CC-Link IE TSN has at least two Mitsubishi-disclosed, network-exploitable denial-of-service vulnerabilities on record in 2025 and 2026, and only the 2025 one has vendor firmware fixes. CVE-2026-13584 (CVSS v4.0 7.1) lets an attacker already on a CC-Link IE TSN network send specially crafted packets to tamper with control data and disrupt 37 listed product entries; CVE-2025-3511 (CVSS v3.1 7.5) lets a remote, unauthenticated attacker crash CC-Link IE TSN Remote I/O and MELSEC iQ-R/iQ-F modules with a single crafted UDP packet. Mitsubishi Electric's own advisory for the newer finding lists no fixed version as of its 5 November 2026 update — the mitigation is network segmentation and physical access control, not a firmware update.
This guide draws on CLPA's own technology, specification and security pages, Mitsubishi Electric's PSIRT advisory PDFs 2026-005 and 2025-001, NVD's records for both CVEs, and CISA's CSAF files for the republished advisories, each read on 12 November 2026.
Key takeaways
- CC-Link IE TSN has at least two Mitsubishi-disclosed, network-exploitable denial-of-service vulnerabilities on record in 2025 and 2026, and only the 2025 one has vendor firmware fixes.
- CC-Link IE TSN is the third generation of the CC-Link family; the CC-Link Partner Association (CLPA) published its specifications in 2018.
- Little at the protocol level; CLPA's guidance puts the controls around it.
- An attacker on the CC-Link IE TSN network can alter control data and cause a denial of service.
What is CC-Link IE TSN, and why does it matter for OT security?
CC-Link IE TSN is the third generation of the CC-Link family; the CC-Link Partner Association (CLPA) published its specifications in 2018. Per CLPA's technology page, it is "the world's first to adopt TSN (Time-Sensitive Networking) technology," sits at Layer 2 of the OSI model with standard Ethernet protocols in Layers 3-7, uses IEEE 802.1AS for time synchronization "within ±1 μs," and uses IEEE 802.1Qbv to schedule frames in time slots by priority. The same page says the network supports SNMP and that stations can be built on ASICs, FPGAs or a software protocol stack on a general-purpose Ethernet chip.
CLPA's specification sheet lists 1 Gbps and 100 Mbps links, line, star and ring topologies, up to 64,770 devices per network, and transient transmission whose "transmission capacity is the same as SLMP." That design goal, carrying motion control and ordinary IT traffic on one wire, is also the security issue: a host on a compromised IT segment is now on the same network as servos, I/O and controllers. Both CVEs below assume an attacker who already has that network position.
What security does the protocol itself provide?
Little at the protocol level; CLPA's guidance puts the controls around it. CLPA's security page describes three example threats and countermeasures:
| Threat (CLPA example) | Countermeasure CLPA describes | What it does |
|---|---|---|
| Ransomware via an infected USB device | IDS/IPS function | Detects or blocks malware that IP/port filtering misses |
| DoS attacks | Band limitation and network filtering | Only registered source IP addresses can reach the equipment |
| Tamper by spoofing | Authentication function | A remote password limits access through the master station, per ID |
The detailed CLPA security guidelines are available to CLPA members only. In a notice dated 24 August 2026, CLPA said it runs a Security Working Group with partners and pointed users to Mitsubishi Electric's advisory 2026-005. CLPA's development page describes conformance testing as ensuring "products meet communication specifications by testing communications performance," so a conformance certificate is not a security evaluation. Mitsubishi classes CVE-2026-13584 as CWE-924, improper enforcement of message integrity during transmission: the weakness sits in the protocol, which is why no single product's firmware closes it.
What does CVE-2026-13584 let an attacker do, and which products are affected?
An attacker on the CC-Link IE TSN network can alter control data and cause a denial of service. Mitsubishi Electric's advisory 2026-005 (released 30 July 2026, last updated 5 November 2026) says an attacker "may be able to tamper with communication data (control input/output values) by sending specially crafted packets under specific timing conditions," and may thereby cause "a denial-of-service (DoS) condition in the affected product by interfering with its control function or causing it to operate incorrectly." The CVSS v4.0 vector is AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:L/SC:N/SI:N/SA:N, base score 7.1: adjacent network, no privileges, no user interaction. Nozomi Networks researchers reported it.
