Emerson vulnerabilities: DeltaV DCS, Ovation, ROC800 and FloBoss RTUs and ControlWave, fixed versions and hardening

Last updated:

Emerson's DeltaV distributed control system, Ovation DCS, ROC800 and FloBoss RTUs and flow computers, and ControlWave RTUs had no CVE in CISA's KEV catalog as of 2026-11-23, but their published flaws fall into four main families: unauthenticated control and engineering protocols, hard-coded or weak credentials, unsigned firmware, and file, DLL and privilege weaknesses on Windows workstations. Most fixes sit behind Emerson's login portals, so CISA's ICS advisories are the main public record. The newest set, CISA's 2024 Ovation advisory, had its two CVEs published on CVE.org only on 3 November 2026.

The rest of this guide maps the products to their place in a plant or pipeline network, explains the engineering and communication paths the advisories name, walks through the CVEs by product with the fixed versions and mitigations Emerson and CISA give, and ends with hardening, monitoring and a worked example. Every score below names its scorer: CISA's score and NVD's Primary score for the same CVE often differ, in both directions.

Key takeaways

  • CISA's advisories list Emerson as headquartered in the United States with worldwide deployment.
  • Port 20547 is the only port number that CISA or Emerson names in the advisories used here.
  • DeltaV advisories run from 2014 to 2022.
  • CVE-2022-29966: several protocols have no authentication, so an attacker can change controller configuration or cause a denial of service.

Where do DeltaV, Ovation, ROC and ControlWave sit in OT networks?

CISA's advisories list Emerson as headquartered in the United States with worldwide deployment. The 2024 Ovation advisory names the energy sector; the DeltaV and ROC advisories say "multiple sectors"; the ControlWave and OpenBSI advisories name oil and gas, petrochemical, chemical, life sciences, and water and wastewater. The product names in the advisories fall into five groups:

Group Products named in advisories Typical place in the network
DeltaV DCS workstations and servers DeltaV workstations running v11.3.1 to v14 and R5/R6, the Easy Security Management application, the Smart Switch Command Center Supervisory level: Windows computers for operation, engineering and configuration
DeltaV controllers and I/O M-series, S-series and P-series controllers, DeltaV SIS, CIOC, EIOC and WIOC I/O cards, the SE4801T0X and SE4801T1X Wireless I/O Cards, DeltaV Smart Switches Control and safety level, on the DeltaV control network
Ovation DCS Ovation software up to 3.8.0 Feature Pack 1, OCR400 controllers, OCR3000 controllers as a recommended replacement, Ovation Developer Studio and Ovation HMIs Power generation and water plants, on the Ovation Highway control network
Remote automation: RTUs and flow computers ROC800 (ROC809, ROC827), ROC800L, DL8000 preset controllers, FloBoss 107 flow computers, ControlWave and ControlWave Micro RTUs Remote sites such as wellheads, pipeline stations and terminals, often reached over WAN or radio links
Remote automation engineering and SCADA ROCLINK 800 configuration software, OpenBSI engineering tools for ControlWave and Bristol Babcock RTUs, OpenEnterprise SCADA server Control centre and engineering workstations that poll and configure the RTUs

DeltaV SIS appears in the 2022 DeltaV advisory alongside the basic process controllers, so the IEC 61511 safety instrumented systems guide applies to it. For the zoning model behind the table, see the Purdue model guide.

How are Emerson systems managed and reached?

The engineering and communication paths that the advisories name are the attack paths:

Path Products What the sources say
DeltaV proprietary protocols (firmware upgrade, plug-and-play, Hawk services, management, SIS communications, multicast) DeltaV controllers, SIS and I/O cards No authentication, so anyone who has reverse-engineered the traffic can invoke functions or cause a denial of service (CVE-2022-29957)
FTP, read-only Telnet and SSH services DeltaV controllers and I/O cards; WIOC Hard-coded credentials; CISA notes FTP and SSH are disabled by default (CVE-2022-29962 to CVE-2022-29964)
Maintenance port DeltaV controllers Challenge-response with a deterministic algorithm (CVE-2022-29965); authentication bypass by script (CVE-2018-19021)
Ovation controller protocols and FTP Ovation, OCR400 Unauthenticated protocols (CVE-2022-29966); FTP buffer overflows when communication services are enabled (CVE-2019-10965, CVE-2019-10967)
ROC and ROC Plus protocols ROC800, ROC800L, DL8000, FloBoss File read, write and delete over the protocol (CVE-2022-30264); before Emerson's enhanced security, passwords were sent in clear text
BSAP-IP firmware download ControlWave Firmware images have no signature, only checksums (CVE-2022-30262)
Port 20547 ControlWave Micro Crafted packets halt the controller (CVE-2018-5452, ICSA-18-058-03)

