CVE-2014-9191 is a denial of service in the CodeWrights HART DTM library: a rogue device on the 4-20 mA current loop sends crafted HART responses and the DTM stops, hanging the FDT frame application on the engineering workstation. CISA names Emerson Rosemount, Micro Motion and Fisher device DTMs and Endress+Hauser device DTMs. NVD scores it CVSS v2 2.1.
Vulnerability summary
CVSS base score
2.1
Low severity
EPSS score (FIRST)
0.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2014-9191 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| CodeWrights HART Device Type Manager (DTM) library | cpe:2.3:a:codewrights:hart_device_type_manager:*:*:*:*:*:*:*:* | NVD CPE: up to and including 1.0.44; NVD description: Emerson HART DTM before 1.4.181 |
| Emerson HART DTMs for Rosemount, Micro Motion and Fisher field devices | — | 57 device and revision entries in CISA ICSA-15-008-01A; fixed by Emerson HART DTM 1.4.181 (Rosemount 644 Rev. 8 DTM, 2014-11-17) |
| Endress+Hauser HART device DTMs | — | Device DTM list in CISA ICSA-15-237-01; update HART DTM library to 2.41 and FieldCare to 2.10 |
What does this mean for affected devices?
NVD's description of CVE-2014-9191 says the CodeWrights HART Device Type Manager (DTM) library in Emerson HART DTM before 1.4.181 "allows physically proximate attackers to cause a denial of service (DTM outage and FDT Frame application hang) by transmitting crafted response packets on the 4-20 mA current loop." NVD's only Primary metric is CVSS v2 2.1 (low), vector AV:L/AC:L/Au:N/C:N/I:N/A:P, with CWE-399; the record has no CVSS v3 score (checked 2026-11-17). CISA scored the same flaw CVSS v2 1.8 (AV:A/AC:H/Au:N/C:N/I:N/A:P) and classes it as CWE-20, improper input validation (NVD, CISA ICSA-15-008-01A).
Where does the vulnerable code run?
On the engineering workstation, not in the field device. A DTM is the device-specific driver that an FDT frame application, such as asset-management or configuration software, loads to talk to one HART instrument. Here the attack runs in the opposite direction to the usual concern about wired HART: a rogue device connected to the loop answers the DTM with malformed responses, and the DTM and the frame stop. CISA's advisory states that "an attacker would require physical access to the HART loop", that exploitation is not possible with adequate physical protection of the loop, and that "field devices and WirelessHART installations are unaffected" (CISA CSAF of ICSA-15-008-01A).
Which device DTMs are affected?
CISA's machine-readable copy of ICSA-15-008-01A lists 57 Emerson device and revision entries whose DTMs carry the library. They include Fisher DVC6000 and DVC2000 digital valve controllers, Micro Motion 1700 and 2700 transmitters, Rosemount 2051 and 3051 pressure transmitters, Rosemount 644 and 3144P temperature transmitters, Rosemount 5300 and 5400 radar level transmitters and Rosemount 8712 and 8732 magnetic flowmeters. Emerson fixed them with one DTM: it updated the HART DTM for the Rosemount 644 Temperature Transmitter Rev. 8 to version 1.4.181 on 17 November 2014, and CISA says installing it "will resolve the vulnerability for all the impacted Emerson products listed above." The device install kit link in CISA's advisory now redirects to Emerson's Software & Drivers portal (checked 2026-11-17).
The same CVE appears in CISA's ICSA-15-237-01 for Endress+Hauser HART device DTMs. Its CSAF copy lists more than 100 Endress+Hauser product entries, among them Cerabar and Deltabar pressure transmitters, Micropilot radar level gauges and Promag and Promass flowmeters, and Endress+Hauser recommends updating the HART DTM library to 2.41 and the FieldCare FDT tool to 2.10 (CISA CSAF of ICSA-15-237-01).