The affected-products table has 37 numbered rows, every one at "All versions." It has changed twice: on 17 September 2026 Mitsubishi added MXF100S models and LD78G4/G16 and removed MI2532-W, MI2332-W and NZ2GACP610-60; on 5 November 2026 it added NZ2CT-GN and FR-D800-E. Examples:
| Product category | Example models |
|---|---|
| MELSEC MX Controllers | MXR300-16/32/64, MXR500-128/256, MXF100 and MXF100S series |
| Master/local modules and interface boards | RJ71GN11-T2/SX/EIP, FX5-CCLGN-MS, NZ81GN11-SX/T2 |
| Motion | RD78G4/G8/G16/G64, LD78G4/G16, MR-EM441G, SWM-G |
| Remote I/O, analog and FPGA modules | NZ2GN2S1/NZ2GN2B1 series, NZ2GN2S-60AD4, NZ2GN2S-D41P01 |
| Drives and servos | MELSERVO-J5, MELSERVO-JET, FR-A800/F800/E800/D800 inverters |
| HMIs and robots | GOT3000 (GT3715, GT3712, GT3710, GT3708), CR800-D Network Base Card 2F-DQ535-TSN |
| Silicon and SDKs | NZ2KT-NPETNG51 DeviceKit, NZ2GACP620/621 LSIs, SW1DNN-GN610SRC-M, SW1DNC-GNSDK1S/2S-M |
The advisory lists no fixed version. Its mitigations are to restrict physical access (site access control, locked control panels, port-lock accessories), to use the products only inside a trusted network where a firewall blocks untrusted hosts, and to configure credentials and access privileges on boundary network devices. CISA's CSAF file for ICSA-26-211-07 is at Update B, matching the 5 November revision.
Is CVE-2025-3511 fixed, and which firmware fixes it?
Yes, for every listed model. CVE-2025-3511 (CWE-1284, CVSS v3.1 7.5, AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H) lets a remote, unauthenticated attacker cause a denial of service with crafted UDP packets. Mitsubishi Electric's advisory 2025-001, last updated 27 August 2026, covers 14 rows. For the remote I/O, converter, FPGA and CP620 rows the attack works "if the affected product does not receive a valid UDP packet within 3 seconds," and "a system reset of the product is required for recovery." For FX5-ENET and FX5-ENET/IP it causes a CC-Link IEF Basic timeout and Simple CPU communication delay.
| Product | Affected | Fixed |
|---|---|---|
| CC-Link IE TSN Remote I/O (NZ2GN series) | 09 and prior | 10 or later |
| Analog-Digital / Digital-Analog converters | 07 and prior | 08 or later |
| FPGA module NZ2GN2S-D41P01/D41D01/D41PD02 | 01 | 02 or later |
| CP620 LSI NZ2GACP620-300/60 (sample code) | 1.08J and prior | 1.09K or later |
| RJ71GN11-T2 / -EIP / -SX | 26 / 10 / 05 and prior | 28 / 13 / 07 or later |
| RJ71EN71 and R04/08/16/32/120ENCPU network part | 85 and prior | 86 or later |
| CP610 LSI NZ2GACP610-60, NZ2KT-NPETNG51 | 05 and prior | 06 or later |
| FX5-CCLGN-MS / FX5-ENET / FX5-ENET/IP | 1.020 / 1.200 / 1.106 and prior | 1.030 / 1.210 / 1.107 or later |
The fixes arrived in stages: FX5 models were added to the advisory on 3 February 2026, their fixes on 23 April 2026, and the R-series CPU network part fix on 27 August 2026. NVD's CVE-2025-3511 record carries the same vector.
What does a device maker building on CC-Link IE TSN inherit?
If you make a drive, I/O block or sensor with a CC-Link IE TSN port, the protocol weakness is yours too. The 2026-005 table lists Mitsubishi's own silicon and kits: the CP620/621 remote station LSIs, the NZ2KT-NPETNG51 DeviceKit, the master/local LSI SDK and the remote station SDKs. Third-party devices built on those parts sit behind the same CWE-924 finding, and the CP620 sample code has its own CVE-2025-3511 fix (1.09K).
Software-stack devices bring their own dependencies. CLPA's remote station sample code runs on an STM32 NUCLEO-F439ZI board with FreeRTOS V10.3.1 and lwIP 2.1.2. A product derived from it ships those packages, and their CVEs, unless you update them. Mitsubishi's own managed switches show the pattern: ICSA-23-278-03 covered OpenSSL flaws (CVE-2022-4304, CVE-2022-4450) in NZ2MHG-TSNT8F2 and NZ2MHG-TSNT4, fixed in firmware 06.
For a maker, that means:
List the CC-Link IE TSN silicon, SDK version and sample-code base in your SBOM, next to the RTOS and IP stack. Our firmware SBOM guide covers how. Publish your own advisorywhen an upstream one lands, mapped to your models. Customers search by your product name, not Mitsubishi's LSI part number. Document the compensating controlsyour product supports (IP filtering, remote password, SNMP settings), because the IEC 62443-4-2 component requirements expect message-integrity capability that this protocol does not give you.
Worked example: how would a plant rank its CC-Link IE TSN exposure?
Synthetic example, for illustration only. A packaging line has one MXR300 controller, 12 MELSERVO-J5 servos, 20 NZ2GN2S1 remote I/O blocks (firmware 09), an RJ71EN71 (firmware 85) linking to the plant LAN, and two GOT3000 HMIs.
