Moxa EDS, ICS, IKS and SDS industrial Ethernet switches and EDR and TN secure routers had no entry in the CISA KEV catalog as of 2026-11-22, but Moxa security advisories, CISA ICS advisories and NVD list more than 40 CVEs for them. The most serious are unauthenticated: missing authentication in the Moxa Service (CVE-2024-9137), OS command injection in EDR and TN-4900 routers (CVE-2024-9140), a hard-coded JWT signing key (CVE-2025-6950) and web server buffer overflows. Fixes are firmware updates or security patches per product series, plus the hardening Moxa's manuals and advisories describe: disable the Moxa Service, Telnet and HTTP when unused, replace the default moxa password, use Trusted Access, and regenerate certificates and SSH keys before commissioning.
Key takeaways
- Moxa publishes fixed versions per product series, and the same CVE often has a different fixed build for each series, so first record the series and the full firmware version of every device.
- The services below are the attack surface Moxa's manuals and advisories describe.
- The recurring switch flaws are Moxa Service bugs, web login bypass, web server memory corruption, hard-coded secrets and missing firmware signature checks.
- The EDR and TN routers have a heavier record of OS command injection and authorization flaws than the switches, and several are reachable before login.
Which Moxa switch and router series does this guide cover?
Moxa publishes fixed versions per product series, and the same CVE often has a different fixed build for each series, so first record the series and the full firmware version of every device. The table groups the series by the firmware family and manual Moxa names in its advisories. Moxa's NPort serial device servers share some of these CVEs and have their own Moxa NPort guide.
| Product family | Series named in Moxa or CISA advisories | Firmware and manual |
|---|---|---|
| EDS-A, EDS-600 and EDS-G509 managed switches | EDS-405A, EDS-408A, EDS-505A, EDS-508A, EDS-510A, EDS-516A, EDS-518A, EDS-608, EDS-611, EDS-616, EDS-619, EDS-G509, EDS-P510, EDS-P510A | 3.x firmware; Moxa Managed Ethernet Switch Manual for EDS Series |
| EDS-E managed switches | EDS-510E, EDS-518E, EDS-528E, EDS-G508E, EDS-G512E, EDS-G516E, EDS-P506E | 5.x and 6.x firmware; Managed Ethernet Switch UI 2.0, FW 5.x manual |
| ICS and IKS rackmount and modular switches | ICS-G7526A to ICS-G7852A, IKS-6726A, IKS-6728A, IKS-G6524A, IKS-G6824A | 5.x firmware; same UI 2.0, FW 5.x manual |
| SDS smart switches | SDS-3006, SDS-3008, SDS-3010, SDS-3016 and the SDS-G3000 equivalents | 3.x firmware; Industrial Smart Ethernet Switch manual |
| EDS-4000 and EDS-G4000 switches | EDS-4008 to EDS-4014, EDS-G4008 to EDS-G4014 | 4.x firmware |
| TN rail switches | TN-4500A, TN-5500A, TN-G4500, TN-G6500, TN-4500B | 3.x to 5.x firmware; TN Series manuals |
| EDR secure routers, older line | EDR-810, EDR-G902, EDR-G903 | 5.x firmware |
| EDR and TN routers on MX-ROS V3 | EDR-8010, EDR-G9004, EDR-G9010, TN-4900; Moxa groups them with EDF-G1002-BP, NAT-102/108 and OnCell G4302-LTE4 | 3.x firmware; MX-ROS V3 user manual |
| TN-5900 rail routers | TN-5900, TN-5916 | 3.x and 4.x firmware |
These devices sit at the boundaries of an OT network. The MX-ROS V3 manual says the router must be installed at the security perimeter or the boundary between different zones to provide network segmentation, and the EDS, ICS and IKS switches carry the cell and backbone traffic below it. A compromised router opens the zone it protects; a crashed switch takes the traffic of every PLC, HMI and drive behind it down with it.
How are Moxa EDS switches and EDR routers managed?