Version matching needs care. NVD's CPE configuration matches the CodeWrights library up to and including 1.0.44, while the 1.4.181 in its description is the Emerson DTM version. A scanner that matches NVD's CPE will not see either vendor's DTM package numbers, so compare the DTMs installed in each frame application with the two CISA advisories instead.
Our HART and WirelessHART security guide lists this flaw with the later HART-family advisories and explains why loop wiring is the security boundary for classic wired HART. For the other HART-family pages, see CVE-2020-12030 in Emerson's WirelessHART gateways and CVE-2020-16209 in FieldComm Group's HART-IP reference server.
CVE-2014-9191 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.00377, the 32nd percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).
To fix it, install Emerson HART DTM 1.4.181 or later, or the Endress+Hauser HART DTM library 2.41 with FieldCare 2.10, on every workstation that runs the affected DTMs. Physical protection of loop terminals and junction boxes is the control CISA's advisory names for the attack path.
Evidence
- NVD description: CodeWrights HART DTM library in Emerson HART DTM before 1.4.181, physically proximate attackers, DTM outage and FDT Frame application hang via crafted response packets on the 4-20 mA current loop. NVD Primary CVSS v2 2.1 AV:L/AC:L/Au:N/C:N/I:N/A:P; no v3 metric; CWE-399; CPE codewrights hart_device_type_manager versionEndIncluding 1.0.44; published 2015-01-10. — NVD
- CSAF ICSA-15-008-01A: CWE-20; CVSS v2 1.8 AV:A/AC:H/Au:N/C:N/I:N/A:P; 57 Emerson Process Management product entries (Fisher DVC6000/DVC2000, Micro Motion, Rosemount, Rosemount Analytical); Emerson updated the Rosemount 644 Rev. 8 HART DTM to 1.4.181 on November 17, 2014, resolving all listed products; physical access to the HART loop required; field devices and WirelessHART installations unaffected. — CISA ICSA-15-008-01A (CSAF)
- CSAF ICSA-15-237-01 (Endress+Hauser HART Device DTM Vulnerability): CVE-2014-9191; Endress+Hauser product entries from Cerabar, Deltabar, Micropilot, Promag, Promass and others; recommends updating HART DTM library 2.41 and FDT tool FieldCare to version 2.10. — CISA ICSA-15-237-01 (CSAF)
- Not in the CISA KEV catalog, version 2026.11.13, checked 2026-11-17. — CISA KEV
- EPSS 0.00377, percentile 0.32151, dataset 2026-11-16. — FIRST EPSS

Related advisories
Sources
- NVD
- CISA ICS Advisory ICSA-15-008-01A: Emerson HART DTM Vulnerability (Update A)
- CISA CSAF: ICSA-15-008-01A (machine-readable advisory)
- Emerson Software & Drivers portal (device install kits)
- CISA ICS Advisory ICSA-15-237-01: Endress+Hauser HART Device DTM Vulnerability
- CISA CSAF: ICSA-15-237-01 (machine-readable advisory)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Does CVE-2014-9191 affect the HART field devices themselves?
No. The flaw is in the DTM software on the engineering workstation; a rogue device on the 4-20 mA loop sends crafted responses that hang the DTM and its FDT frame. CISA states field devices and WirelessHART installations are unaffected (per CISA ICSA-15-008-01A).
Which update fixes CVE-2014-9191?
For Emerson products, the HART DTM 1.4.181 released for the Rosemount 644 Rev. 8 on 17 November 2014 resolves it for all listed devices. For Endress+Hauser, update the HART DTM library to 2.41 and FieldCare to 2.10 (per CISA ICSA-15-008-01A and ICSA-15-237-01).
Why is the CVSS score for CVE-2014-9191 so low?
An attacker needs physical access to the HART loop, and the impact is a hang of configuration software, not of the process. NVD scores it CVSS v2 2.1 and CISA 1.8; NVD has no CVSS v3 score for it (per NVD and CISA, checked 2026-11-17).
Is CVE-2014-9191 in the CISA KEV catalog?
No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.00377, the 32nd percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?