Separate the fixable from the unfixableThe 20 I/O blocks and the RJ71EN71 have CVE-2025-3511 fixes (10 and 86). Schedule those updates for the next maintenance window. Rank the CVE-2026-13584 exposure by reachabilityThe RJ71EN71 bridges the plant LAN and the CC-Link IE TSN segment; that boundary is where an attacker would enter, so its firewall rules come first. Lock physical accessThe servo cabinet has an unused switch port in the aisle. Fit a port lock and lock the panel, as the advisory recommends. Record the residual riskNo fix exists for the 37 rows of 2026-005, so the risk owner signs off the segmentation and physical controls and sets a date to re-check the advisory.
What are the common pitfalls?
- Reading an old copy of the advisory. The 2026-005 list grew from 35 to 37 rows; check the "Last update date" line.
- Assuming neither CVE is fixable. CVE-2025-3511 has firmware fixes for every listed model.
- Treating TSN scheduling or CLPA conformance as security. Neither authenticates frames.
- Forgetting engineering PCs. The 2025-001 advisory also recommends anti-virus on PCs that can reach the products.
- Device makers waiting for Mitsubishi to notify their customers. End users see your brand, not the LSI.
What should you do first?
Inventory every CC-Link IE TSN device with model and firmware versionBoth advisories are per-model; nothing can be assessed without that list. Apply the CVE-2025-3511 firmware fixeslisted in 2025-001. Segment the CC-Link IE TSN network behind an industrial DMZ, as NIST SP 800-82 and the Purdue Model recommend for integrity-unprotected OT protocols. The same reasoning appears in our PROFINET and EtherNet/IP guides. Treat Mitsubishi's physical-access mitigations as primary controls for CVE-2026-13584 Re-check both advisories before each change windowEach has been revised several times in 2026.
What can AI and passive monitoring tell you here?
Less than a full inventory, and it is worth being exact about where the limits are. SoftWSP matches a component list (vendor, model, firmware) against NVD, CISA KEV, FIRST EPSS and CISA CSAF ICS advisories, the feed that carries both Mitsubishi advisories. AI then drafts a cited summary of which devices matched which advisory and why; an engineer reviews every finding and decides whether segmentation, port locks or a firmware update applies.
The OT Snapshot reads Zeek logs from a mirror-port capture. It decodes Modbus, S7comm, DNP3, EtherNet/IP and BACnet and records IP hosts, ports and flows for everything else. CC-Link IE TSN's cyclic frames are Layer 2 Ethernet and do not appear there; IP traffic to the same modules (engineering tools, SNMP) appears as ordinary flows. The snapshot does not identify model or firmware from traffic, so the component list from step 1 above is still the input for advisory matching. Device makers can have their own firmware images analysed through device & firmware security.
This guide is not a substitute for Mitsubishi Electric's current advisories, CISA's current ICSA-26-211-07 and ICSA-25-128-03 records, or an engineer's assessment of a specific deployment, and does not constitute security advice.
Put this guide to work
Frequently asked questions
What is CC-Link IE TSN, and who maintains it?
CC-Link IE TSN is an open industrial Ethernet network maintained by the CC-Link Partner Association (CLPA), a Japan-based organization with, per its own site, more than 4,500 partner companies worldwide. CLPA's own technology page states it is "the world's first to adopt TSN (Time-Sensitive Networking) technology, which extends the standard Ethernet," placing the CC-Link IE TSN protocol at Layer 2 of the OSI reference model alongside standard Ethernet protocols running at Layers 3–7. For time synchronization, CLPA's page states the network uses IEEE 802.1AS to achieve "highly accurate time synchronization accuracy within ±1 μs," and IEEE 802.1Qbv to divide communication cycles into time slots so each connected station can schedule frame transmission according to priority. CC-Link IE TSN is the newest, "third generation" member of the broader CC-Link family, which also includes the original CC-Link fieldbus, CC-Link/LT for sensors and actuators, and CC-Link IE Field Network — the TSN variant is specifically positioned by CLPA for mixing different network traffic types on one physical network to support Industrial IoT (IIoT) and smart-factory deployments.
What does CVE-2026-13584 actually let an attacker do?
Per Mitsubishi Electric's own PSIRT advisory (2026-005, released 30 July 2026, last updated 5 November 2026), CVE-2026-13584 is an Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability (CWE-924) with a CVSS v4.0 base score of 7.1. Mitsubishi's advisory states plainly: "An attacker with access to a CC-Link IE TSN network may be able to tamper with communication data by sending specially crafted packets under specific timing conditions," and that "as a result, the attacker may be able to cause a denial-of-service (DoS) condition in the affected product by interfering with its control function or causing it to operate incorrectly." The advisory lists 37 numbered product entries as affected, spanning MELSEC MX Controllers, master/local communication modules, motion modules, AC servos (MELSERVO-J5 and -JET), industrial robot network cards, inverters, GOT3000 HMIs and multiple SDKs — all at "all versions," meaning no unaffected firmware revision exists. CISA republished the finding as ICSA-26-211-07 (Update B).