The services below are the attack surface Moxa's manuals and advisories describe. Switch ports come from the Moxa Managed Ethernet Switch (UI 2.0, FW 5.x) user manual (version 2.8, November 2026); router ports and defaults come from the MX-ROS V3 user manual (version 1.18, October 2026).
| Service | Switch port (FW 5.x manual) | MX-ROS V3 router port and default | Advisories that reach it |
|---|---|---|---|
| HTTP web server | TCP 80 | TCP 80, enabled | Web buffer overflows, CVE-2024-12297, CVE-2025-0415 |
| HTTPS web server | TCP 443 | TCP 443, enabled | CVE-2026-3868, CVE-2026-15579 |
| SSH | TCP 22 | TCP 22, enabled | CVE-2024-9138, CVE-2024-9140 (Moxa's mitigation limits SSH access) |
| Telnet | TCP 23 | TCP 23, disabled | Clear-text credentials (MPSA-241021) |
| SNMP | UDP 161, off by default | UDP 161 | Inventory and configuration access |
| Moxa Service | TCP 4000 and UDP 4000 | Only the encrypted service is listed | CVE-2024-9137, CVE-2024-9404 |
| Moxa Service (Encrypted) | TCP 443 and UDP 40404 | TCP 443 and UDP 40404, enabled | CVE-2024-9137, CVE-2024-9404 |
| Serial or USB console | Local | Local | CVE-2025-0676 (console access) |
Moxa says the Moxa Service is only for its network management software suite. Moxa advisory MPSA-240931 calls it "commonly referred to as moxa_cmd, originally designed for deployment purposes", and two of the 2024 switch CVEs are reached through it. The switch manual sets the default password to moxa and the default IP address to 192.168.127.253; the MX-ROS V3 manual sets admin/moxa and 192.168.127.254 and forces a password change at first login.
Some switches also run industrial protocol services. Moxa's MPSA-241021 says attackers could read Modbus/TCP coil settings and device identification from EDS-P510 switches on firmware 3.11 and earlier, and that their Telnet server sends credentials in clear text; firmware 3.12 fixes it. CISA's ICSA-19-353-01 covers CVE-2019-19707, where PROFINET DCE-RPC endpoint discovery packets take EDS-G508E, EDS-G512E and EDS-G516E switches on 6.0 and lower out of service.
Which switch vulnerabilities appear in Moxa and CISA advisories?
The recurring switch flaws are Moxa Service bugs, web login bypass, web server memory corruption, hard-coded secrets and missing firmware signature checks. Scores are CVSS v3.1 unless marked v4; the scorer is named in brackets. "Moxa" is the score Moxa publishes as CVE Numbering Authority, "CISA" the score in the CISA advisory.
| CVE | Series and affected versions | What it allows | Score (scorer) | Fix |
|---|---|---|---|---|
| CVE-2024-9137 | 53 series, including EDS-405A 3.14 and earlier, EDS-508A 3.11 and earlier, EDS-G508E/G512E/G516E 6.4 and earlier, ICS-G7528A 5.10 and earlier, IKS-G6524A 5.10 and earlier, SDS-3008 3.0 and earlier, TN-4500A/TN-5500A 3.13 and earlier, TN-G4500/TN-G6500 5.5 and earlier | No authentication check on commands sent through the Moxa Service; configuration download or upload and system compromise | 9.4; 8.8 v4 (Moxa) | Security patch from Moxa Technical Support, for example 3.11.4 for EDS-508A, 6.4.8 for EDS-G5xxE, 5.10.10 for ICS-G7528A, 3.0.8 for SDS (MPSA-241156) |
| CVE-2024-7695 | 43 EDS, ICS, IKS and SDS series at the same versions as above | Unauthenticated out-of-bounds write; denial of service | 7.5; 8.7 v4 (Moxa) | Same security patches (MPSA-240163) |
| CVE-2024-9404 | Same 43 EDS, ICS, IKS and SDS series | Insufficient input validation in moxa_cmd triggers a cold start or denial of service | 7.5; 8.7 v4 (Moxa) | Same security patches (MPSA-240931) |