Port 20547 is the only port number that CISA or Emerson names in the advisories used here. The 2022 DeltaV and ROC CVE records, written by MITRE as the assigning CNA, list further TCP and UDP ports for the proprietary protocols. Confirm those against Emerson's DeltaV Security Manual or a capture before you build firewall rules on them. The BOD 23-02 guide on internet-exposed management interfaces shows how to test whether any of these interfaces are reachable from outside.

Which DeltaV vulnerabilities did CISA publish?

DeltaV advisories run from 2014 to 2022. Emerson's own DeltaV Security Notifications (DSN numbers) and knowledge base articles sit on its Guardian Support Portal, which needs a login; CISA's advisories quote the DSN and KBA numbers.

CVE Weakness CISA CVSS v3 NVD Primary Fix or mitigation named
CVE-2022-29957 Missing authentication in proprietary protocols 6.8 v3.1 7.8 No separate fix in the advisory; details on Guardian
CVE-2022-29962 Hard-coded credentials, FTP service 4.2 v3.1 5.5 Mitigated in all supported DeltaV versions
CVE-2022-29963 Hard-coded credentials, read-only Telnet 1.8 v3.1 5.5 Same
CVE-2022-29964 Hard-coded credentials, SSH service (WIOC) 4.2 v3.1 5.5 Same
CVE-2022-29965 Deterministic maintenance-interface password algorithm 8.8 v3.1 5.5 Corrected in all supported versions
CVE-2022-30260 Unsigned firmware, insecure checksums 6.3 (text) v3.1 7.8 Corrected in v14.3, mitigated in other versions
CVE-2021-26264 Script restarts a controller (denial of service) 6.1 v3.1 5.5 Patches for 13.3.1, 14.LTS, 14.FP1, 14.FP2 and R6 (DSN21008)
CVE-2021-44463 Missing DLLs replaced by an insider (privilege escalation) 8.1 v3.1 7.3 Same
CVE-2018-19021 Maintenance-port authentication bypass (denial of service) 8.8 v3.1 6.5 Patches for 11.3.1, 11.3.2, 12.3.1, 13.3.1, 14.3, R5.1 and R6
CVE-2018-11691 Smart Switch management password never changed from default 6.1 v3.0 9.8 Workstation patch (DSN19003); 13.3 and later use Network Device Command Center
CVE-2018-14793 Stack buffer overflow through an open communication port 9.6 v3.0 8.8 Patch (DSN18003) for 11.3.1, 12.3.1, 13.3.0, 13.3.1 and R5
CVE-2018-14795 Path traversal lets an attacker replace executables 8.8 v3.0 8.8 Same
CVE-2018-14791 Non-administrators can change executables and libraries 8.2 v3.1 7.8 Same
CVE-2018-14797 DLL search-path hijacking 8.2 v3.1 7.8 Same
CVE-2016-9345 Easy Security Management privilege escalation 6.8 v3.0 6.8 Uninstall the application (KBA NK-1600-0336)
CVE-2016-9347 SSH enabled unnecessarily on Wireless I/O Cards v13.3 5.0 v3.0 5.0 Hotfix DeltaV_133_WIOC_02_CSS (KBA NK-1500-0152)
CVE-2014-2350 Hard-coded credentials for diagnostic services v2 2.4 v2 7.5 Patch per KBA NK-1400-0031 for 10.3.1 to 12.3
CVE-2014-2349 Engineering-level users can read or modify configuration files v2 6.2 v2 4.6 Same

Three notes on the table. For the two 2014 CVEs the CISA column gives CISA's CVSS v2 score from the CVE record, since that advisory has no v3 score. CISA's CSAF for ICSA-22-181-03 puts 4.2 in the structured score for CVE-2022-30260 while its text says 6.3; the table uses the text. NVD's 9.8 for CVE-2018-11691 is far above CISA's 6.1, because CISA scores it from the adjacent network with high privileges. And the CVE.org record for CVE-2014-2349 repeats the hard-coded credential text of CVE-2014-2350, while CISA's advisory describes it as local configuration file access; CISA's description is used here.

