Security Advisory

CVE-2024-37365: FactoryTalk View ME Project Folder Flaw

Last updated:
  • CVE-2024-37365

CVE-2024-37365 is a project storage flaw in Rockwell Automation FactoryTalk View Machine Edition v14.0. It saves projects in a public folder, so anyone with local access can change or delete them, and a malicious user could edit a project macro to run code with higher privileges. NVD scores it 7.8, Rockwell 7.3. Rockwell corrected it in V15.0.

Vulnerability summary

CVSS base score

7.8

High severity

EPSS score (FIRST)

0.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2024-37365 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation FactoryTalk View Machine Edition (ME)cpe:2.3:a:rockwellautomation:factorytalk_view:14.0:*:*:*:machine:*:*:*v14.0 and earlier when using default folder privileges (CISA ICSA-24-317-03); NVD CPE: 14.0; corrected in V15.0

What does this mean for affected devices?

Rockwell Automation, the CNA, describes it as a code execution flaw that "allows users to save projects within the public directory allowing anyone with local access to modify and/or delete files. Additionally, a malicious user could potentially leverage this vulnerability to escalate their privileges by changing the macro to execute arbitrary code." NVD's Primary score is 7.8 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H); NVD records no CWE of its own (NVD-CWE-noinfo). Rockwell scores it CVSS 3.1 7.3 (AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H) and CVSS v4.0 7.0 with CWE-20, improper input validation; the difference is that Rockwell requires user interaction. NVD's configuration matches FactoryTalk View ME 14.0 (NVD, CVE record).

Which FactoryTalk View ME versions are affected?

CISA's ICSA-24-317-03 (CSAF), released on 2024-11-12, lists FactoryTalk View ME v14.0 and earlier "when using default folder privileges", deployed worldwide in the Critical Manufacturing sector, with the same 7.3 score. Rockwell reported it to CISA; its own record points to advisory SD1709 and gives the affected range as ">=V14", which reads as the opposite direction, so rely on CISA's wording and NVD's 14.0 entry. The View SE counterpart is CVE-2024-7513, a public-folder permission flaw in View SE 13.0; the View ME path traversal CVE-2025-9064 and the PanelView Plus code execution flaw CVE-2023-2071 affect other parts of the same product line.

How do you fix CVE-2024-37365?

Rockwell corrected the problem in V15.0. For users who cannot upgrade, CISA lists Rockwell's mitigations:

  • harden Windows by removing the INTERACTIVE group from the security properties of the HMI projects folder;
  • add specific users or user groups and give them permissions on that folder by least privilege; users with read-only permission can still test run and run FactoryTalk View ME Station;
  • follow the FactoryTalk View ME v14 Help topic "HMI projects folder settings" (FactoryTalk View ME Studio, Help, Contents, FactoryTalk View ME Help, Create a Machine Edition application, Open applications);
  • apply Rockwell's security best practices.

The Rockwell FactoryTalk software guide lists this CVE in its View ME table alongside the folder-permission fix it shares with View SE. The OT/ICS security guide for small manufacturers covers local account control on shared engineering PCs, which is what this flaw depends on.

Is CVE-2024-37365 exploited?

CVE-2024-37365 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0036, a percentile of 22.0, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Analyzed; published 2024-11-12; [email protected] Primary CVSS 3.1 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; NVD-CWE-noinfo; Rockwell Secondary CVSS 3.1 7.3 AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H and CVSS 4.0 7.0, CWE-20; CPE factorytalk_view 14.0 machine edition. — NVD
  • CISA ICSA-24-317-03 CSAF (read 2026-11-28): released 2024-11-12; FactoryTalk View ME, when using default folder privileges, <=v14.0; CWE-20; CVSS 3.1 7.3; Critical Manufacturing, worldwide; corrected in V15.0; remove INTERACTIVE group, least-privilege users; v14 Help topic HMI projects folder settings; reported by Rockwell. — CISA ICSA-24-317-03
  • CVE record (read 2026-11-28): PUBLISHED, assigner Rockwell, published 2024-11-12; FactoryTalk View Machine Edition >=V14; CWE-20; CNA CVSS 3.1 7.3, CVSS 4.0 7.0; solution upgrade to Version 15; reference advisory SD1709. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.00359, percentile 0.2197, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-24-317-03: Rockwell Automation FactoryTalk View ME
  3. CISA ICSA-24-317-03 CSAF (machine-readable advisory)
  4. CVE record CVE-2024-37365 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which FactoryTalk View ME versions are affected by CVE-2024-37365?

v14.0 and earlier when the default folder privileges are in place, per CISA ICSA-24-317-03; NVD's configuration lists 14.0. Rockwell corrected it in V15.0.

Who can exploit CVE-2024-37365?

Only someone with local access and a low-privileged account on the computer that holds the View ME projects. NVD and Rockwell both use a local attack vector; Rockwell also requires user interaction.

How do I mitigate CVE-2024-37365 without upgrading?

Remove the INTERACTIVE group from the HMI projects folder's security properties and grant access only to named users or groups by least privilege, as described in the View ME v14 Help topic "HMI projects folder settings".

Is CVE-2024-37365 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0036 (percentile 22.0) in the 2026-11-27 dataset.