| CVE-2024-12297 | EDS-508A 3.11 and earlier; EDS-510E 5.5, EDS-518E/528E 6.3, EDS-G5xxE 6.4, EDS-P506E 5.8 and earlier; SDS 3.0 and earlier; TN-4500A/TN-5500A 4.1 and earlier; TN-G4500/TN-G6500 5.5 and earlier | Authentication bypass: flaws in the login logic allow brute force or MD5 collision attacks on authentication hashes | 9.2 v4 (Moxa) | EDS-510E 5.6, EDS-518E/528E 6.4, EDS-G5xxE 6.5, EDS-P506E 5.9, SDS 3.1, TN-A 4.2, TN-G patch 5.5.255, EDS-508A patch (MPSA-241407, MPSA-241409) |
| CVE-2026-130493, CVE-2026-130494 | All firmware of the EDS-E, EDS-A, ICS, IKS, SDS, PT, TWS and TN switch series | Shared RSA-1024 key in public firmware lets an attacker impersonate devices; no firmware signature check lets an administrator-level attacker install unauthorized firmware | 7.7 v4 and 8.6 v4 (Moxa) | No fix; mitigations only (MPSA-268140) |
| CVE-2026-15579 | TN-4500B 2.0 and earlier | Over-long user name in the web login overflows a buffer and crashes authentication | 8.8 v4 (Moxa) | 2.1 or later (MPSA-252620) |
| CVE-2019-6557, CVE-2019-6563, CVE-2019-6520, CVE-2019-6524 and six others | IKS-G6824A 5.6 and prior; EDS-405A, EDS-408A, EDS-510A 3.8 and prior | Web buffer overflows, predictable MD5 session cookie, read-only user can change configuration, no limit on failed logins, plain-text passwords | 9.8, 9.8, 9.1, 9.8 (CISA) | Patches from Moxa; set web configuration to HTTPS only (ICSA-19-057-01) |
| CVE-2020-7007, CVE-2020-6981, CVE-2020-6979 and four others | EDS-G516E, EDS-510E 5.2 or lower | Stack overflow in the IEEE 802.1X setting page, hard-coded password, hard-coded cryptographic key, weak password rules | 9.8 each (CISA); 7.5 for 6979 (NVD) | EDS-G516E new firmware, EDS-510E via Moxa support (ICSA-20-056-04) |
| CVE-2015-6464 and two others | EDS-405A 3.5 and earlier, EDS-408A 3.6 and earlier | Privilege escalation, denial of service in the embedded GoAhead web server, XSS | 8.2 CVSS v2 (Moxa) | EDS-405A 3.6, EDS-408A 3.7 (MPSA-154603) |
Read CVE-2024-9137 and CVE-2024-12297 first. Both are unauthenticated and give an attacker the switch configuration or the login itself; the coding pattern behind them is covered in how to fix authentication bypass in embedded firmware. One Moxa security patch build per series covers CVE-2024-9137, CVE-2024-7695 and CVE-2024-9404 together, and Moxa ships it on request rather than as a public download, so a device that shows the base version (3.11, 6.4, 5.10) is still affected.
The CVE-2026-130493 mitigation follows from the default certificate. The switch manual says that by default the device uses an RSA-1024 private key embedded in Moxa's publicly available firmware to issue a self-signed X.509 certificate, and recommends regenerating the SSL certificate and SSH key before commissioning. Moxa's MPSA-241044 adds that EDS-G508E, EDS-G512E and EDS-G516E firmware 6.4 and earlier uses a weak SSL/TLS key exchange, fixed by a security patch from Moxa Technical Support. The hard-coded password and key flaws from ICSA-20-056-04 belong to the class in how to fix hard-coded credentials in embedded firmware.
Which router vulnerabilities appear in Moxa and CISA advisories?
The EDR and TN routers have a heavier record of OS command injection and authorization flaws than the switches, and several are reachable before login. Fixed versions differ between the 5.x line (EDR-810, EDR-G902, EDR-G903) and the 3.x MX-ROS V3 line (EDR-8010, EDR-G9004, EDR-G9010, TN-4900).