For the 2018 workstation flaws, ICSA-18-228-01 adds that CVE-2018-14791, CVE-2018-14795 and CVE-2018-14797 cannot be exploited when application whitelisting is in place, because it stops the files from being overwritten. The hard-coded credentials fix guide explains why the 2014 and 2022 credential CVEs keep coming back in controller firmware.

What are the Ovation DCS vulnerabilities?

CISA's ICSA-24-158-02 of 6 June 2024 covers Ovation up to 3.8.0 Feature Pack 1 and credits Daniel dos Santos and Jos Wetzels of Forescout Technologies:

  • CVE-2022-29966: several protocols have no authentication, so an attacker can change controller configuration or cause a denial of service. CISA scores it CVSS v3.1 9.8 and v4 9.3.
  • CVE-2022-30267: firmware has no signature and relies on an insecure checksum, so an attacker can push malicious firmware, cause a denial of service or run code. CISA scores it v3.1 7.5 and v4 8.7.

Both CVE records were published on CVE.org on 3 November 2026, and as of 2026-11-23 NVD had no Primary score for either. Emerson's recommendations in the advisory are to upgrade to Ovation 3.8.0 Feature Pack 3, to consider OCR3000 controllers, which "offer an extra layer of protection that is not available to older controller models", to follow the Cybersecurity for Ovation Systems manual (OVREF1000), and to contact Ovation-CERT with questions.

The older Ovation advisory, ICSA-19-148-01, covers two buffer overflows in the third-party FTP server embedded in OCR400 controllers running Ovation 3.3.1 or earlier: CVE-2019-10965 (heap overflow on a long command; CISA 6.8, NVD v3.1 8.8) and CVE-2019-10967 (stack overflow on a long file name in LIST; CISA 6.3, NVD v3.1 8.8). The advisory's version split is useful for triage:

  • OCR161 controllers are not affected.
  • Ovation 3.0.4 and older: FTP cannot be disabled through communication services; Emerson recommends upgrading and limiting FTP, Telnet, rlogin and SSH with access control lists on Cisco 2960 or 3750 Ovation Highway switches.
  • Ovation 3.1.0 to 3.3.1: check "Comm Services" in Ovation Developer Studio or the Controller Diagnostics application and set it to Disabled on both primary and secondary controllers.
  • Ovation 3.5.0 and newer: FTP communication services cannot be enabled, so the advisory does not apply.

Which ROC800, FloBoss and DL8000 flaws matter most?

The remote automation line has the oldest and the highest-scored flaws in this guide. CISA's ICSA-13-259-01B covers five CVEs in ROC800 software 3.50 and earlier, DL8000 2.30 and earlier and ROC800L 1.20 and earlier:

CVE Weakness NVD Primary CVSS v2 FIRST EPSS (2026-11-22)
CVE-2013-2810 Arbitrary commands via a TCP replay attack 10.0 0.060
CVE-2013-0689 TFTP server allows file upload and code execution 10.0 0.050
CVE-2013-0692 ENEA OSE kernel debug service allows code execution 10.0 0.049
CVE-2013-0693 Network-beacon broadcasts reveal device presence 10.0 0.033
CVE-2013-0694 Hard-coded credentials in ROM give OS shell access 9.0 0.026

The advisory's fix is a vendor patch from Emerson's support site. As an added mitigation, Emerson tested and verified a Moxa EDR-810 secure router with IPsec between the host and the field device.

Two later advisories followed:

  • CVE-2022-30264 (ICSA-22-223-04, Forescout): the ROC protocol lets a master terminal read, write and delete files and folders on the flash file system. CISA scores it 6.3; NVD's Primary score is v3.1 9.8. CISA lists all versions of ROC800, ROC800L and DL8000, and Emerson points to section 1.11 "Secure Gateway" of the ROC800-Series instruction manual (D301766X012). NVD's description also names the FloBoss line.
  • CVE-2023-1935 (ICSA-23-206-03, reported by Emerson): an authentication bypass in ROC800-Series RTUs that can give access to data or control of the device, scored 9.4 by both CISA and NVD. The fixes are ROC800 Series 2 firmware 3.91 or later, ROC800L Series 2 firmware 1.71 or later and DL8000 Series 2 firmware 2.60 or later, from SupportNet. Series 1 ROC800 and DL8000 hardware, obsolete since 2008, must be replaced with Series 2.

