET DCP background is in our PROFINET protocol security guide. Related Siemens DCP pages are CVE-2018-4843 and CVE-2020-28400. For resource exhaustion as a class, see our input-handling fix guide.
CVE-2017-2680 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.01149, the 67.4th percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS). The attacker needs Layer 2 access, so keep DCP inside the cell, update to the versions above, and restart affected devices after an outage, since they do not recover alone.
Evidence
- Crafted PROFINET DCP broadcast packets cause DoS on a local Ethernet segment; human interaction required; PROFIBUS not affected; CVSS 3.1 6.5 Primary; CWE-400; 209 CPE match entries. — NVD
- SSA-293562 published 2017-05-08, revision 27 of 2024-09-10; 126 product entries for CVE-2017-2680 and CVE-2017-2681; fixed versions listed; 28 entries with no fix; mitigation VPN between cells. — Siemens ProductCERT SSA-293562
- CISA ICSA-17-129-02 (Update V) lists the same 126 entries for CVE-2017-2680 and CVE-2017-2681, 28 without a fix. — CISA ICSA-17-129-02 (CSAF)
- Extension Units 12/15/19/22 PROFINET before V01.01.01; CP 1242-7 GPRS V2, CP 1243-7 LTE/US, CP 1243-8 before V2.1.82; CP 1626 before V1.1. — Siemens ProductCERT SSA-284673
- ICSA-18-023-02 republishes SSA-284673 for CVE-2017-2680. — CISA ICSA-18-023-02 (CSAF)
- Medium-voltage SINAMICS GH150, GL150, GM150, SL150, SM120 and SIMOTION D4xx for SM150i-2 affected via DCP broadcasts; fixes in V4.7 hotfixes or V4.8 SP2. — Siemens ProductCERT SSA-546832
- Not in the KEV catalog as of 2026-11-17 (catalog version 2026.11.13). — CISA KEV
- EPSS 0.01149 (67.4th percentile), dataset 2026-11-16, read 2026-11-17. — FIRST EPSS

Related advisories
Sources
- NVD
- Siemens ProductCERT SSA-293562: Denial of Service Vulnerabilities in PROFINET DCP Implementation of Industrial Products
- Siemens ProductCERT SSA-284673: Vulnerability in Industrial Products
- Siemens ProductCERT SSA-546832: Vulnerabilities in Medium Voltage SINAMICS and SIMOTION Products
- CISA ICSA-17-129-02: Siemens PROFINET DCP (CSAF)
- CISA ICSA-18-023-02: Siemens Industrial Products (CSAF)
- CISA KEV
- FIRST EPSS
Frequently asked questions
What is the difference between CVE-2017-2680 and CVE-2017-2681?
CVE-2017-2680 is triggered by crafted DCP broadcast packets, CVE-2017-2681 by crafted DCP packets sent to one product. Siemens lists the same 126 product entries, fixes and 6.5 score for both (per Siemens SSA-293562).
Can CVE-2017-2680 be exploited from the internet?
No. The attacker needs access to the same Ethernet segment (Layer 2), which is why NVD and Siemens score the attack vector as adjacent network. PROFIBUS interfaces are not affected (per NVD and SSA-293562).
Which Siemens devices have no fix for CVE-2017-2680?
Siemens lists 28 entries without a fix, including ET 200M, ET 200S and ET200ecoPN modules, CP 343-1 Advanced, CP 443-1 OPC UA, IE/AS-i Link PN IO and SIRIUS M200D and 3RW44 PN starters; it recommends VPNs between cells (per SSA-293562).
Is CVE-2017-2680 in the CISA KEV catalog?
No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.01149, the 67.4th percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?