| CVE | Series and affected versions | What it allows | Score (scorer) | Fix |
|---|---|---|---|---|
| CVE-2024-9140 | EDR-8010, EDR-G9004, EDR-G9010 3.13.1 and earlier; TN-4900 3.13 and earlier | Special characters bypass input restrictions; unauthenticated command execution | 9.8; 9.3 v4 (Moxa) | 3.14 or later (MPSA-241155) |
| CVE-2024-9138 | EDR-810 5.12.37 and earlier; EDR-G902/G903 5.7.25 and earlier; EDR-8010, EDR-G9004, EDR-G9010 3.13.1 and earlier; TN-4900 3.13 and earlier | Hard-coded credentials let an authenticated user gain root | 7.2; 8.6 v4 (Moxa) | 3.14 or later for the 3.x line (MPSA-241155); see the note on 5.x below |
| CVE-2024-9137 | EDR-8010, EDR-G9004, EDR-G9010 3.12.1 and earlier; TN-4900 3.6 and earlier | No authentication on commands sent through the Moxa Service; configuration download or upload | 9.4; 8.8 v4 (Moxa) | 3.13 or later (MPSA-241154) |
| CVE-2024-9139 | As above, plus EDR-810 5.12.33 and earlier | OS command injection by a high-privileged user | 7.2; 8.6 v4 (Moxa) | 3.13 or later; EDR-810 5.12.37 or later (MPSA-241154) |
| CVE-2025-6950, CVE-2025-6949, CVE-2025-6893, CVE-2025-6892 | EDR-G9010 3.14 and earlier; EDR-8010 3.17 and earlier; TN-4900 3.14 and earlier | Hard-coded JWT signing key lets an unauthenticated attacker forge tokens as any user; API flaws let a low-privileged user create administrator accounts or change system settings | 9.9, 9.3, 9.3, 8.7 v4 (Moxa) | 3.21 or later (MPSA-258121) |
| CVE-2025-0415 | EDR-810 5.12.39 and earlier; EDR-8010, EDR-G9004, EDR-G9010, TN-4900 3.14 and earlier | Web administrator injects commands through the NTP settings; infinite reboot loop | 9.2 v4 (Moxa) | EDR-810 5.12.41; EDR 3.17; TN-4900 3.21 (MPSA-259491) |
| CVE-2025-0676 | Same as CVE-2025-0415 | Command injection in tcpdump by an authenticated user with console access; root shell | 8.6 v4 (Moxa) | Same as CVE-2025-0415 (MPSA-251431) |
| CVE-2026-3868, CVE-2026-3867 | TN-4900 3.22 and earlier; EDR-8010 3.23 and earlier; EDR-G9010 3.23.1 and earlier; TN-5900 4.0 and earlier (CVE-2026-3867 only) | Unauthenticated HTTPS request overflows a buffer and hangs the web service; low-privileged user reads an exported configuration file with the administrator password hash | 8.7 v4 and 6.0 v4 (Moxa) | TN-4900 3.24; EDR 3.24; TN-5900 4.1 (MPSA-261521) |
| CVE-2023-4452 | EDR-810 5.12.28 and prior; EDR-G902/G903 5.7.20 and prior | Unauthenticated URI buffer copy reboots the router | 6.5 (Moxa); 7.5 (NVD) | EDR-810 5.12.29; EDR-G902/G903 5.7.21 (MPSA-234880) |
| CVE-2020-14511 | EDR-G902, EDR-G903 5.4 and prior | Crafted browser cookie overflows a stack buffer in the web server | 9.8 (CISA, NVD) | New firmware from Moxa (ICSA-20-196-02) |
| CVE-2019-10969 | EDR-810 5.1 and prior | Authenticated user abuses the ping feature to execute commands | 7.2 (CISA, NVD) | 5.2 or later (ICSA-19-274-03) |
Moxa's MPSA-221103 adds a web service command injection in the EDR-810 (fixed in 5.12.13), EDR-G902 (5.7.9) and EDR-G903 (5.7.11), and an unauthenticated command injection in the TN-5916 (fixed in 3.3). The two CVE IDs it cites have no published CVE record as of 2026-11-22; both are still in the RESERVED state, so match these on the advisory number. Command injection is the dominant router weakness, and how to fix command injection in embedded firmware explains the pattern behind CVE-2024-9140, CVE-2024-9139, CVE-2025-0415 and CVE-2025-0676.
For CVE-2024-9137 on the routers, the mitigations are to keep the device off the internet, limit web access to trusted IP addresses with firewall rules or TCP wrappers, and use an IDS or IPS. For CVE-2024-9138 and CVE-2024-9140, Moxa says to limit SSH access to trusted IP addresses in the same way.
Which embedded third-party components does Moxa list?
Moxa publishes separate advisories when a bundled open-source component is affected, and their fixed versions differ from those for Moxa's own code:
- NTP, MPSA-258681 (V1.1, 2026-07-13): CVE-2020-11868, an off-path attacker blocks unauthenticated NTP synchronization (7.5 per Moxa and NVD). Fixed in EDS-405A 3.17, EDS-408A 3.16, EDS-505A and EDS-508A 3.13, EDS-510A, EDS-516A, EDS-518A and EDS-P510A 3.14, EDS-G509 3.12 and the EDS-600 series 3.14. For all firmware of the EDS-E, ICS, IKS and SDS series there is no update: Moxa says to enable NTP authentication and synchronize only with trusted authenticated servers.
- OpenSSH, MPSA-256261 (V1.1, 2026-02-26): CVE-2023-38408, the ssh-agent PKCS#11 flaw, in EDS-4000 and EDS-G4000 firmware 4.1 and earlier (security patch 4.1.58) and RKS-G4000 5.0 and earlier (patch 5.0.4). Moxa rates the practical risk very low because its switches act as SSH servers and do not enable ssh-agent or agent forwarding.