Emerson's Security Deployment Guide for ROC800-Series and FloBoss 107 (D301912X012, March 2023) describes the enhanced security that Emerson released after the TSA pipeline Security Directive Pipeline-2021-02. It needs ROC800 firmware 3.90, ROC800L firmware 1.70 or FloBoss 107 firmware 2.00, together with ROCLINK 800 2.71. Once an owner opts in, user names can be 3 to 30 characters, passwords 8 to 32 characters, and passwords are no longer sent in clear text over the ROC, ROC Plus and Liquids protocols. The guide warns that opting in cannot be reversed, that third-party SCADA and HMI drivers must support the new protocols first, that the FloBoss 107 change removes legacy point types 6, 7, 10 and 41, and that security must be enabled on each comm port. The TSA pipeline security directives guide covers the directive itself.

What about ControlWave, OpenBSI and OpenEnterprise?

ControlWave RTUs and their engineering and SCADA software appear in four advisories:

  • CVE-2018-5452 (ICSA-18-058-03, Nozomi Networks): a stack overflow in ControlWave Micro firmware CWM 05.78.00 and earlier, triggered by crafted packets on port 20547, puts the controller in halt mode. CISA and NVD score it 7.5. The fix is firmware 05.79.00.
  • CVE-2022-30262 (ICSA-22-221-02): ControlWave firmware images sent over BSAP-IP are not signed. CISA scores it 9.1; NVD's Primary score is 7.8. Emerson's mitigations are the hardware switch that blocks remote firmware download, setting the system variable _APPLICATION_LOCKED to TRUE, and checking the MD5 or SHA256 hashes published on SupportNet before installing firmware.
  • CVE-2022-29960 (ICSA-22-221-03): OpenBSI 5.9 SP3 and earlier, the engineering environment for ControlWave and Bristol Babcock RTUs, protects credentials, engineering files and utilities with DES and hard-coded keys. CISA scores it 8.1; NVD says 5.5. Emerson's advice is to stop using the OpenBSI User Management Tool, back up and delete SecUsers.ini, delete UserMngtTool.exe, keep OpenBSI hosts and RTUs off the internet, and follow section 6.1 of the OpenBSI Utilities Manual (D301414x012).
  • CVE-2020-6970 (ICSA-20-049-02): a heap overflow in the OpenEnterprise SCADA server lets a crafted script run code. It affects OpenEnterprise 2.83 when the Modbus or ROC interfaces are installed and in use, and 3.1 through 3.3.3. CISA scores it 8.1; NVD says 9.8. The fix is OpenEnterprise 3.3 Service Pack 4 (3.3.4).

OpenEnterprise polls RTUs over Modbus as well as ROC, so the Modbus protocol security guide applies to the same links.

Which other Emerson products have advisories worth knowing?

Two field-level advisories touch the same plants:

  • CVE-2020-12030 (advisory page): enabling VLAN on Wireless 1410, 1420 and 1552WU WirelessHART gateways with revisions 4.6.43 to 4.7.84 disables the internal firewall. CISA and NVD score it 10.0. Emerson asks owners to update the firmware on VLAN-enabled Version 4 gateways; without VLAN, no immediate action is needed (Emerson notification EMR.RMT20001-1).
  • CVE-2014-9191 (advisory page): a HART DTM library flaw lets a rogue device on the 4-20 mA loop hang the FDT frame application. NVD's Primary score is v2 2.1. Emerson updated the affected HART DTM to version 1.4.181.

The HART and WirelessHART security guide covers the protocol side of both.

How do you harden Emerson DeltaV, Ovation and ROC systems?

Work from the vendor's and CISA's own mitigations:

  1. Bring DeltaV to a supported release with current patchesEmerson mitigated the 2022 credential flaws "in all currently supported versions" and corrected firmware verification in v14.3; older releases need the DSN patches listed above.
  2. Enable application whitelisting on DeltaV workstations, which CISA says blocks the 2018 file-replacement CVEs.
  3. Move Ovation to 3.8.0 Feature Pack 3, consider OCR3000 controllers, and on Ovation 3.1.0 to 3.3.1 keep controller communication services disabled.
  4. Update ROC800, ROC800L and DL8000 Series 2 firmwareto 3.91, 1.71 and 2.60 or later, replace Series 1 hardware, and opt into enhanced security after checking SCADA driver support.
  5. Lock ControlWave firmware downloadwith the hardware switch or _APPLICATION_LOCKED, and check firmware hashes before every load.
  6. Retire the OpenBSI User Management Tooland remove SecUsers.ini as Emerson describes.
  7. Commission or re-password DeltaV Smart Switchesafter the DSN19003 patch, as the CVE-2018-11691 record says owners must do.
  8. Firewall the control networkCISA asks owners to keep control system devices off the internet, put control networks and remote devices behind firewalls isolated from business networks, and use VPNs for remote access, keeping the VPN itself updated.