Is there a patch for CVE-2026-13584, and what does Mitsubishi recommend instead?
No. Mitsubishi Electric's own advisory lists no fixed version and directs customers to mitigations instead (as of its 5 November 2026 update). The advisory's "Mitigations / Workarounds" section recommends, verbatim in substance: restrict physical access to the affected products and to the CC-Link IE TSN network segment they connect to — by controlling site access, locking control panels that house the affected products or network devices, and locking Ethernet ports with port-lock accessories; use the affected products only within a trusted network where communication with untrusted networks and hosts is blocked by a firewall or equivalent control; and appropriately configure credentials and access privileges on network devices sitting at the boundary between trusted and external networks. Mitsubishi credits the discovery to Alessandro Di Pinto, Giovanni Dini Gentilini, Luca Cremona and Gabriele Quagliarella of Nozomi Networks, Inc. Because the vulnerability sits in the protocol's own message-integrity design rather than in one product's implementation bug, a firmware patch for any single device would not close the underlying gap across the other 36 affected product entries — which is consistent with Mitsubishi choosing network-segmentation mitigations over a patch.
Is CVE-2026-13584 the first disclosed vulnerability in CC-Link IE TSN products?
No — it is at least the second within roughly 15 months. CVE-2025-3511, published 25 April 2025 (also credited to Mitsubishi Electric's own PSIRT disclosure), is an Improper Validation of Specified Quantity in Input vulnerability (CWE-1284) with a CVSS v3.1 base score of 7.5 (vector AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H) — fully network-exploitable with no privileges or user interaction required. NVD's record describes it as allowing a remote, unauthenticated attacker to trigger denial-of-service by sending a specially crafted UDP packet to affected CC-Link IE TSN Remote I/O modules (NZ2GN series), Analog/Digital Converter modules, FPGA modules, several MELSEC iQ-R and iQ-F series modules (including RJ71GN11-T2, RJ71EN71, the R04/08/16/32/120ENCPU family, FX5-CCLGN-MS, FX5-ENET, FX5-ENET/IP), and CP610/CP620 communication LSIs. Two network-reachable denial-of-service findings against the same protocol family inside roughly 15 months is a pattern worth tracking, not a one-off.
Sources
- CLPA (CC-Link Partner Association): CC-Link IE TSN technology overview (TSN architecture, IEEE 802.1AS/802.1Qbv, OSI Layer 2 placement)
- Mitsubishi Electric Corporation: Security Advisory 2026-005 — Information tampering and Denial-of-service (DoS) vulnerability in CC-Link IE TSN communication protocol (released 30 July 2026, updated 5 November 2026, PDF)
- NVD: CVE-2026-13584 — CVSS v4.0 7.1, CWE-924, CC-Link IE TSN communication protocol message-integrity vulnerability
- NVD: CVE-2025-3511 — CVSS v3.1 7.5, CWE-1284, CC-Link IE TSN Remote I/O and MELSEC iQ-R/iQ-F module UDP input-validation vulnerability
- CISA: ICS Advisory ICSA-26-211-07 — Mitsubishi Electric CC-Link IE TSN Communication Protocol (Update B)
- Mitsubishi Electric Corporation: Security Advisory 2025-001 — Denial-of-Service Vulnerability in Ethernet function of multiple FA products (CVE-2025-3511; fixed versions; last updated 27 August 2026, PDF)
- CLPA: CC-Link IE TSN security page (security guideline outline, threat and countermeasure examples)
- CLPA: Security Advisory for CC-Link IE TSN (notice dated 24 August 2026, PDF)
- CLPA: Network specifications (CC-Link IE TSN communication speed, node count, SLMP transient transmission)
- CLPA: Sample code for CC-Link IE TSN remote station Class A (STM32 NUCLEO-F439ZI, FreeRTOS V10.3.1, lwIP 2.1.2)
- CLPA: Product development and conformance testing
- CLPA: Network technology overview (CC-Link family generations; CC-Link IE TSN specifications published 2018)
- CISA CSAF: ICSA-26-211-07 (Update B, revision history to 5 November 2026)
- CISA CSAF: ICSA-23-278-03 — Mitsubishi Electric CC-Link IE TSN Industrial Managed Switch (Update A; OpenSSL CVE-2022-4304, CVE-2022-4450; fixed in firmware 06)
About this guide
SoftWSP OT/ICS Desk
Covers the OT/ICS security cluster: 67 guides.

In this cluster
Questions about this page?