- GoAhead web server, MPSA-154603: Moxa names the embedded GoAhead web server on the EDS-405A and EDS-408A as the component behind the denial of service CVE-2015-6465.
The OpenSSH guide and the NTP and chrony guide explain how these component flaws behave in embedded firmware.
How should KEV and EPSS shape the order of work?
No Moxa product appears in the CISA KEV catalog data as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries), and none of the CVEs above, including the NTP and OpenSSH ones, is listed. FIRST EPSS scores dated 2026-11-21 are highest for the analyzed older CVEs: CVE-2019-10969 at 0.10622, CVE-2019-6557 at 0.05014, CVE-2020-7007 at 0.02900 and CVE-2019-6524 at 0.02734. Among Moxa's own 2024 to 2026 CVEs, the highest are CVE-2024-9140 at 0.01765 and CVE-2024-9138 at 0.01147; CVE-2024-9137 scores 0.00501. The OpenSSH flaw CVE-2023-38408 scores 0.79700, but that reflects OpenSSH across all systems, and Moxa says its switches lack the agent forwarding the flaw needs.
EPSS is a probability of exploitation activity across all systems, not a statement about Moxa devices, so use it for ordering rather than dismissal. A practical order is:
- Any Moxa router or switch whose web server, SSH, Telnet, SNMP or Moxa Service ports (TCP 80, 443, 22, 23, 4000; UDP 161, 4000, 40404) are reachable from outside its zone or from the internet. Our BOD 23-02 guide on internet-exposed management interfaces explains why exposed admin consoles come first.
- EDR and TN-4900 routers below the fixes for unauthenticated takeover: CVE-2024-9140, CVE-2025-6950 and CVE-2024-9137.
- Switches below the CVE-2024-9137 and CVE-2024-12297 fixes, then the denial of service patches for CVE-2024-7695 and CVE-2024-9404, because a crashed switch stops its cell.
- Authenticated command injection (CVE-2024-9139, CVE-2025-0415, CVE-2025-0676), the 2026 router and switch fixes, then the component advisories.
The KEV and EPSS prioritization guide explains how to combine the two signals.
Why do Moxa NVD records need care?
Moxa's own CVEs from 2024 onward are hard to match by CVE data alone. As of 2026-11-22, CVE-2024-9137, CVE-2024-7695, CVE-2024-9404, CVE-2024-12297, CVE-2024-9138, CVE-2024-9140, CVE-2025-0415, CVE-2025-0676, CVE-2025-6892, CVE-2025-6893, CVE-2025-6949 and CVE-2025-6950 are Deferred in NVD, and CVE-2026-3867, CVE-2026-3868, CVE-2026-15579, CVE-2026-130493 and CVE-2026-130494 are Awaiting Analysis or Received. None has an NVD CPE configuration, and the only score is Moxa's. The older CVEs from CISA advisories are analyzed with CPE data.
Scores and references also disagree. CISA scores CVE-2019-6520 at 9.1 where NVD gives 7.5, and CVE-2020-6979 at 9.8 where NVD gives 7.5; Moxa scores CVE-2023-4452 at 6.5 where NVD gives 7.5. Moxa's 2024 and early 2025 advisories use CVSS 3.1 for severity with v4.0 as a reference, while later ones publish only v4.0. CVE-2024-9137 appears in two advisories with different product lists and fixes: MPSA-241154 for the routers (3.13) and MPSA-241156 for 53 switch series (security patches). Moxa's MPSA-221201 for a TN-4900 hard-coded credential (fixed in firmware 1.2) cites CVE-2008-1160, whose NVD text describes a hard-coded Quagga and Zebra password in the ZyXEL ZyWALL 1050, so a CVE-based match will mislabel it.
One fixed version needs a check with Moxa. The solution table in MPSA-241155 prints "firmware version 3.14 or later" for the EDR-810, EDR-G902 and EDR-G903 as well, although those series run 5.x firmware and the same advisory lists them as affected up to 5.12.37 and 5.7.25. MPSA-251431 lists EDR-810 5.12.41 as its fix and says EDR-G902 and EDR-G903 firmware 5.7.27 and earlier is not affected by CVE-2025-0676. Ask Moxa Technical Support which 5.x build fixes CVE-2024-9138 on your hardware.
How do you harden Moxa switches and routers per Moxa guidance?