Plan these updates through a change process such as the one in the IEC 62443-2-3 patch management guide. If you bridge DCS data to site systems over OPC UA, the OPC UA security guide covers the security modes to require on that boundary.

How do you check which version an Emerson system runs?

Emerson's fixes depend on release, feature pack, controller model and hardware series, so record each one:

  1. Record the DeltaV release per workstation and controller, including LTS or feature pack (14.LTS, 14.FP1, 14.FP2), since the 2021 patches list each one.
  2. Record controller and I/O card typesM-series and SIS nodes carry the maintenance-port flaw; S-series, P-series and CIOC/EIOC carry the Telnet credential; WIOC carries the SSH credential.
  3. Record the Ovation controller model and software versionOCR400 on 3.1.0 to 3.3.1 needs a Comm Services check; OCR161 and 3.5.0 or later do not.
  4. Record ROC and DL8000 hardware series and firmwareSeries 1 units cannot be fixed by firmware.
  5. Do not rely on CPE matching aloneAs of 2026-11-23, NVD's CPE configuration for CVE-2018-11691 names only Smart Switch firmware VE6046 09.0.12, not the DeltaV 11.3.x and 12.3.1 workstations that need the patch, and the two Ovation CVEs had no NVD analysis. Read the advisories.

How do you monitor Emerson control networks?

Start with a baseline of which hosts talk to each workstation, controller and RTU, and on which ports, then alert on changes:

  • New hosts on the DeltaV control network, since CVE-2022-29957, CVE-2022-29965 and CVE-2021-26264 need an adjacent attacker.
  • FTP, Telnet or SSH sessions to DeltaV controllers, I/O cards or Ovation controllers, which fit the 2019 and 2022 credential and FTP flaws.
  • Connections to ControlWave Micro on port 20547 from anything other than the engineering and SCADA hosts, which fits CVE-2018-5452.
  • ROC protocol sessions to RTUs from hosts other than the SCADA master and ROCLINK 800 workstations, which fits CVE-2022-30264 and CVE-2023-1935.
  • Firmware download sessions outside a change window, which fit CVE-2022-30260, CVE-2022-30262 and CVE-2022-30267.

Flow records show who connected to which port and when, not which ROC opcode or DeltaV function was used. Map alerts to MITRE ATT&CK for ICS techniques such as remote services and system firmware.

Worked example: what does a review of a gas plant and pipeline find?

Synthetic example, not a real site. A gas processing plant runs DeltaV v13.3.1 with S-series controllers and a WIOC, a separate Ovation 3.3.1 system on the power island with OCR400 controllers, and twelve ROC800 RTUs at compressor and meter stations polled by OpenEnterprise 3.3.3.

Observation Why it matters Action
DeltaV v13.3.1 without the DSN21008 patch CVE-2021-26264 and CVE-2021-44463 are open; the 2022 credential flaws need a supported release Apply DSN21008; plan the move to a supported release
No application whitelisting on DeltaV workstations The 2018 file-replacement flaws remain exploitable Enable whitelisting, as ICSA-18-228-01 notes
Ovation 3.3.1 with Comm Services enabled on two OCR400 drops CVE-2019-10965 and CVE-2019-10967 are reachable Disable Comm Services; schedule Ovation 3.8.0 FP3
Four ROC800 units are Series 1 No firmware fix for CVE-2023-1935 Replace with Series 2 on 3.91 or later
ROC800 Series 2 on 3.90, enhanced security not enabled Passwords cross the WAN in clear text Update to 3.91, confirm OpenEnterprise driver support, then opt in
OpenEnterprise 3.3.3 CVE-2020-6970 is open Install 3.3 Service Pack 4

Where does passive monitoring fit in an Emerson review?