Moxa's MX-ROS V3 manual has a security guidelines chapter, and the switch manual and advisories add to it. In order:
Place routers at zone boundaries and keep management insideThe MX-ROS V3 manual says to install the router in an access-controlled area at the boundary between zones. Moxa's advisories ask you to segregate operational networks from enterprise networks with VLANs or physical separation and to avoid exposing devices directly to the internet; the Purdue model guide shows where those zones sit. Switch off unused servicesDisable Moxa Service and Moxa Service (Encrypted) if your network management software does not need them, as MPSA-241156 and MPSA-240931 say. Use HTTPS instead of HTTP, SSH instead of Telnet, SFTP instead of TFTP and SNMPv3 instead of SNMPv1/v2c, as the MX-ROS V3 manual lists; MPSA-234880 and MPSA-154603 add disabling the web service after configuration until you can patch. Restrict management to known addressesEnable Trusted Access, which the switch manual describes as an IP address filter where only listed addresses can reach the switch, and limit web and SSH access with firewall rules or TCP wrappers as the router advisories say. Moxa also suggested Trusted Access as the stopgap for a hard-coded credential in EDR routers before firmware 5.10 (EDR-810) and 5.7 (EDR-G902 and EDR-G903). Replace default credentials and keysChange the moxa password at first login, give admin rights to as few people as possible and read-only access to others, enable the password policy, and regenerate the SSL certificate and SSH key before commissioning, as MPSA-268140 and both manuals advise. Verify firmware and authenticate timeBefore every update, check the firmware file against the SHA-512 checksum on Moxa's product page; enable NTP authentication with trusted servers. Update to the fixed build for each series and record itNote the full version, including security patch builds such as 6.4.8 or 5.5.255, because Moxa delivers many switch fixes only through Technical Support.
CISA's advisories add its standard measures: minimize network exposure, locate control system networks behind firewalls isolated from business networks, and use secure remote access such as VPNs that are kept updated.
What does a Moxa review of one plant network look like? (worked example)
Synthetic example, not a real site. A water treatment plant has one EDR-G9010 router on 3.14 between the plant and office networks, an older EDR-810 on 5.12.33 for a remote pump station, an ICS-G7528A backbone switch on 5.10, two EDS-G516E switches on 6.4 and one SDS-3008 on 3.0.
| Observation | Why it matters | Action |
|---|---|---|
| EDR-G9010 on 3.14, web interface reachable from the office network | Within CVE-2025-6950 (hard-coded JWT key), CVE-2025-0415, CVE-2025-0676 and CVE-2026-3868 ranges | Update to 3.24 or later, which is at or above the fixes in MPSA-258121, MPSA-259491, MPSA-251431 and MPSA-261521; allow management only from the engineering workstation |
| EDR-810 on 5.12.33 | Within CVE-2024-9139, CVE-2024-9138, CVE-2025-0415 and CVE-2025-0676 ranges | Update to 5.12.41 or later and confirm the CVE-2024-9138 fix build with Moxa |
| ICS-G7528A on 5.10 with Moxa Service enabled | Within CVE-2024-9137, CVE-2024-7695 and CVE-2024-9404; NTP flaw has no update for ICS | Request security patch 5.10.10, disable Moxa Service if unused, enable NTP authentication |
| EDS-G516E switches on 6.4 | Within CVE-2024-9137 (patch 6.4.8), CVE-2024-12297 (fixed in 6.5) and the weak TLS key exchange in MPSA-241044 | Update to 6.5 or later and ask Moxa whether that release includes the MPSA-241044 TLS patch |
| SDS-3008 on 3.0 | Within CVE-2024-9137 (patch 3.0.8) and CVE-2024-12297 (fixed in 3.1) | Update to 3.1 or later |
| Every switch and router still on its factory certificate | CVE-2026-130493 has no fix | Regenerate the SSL certificate and SSH key; verify SHA-512 checksums before each update |
Where does passive monitoring and component matching help?
A mirror-port capture shows who talks to the switches' and routers' management services without logging in to them. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from such a capture and builds a host-by-port inventory at connection level, including hosts reaching the devices on TCP 22, 23, 80, 443 and 4000 and UDP 161, 4000 and 40404, and it lists remote-access sessions (SSH, Telnet, RDP, VNC) that cross from outside the private address range. It has no decoder for the Moxa Service protocol and does not read firmware versions or configuration from traffic, so versions come from your asset list. For that list, Device & Firmware Security identifies components and versions and matches them against NVD, CISA KEV, FIRST EPSS and CISA ICS advisories. AI drafts a cited summary, and an engineer reviews it before delivery. For other vendors' network devices, see our Hirschmann and Belden switch guide and the Siemens SCALANCE and RUGGEDCOM guide.