A passive capture shows who talks to workstations, controllers and RTUs without logging in to anything. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from a mirror-port recording and builds a host-by-port inventory at connection level, including FTP, Telnet, SSH and Modbus sessions and hosts using port 20547, and lists remote-access sessions that cross from outside the private address range. It does not decode DeltaV, Ovation, ROC or BSAP messages or read firmware versions from traffic. Component and version identification comes from the asset records and exports you share. SoftWSP matches the versions found against CVE, CISA KEV and FIRST EPSS data, and an engineer reviews the AI-written summary before it reaches you.

What are the common pitfalls?

  • Taking "mitigated in all currently supported versions" to cover an unsupported DeltaV release still in service.
  • Updating ROC800 firmware but never opting into enhanced security, so passwords stay in clear text.
  • Opting into ROC enhanced security before the SCADA or HMI driver supports it, which Emerson warns against.
  • Assuming one score: NVD rates CVE-2018-11691 at 9.8 where CISA says 6.1, and CISA rates CVE-2022-29965 at 8.8 where NVD says 5.5.
  • Reading only NVD for Ovation, when the 2024 advisory's CVEs had no NVD score as of 2026-11-23.
  • Leaving remote firmware download open on ControlWave RTUs when a hardware switch can block it.

This guide draws on CISA ICS advisories ICSA-13-259-01B, ICSA-14-133-02, ICSA-15-008-01A, ICSA-16-334-02, ICSA-16-334-03, ICSA-18-058-03, ICSA-18-228-01, ICSA-19-010-01, ICSA-19-148-01, ICSA-19-190-01, ICSA-20-049-02, ICSA-20-135-02, ICSA-21-355-04, ICSA-22-181-03, ICSA-22-221-02, ICSA-22-221-03, ICSA-22-223-04, ICSA-23-206-03 and ICSA-24-158-02 and their CSAF records, Emerson's Trust Center and ROC800/FloBoss 107 Security Deployment Guide, NVD and CVE.org records, CISA KEV and FIRST EPSS, all checked as of 2026-11-23.

Put this guide to work

Frequently asked questions

Are any Emerson DeltaV, Ovation or ROC vulnerabilities in the CISA KEV catalog?

No. As of 2026-11-23, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.20, 1,790 entries) has no entry with Emerson as the vendor, and none of the 35 CVEs in this guide is listed. The highest FIRST EPSS scores among them, dated 2026-11-22, belong to the 2013 ROC800 flaws: CVE-2013-2810 at 0.060 and CVE-2013-0689 at 0.050. Every other CVE here is below 0.037.

What did the 2022 Forescout research find in DeltaV, ROC and ControlWave?

Daniel dos Santos and Jos Wetzels of Forescout Technologies reported flaws that CISA published in June and August 2022: unauthenticated DeltaV protocols for firmware upgrade, plug-and-play, management and SIS communications (CVE-2022-29957), hard-coded FTP, Telnet and SSH credentials in DeltaV controllers and I/O cards (CVE-2022-29962 to CVE-2022-29964), a weak maintenance-port password algorithm (CVE-2022-29965), unsigned firmware in DeltaV and ControlWave (CVE-2022-30260, CVE-2022-30262), file operations over the ROC protocol (CVE-2022-30264) and hard-coded DES keys in OpenBSI (CVE-2022-29960). The same researchers are credited in CISA's 2024 Ovation advisory.

Which firmware fixes the ROC800 authentication bypass CVE-2023-1935?

CISA's ICSA-23-206-03 lists ROC800 Series 2 firmware 3.91 or later, ROC800L Series 2 firmware 1.71 or later and DL8000 Series 2 firmware 2.60 or later, all from Emerson's SupportNet portal. Series 1 ROC800 and DL8000 units became obsolete in 2008 and need a hardware change to Series 2. Emerson also asks owners to check the MD5 or SHA256 hashes it publishes before loading firmware.

What should Ovation owners do about the 2024 advisory?

CISA's ICSA-24-158-02 covers Ovation up to 3.8.0 Feature Pack 1. Emerson recommends upgrading to Ovation 3.8.0 Feature Pack 3, considering OCR3000 controllers for their extra protection, and deploying the system as described in its Cybersecurity for Ovation Systems manual (OVREF1000). The two CVEs, CVE-2022-29966 for unauthenticated protocols and CVE-2022-30267 for unsigned firmware, were published on CVE.org only on 3 November 2026 and had no NVD Primary score as of 2026-11-23.

Where does Emerson publish its security advisories?