What are the common pitfalls?
- Recording "EDS-G516E 6.4" when the device runs security patch 6.4.8: the base version is affected by CVE-2024-9137, the patch build is not.
- Treating the 5.x EDR-810, EDR-G902 and EDR-G903 like the 3.x MX-ROS V3 routers: fixed versions differ, and some CVEs affect only one line.
- Leaving the Moxa Service on TCP and UDP 4000 enabled on switches that no Moxa management software uses.
- Relying on NVD CPE matching for Moxa CVEs from 2024 onward, which have no CPE configuration as of 2026-11-22.
- Assuming a firmware update fixes CVE-2026-130493: the factory certificate must be regenerated on every device.
- Matching MPSA-221103 and MPSA-221201 by CVE ID, when one cites reserved IDs and the other a ZyXEL record.
This guide draws on Moxa security advisories MPSA-154603, MPSA-221103, MPSA-221201, MPSA-234880, MPSA-240163, MPSA-240931, MPSA-241021, MPSA-241044, MPSA-241154, MPSA-241155, MPSA-241156, MPSA-241407, MPSA-241409, MPSA-251431, MPSA-252620, MPSA-256261, MPSA-258121, MPSA-258681, MPSA-259491, MPSA-261521 and MPSA-268140, the Moxa Managed Ethernet Switch (UI 2.0, FW 5.x) and MX-ROS V3 user manuals, CISA ICS advisories ICSA-19-057-01, ICSA-19-274-03, ICSA-19-353-01, ICSA-20-056-04 and ICSA-20-196-02, and NVD records. KEV and EPSS facts are as of 2026-11-22. It is general information, not a substitute for Moxa's product-specific security guidance or a current advisory search for your exact hardware and firmware version.
Put this guide to work
Frequently asked questions
Are Moxa EDS switch or EDR router vulnerabilities in the CISA KEV catalog?
No. As of 2026-11-22, the CISA KEV catalog (version 2026.11.20, 1,790 entries) has no entry naming Moxa, and none of the switch or router CVEs in this guide is listed. FIRST EPSS scores dated 2026-11-21 are highest for older, analyzed CVEs such as CVE-2019-10969, the EDR-810 ping command injection, at 0.10622, and CVE-2019-6557, the EDS and IKS web buffer overflows, at 0.05014. Moxa's 2024 to 2026 router and switch CVEs all score below 0.02; the highest is CVE-2024-9140, the unauthenticated EDR and TN-4900 command injection, at 0.01765.
What is the default password on a Moxa EDS switch or EDR router?
Moxa's Managed Ethernet Switch user manual for UI 2.0 and firmware 5.x (version 2.8, November 2026) says the default password is moxa and asks you to change it after you first log in; the switch's default IP address is 192.168.127.253. The MX-ROS V3 user manual (version 1.18, October 2026) for the EDR-8010, EDR-G9004, EDR-G9010 and TN-4900 says the default username is admin and the default password is moxa, that the router's default LAN address is 192.168.127.254, and that you must change the password after logging in with the default credentials.
What is the Moxa Service and should it be disabled?
Moxa Service is the management channel for Moxa's network management software. The switch manual lists Moxa Service on TCP and UDP port 4000 and Moxa Service (Encrypted) on TCP 443 and UDP 40404; the MX-ROS V3 manual lists the encrypted Moxa Service on TCP 443 and UDP 40404, enabled by default. CVE-2024-9137 (missing authentication) and CVE-2024-9404 (denial of service through moxa_cmd) are reached through it, and Moxa's switch advisories tell you to disable Moxa Service and Moxa Service (Encrypted) if they are not required, until the security patch is applied.
Is there a fix for CVE-2026-130493 and CVE-2026-130494 on Moxa switches?
No firmware fix. Moxa advisory MPSA-268140 (2026-11-20) lists all firmware versions of the EDS-E, EDS-A, ICS, IKS, SDS, PT, TWS and TN switch series as affected and points only to mitigations. For CVE-2026-130493, the device by default issues a self-signed certificate from an RSA-1024 private key embedded in Moxa's public firmware, so regenerate the SSL certificate and SSH key before commissioning and renew them often. For CVE-2026-130494, the switch does not verify a firmware signature, so check every firmware file against the SHA-512 checksum on Moxa's product page before you install it.
Why does my scanner miss the 2024 to 2026 Moxa CVEs?
As of 2026-11-22, every Moxa CVE from 2024 onward in this guide is Deferred, Awaiting Analysis or Received in NVD, with no NVD CPE configuration, and the only score is Moxa's own as the CVE Numbering Authority. A scanner that matches NVD CPE data will not flag them. Match the device's product series and full firmware version against the tables in the Moxa advisory instead, and record patch builds such as 6.4.8 or 5.5.255 exactly, because Moxa ships many fixes as security patches that you request from Moxa Technical Support.
Sources
- Moxa MPSA-268140: CVE-2026-130493, CVE-2026-130494 Multiple Vulnerabilities in Ethernet Switches (V1.0, 2026-11-20)
- Moxa MPSA-261521: CVE-2026-3867, CVE-2026-3868 in Secure Router (V1.2)
- Moxa MPSA-252620: CVE-2026-15579 Out-of-bounds Write Vulnerability in Ethernet Switch (V1.0)
- Moxa MPSA-258121: CVE-2025-6892, CVE-2025-6893, CVE-2025-6894, CVE-2025-6949, CVE-2025-6950 in Network Security Appliances and Routers (V1.1)
- Moxa MPSA-259491: CVE-2025-0415 Command Injection Leading to Denial-of-Service (V1.5)
- Moxa MPSA-251431: CVE-2025-0676 Command Injection Leading to Privilege Escalation (V1.5)
- Moxa MPSA-241155: Privilege Escalation and OS Command Injection Vulnerabilities (CVE-2024-9138, CVE-2024-9140, V1.4)
- Moxa MPSA-241154: Missing Authentication and OS Command Injection Vulnerabilities in Routers (CVE-2024-9137, CVE-2024-9139, V1.3)
- Moxa MPSA-241156: CVE-2024-9137 Missing Authentication Vulnerability in Ethernet Switches (V1.1)
- Moxa MPSA-240163: CVE-2024-7695 Out-of-bounds Write in Multiple EDS, ICS, IKS and SDS Switches (V1.1)
- Moxa MPSA-240931: CVE-2024-9404 Denial-of-Service in Multiple EDS, ICS, IKS and SDS Switches (V1.3)
- Moxa MPSA-241407: CVE-2024-12297 Frontend Authorization Logic Disclosure in EDS-508A Series and other switches (V1.2)
- Moxa MPSA-241409: CVE-2024-12297 Frontend Authorization Logic Disclosure in Ethernet Switches (V1.1)
- Moxa MPSA-258681: CVE-2020-11868 NTP Vulnerability in Ethernet Switches (V1.1)
- Moxa MPSA-256261: CVE-2023-38408 OpenSSH Vulnerability in Ethernet Switches (V1.1)
- Moxa MPSA-234880: EDR-810/G902/G903 Series Web Server Buffer Overflow Vulnerability (CVE-2023-4452)
- Moxa MPSA-221103: Multiple Routers Improper Input Validation Vulnerabilities
- Moxa MPSA-241021: Security Enhancements in the EDS-P510 Series (Modbus/TCP access, device identification, unencrypted Telnet)
- Moxa MPSA-154603: EDS-405A/408A Series Multiple Web Vulnerabilities
- Moxa Managed Ethernet Switch (UI 2.0, FW 5.x) User Manual, version 2.8, November 2026
- Moxa MX-ROS V3 User Manual, version 1.18, October 2026
- CISA CSAF: ICSA-19-057-01 Moxa IKS, EDS (Update A)
- CISA CSAF: ICSA-20-056-04 Moxa EDS-G516E and EDS-510E Series Ethernet Switches
- CISA CSAF: ICSA-19-353-01 Moxa EDS Ethernet Switches (CVE-2019-19707)
- CISA CSAF: ICSA-20-196-02 Moxa EDR-G902 and EDR-G903 Series Routers
- CISA CSAF: ICSA-19-274-03 Moxa EDR 810 Series
- NVD: CVE-2024-9140 (EDR and TN-4900 OS command injection)
- NVD: CVE-2024-9137 (Moxa Service missing authentication)
- NVD: CVE-2008-1160 (record cited by Moxa MPSA-221201)
- CISA Known Exploited Vulnerabilities catalog data (kev-data)
- FIRST: Exploit Prediction Scoring System (EPSS) data
About this guide
SoftWSP OT/ICS Desk
Covers the OT/ICS security cluster: 87 guides.