Emerson's Trust Center lists a small set of public security notifications and points to brand-level channels: Guardian for DeltaV and AMS, the Ovation cybersecurity notifications and SupportNet for the remote automation products. Those channels need a login, so CISA's ICS advisories and their CSAF files are the main public record for most of the CVEs in this guide.

Sources

  1. Emerson Trust Center: security advisories and brand-level security notifications
  2. Emerson: Security Deployment Guide for ROC800-Series and FloBoss 107 (D301912X012, March 2023)
  3. CISA CSAF: ICSA-22-181-03 Emerson DeltaV Distributed Control System
  4. CISA CSAF: ICSA-21-355-04 Emerson DeltaV
  5. CISA CSAF: ICSA-19-190-01 Emerson DeltaV Distributed Control System
  6. CISA CSAF: ICSA-19-010-01 Emerson DeltaV
  7. CISA CSAF: ICSA-18-228-01 Emerson DeltaV DCS Workstations
  8. CISA CSAF: ICSA-16-334-02 Emerson DeltaV Easy Security Management Application
  9. CISA CSAF: ICSA-16-334-03 Emerson DeltaV Wireless I/O Card Open SSH Port
  10. CISA CSAF: ICSA-14-133-02 Emerson DeltaV Vulnerabilities
  11. CISA CSAF: ICSA-24-158-02 Emerson Ovation
  12. CISA CSAF: ICSA-19-148-01 Emerson Ovation OCR400 Controller
  13. CISA CSAF: ICSA-23-206-03 Emerson ROC800 Series RTU and DL8000 Preset Controller
  14. CISA CSAF: ICSA-22-223-04 Emerson ROC800, ROC800L and DL8000
  15. CISA CSAF: ICSA-13-259-01B Emerson ROC800 Multiple Vulnerabilities (Update B)
  16. CISA CSAF: ICSA-22-221-02 Emerson ControlWave
  17. CISA CSAF: ICSA-22-221-03 Emerson OpenBSI
  18. CISA CSAF: ICSA-18-058-03 Emerson ControlWave Micro Process Automation Controller
  19. CISA CSAF: ICSA-20-049-02 Emerson OpenEnterprise
  20. CISA CSAF: ICSA-20-135-02 Emerson WirelessHART Gateway
  21. CISA CSAF: ICSA-15-008-01A Emerson HART DTM Vulnerability
  22. NVD: CVE-2022-29957 (DeltaV unauthenticated protocols)
  23. NVD: CVE-2022-30264 (ROC and FloBoss file operations over the ROC protocol)
  24. NVD: CVE-2023-1935 (ROC800-Series authentication bypass)
  25. NVD: CVE-2018-11691 (DeltaV Smart Switch default management password)
  26. CVE.org: CVE-2022-29966 (Ovation unauthenticated protocols)
  27. CVE.org: CVE-2022-30267 (Ovation firmware integrity)
  28. CISA Known Exploited Vulnerabilities catalog
  29. FIRST: Exploit Prediction Scoring System (EPSS)
Was this guide helpful?

In this cluster

EtherCAT security: no native authentication in the wire protocol, and what fills the gapEtherCAT's base protocol (ETG.1000, IEC 61158 Type 12) carries no authentication or encryption of its own — security depends on hardware frame processing, a closed topology, and now an IEC 62443-3-3 Security Level 2 certification layered on top. What academic MITM research and the one confirmed CISA advisory touching EtherCAT actually found.EtherNet/IP and CIP Security: why Rockwell's most-deployed protocol still ships unauthenticated by defaultEtherNet/IP and the Common Industrial Protocol (CIP) it carries run a large share of North American discrete manufacturing, and CIP has no authentication unless a site explicitly deploys ODVA's CIP Security extension. What CIP Security's five profiles actually add, what a 2021-to-2026 run of Rockwell Automation CISA advisories shows about real failures, and the controls that compensate where it isn't deployed.GE Vernova UR relay vulnerabilities: the 2025 CVE chain, explainedNozomi Networks disclosed five 2025 CVEs in GE Vernova's UR protection-relay family and EnerVista UR Setup software, two of which chain into a man-in-the-middle-to-malicious-firmware attack.HART and WirelessHART protocol security: what's protected, and what still isn'tHART runs over a 4-20mA loop with no authentication at all; WirelessHART (IEC 62591) added mandatory AES-128 encryption and key management. What CISA advisories on HART DTMs and WirelessHART gateways show about where the real risk sits.