Security Advisory

CVE-2025-9064: FactoryTalk View ME Path Traversal

Last updated:
  • CVE-2025-9064

CVE-2025-9064 is a path traversal flaw in Rockwell Automation FactoryTalk View Machine Edition, the HMI runtime on PanelView Plus 7 terminals and ASEM 6300 industrial PCs. An unauthenticated attacker on the same network can delete files in the panel operating system if they know the filenames. NVD scores it 9.1 and CISA 7.5. The fix is firmware V14.103 or patch BF31001.

Vulnerability summary

CVSS base score

9.1

Critical severity

EPSS score (FIRST)

0.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2025-9064 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation FactoryTalk View Machine Edition (PanelView Plus 7 Performance Series B; ASEM 6300 industrial PCs)cpe:2.3:a:rockwellautomation:factorytalk_view:*:*:*:*:machine:*:*:*NVD: up to and including 15.0; Rockwell CVE record: V15.00 and prior; CISA ICSA-25-289-01 product list: before V15.00. Fixed by the PanelView Plus 7 Performance Series B V14.103 firmware package, or patch BF31001 for FactoryTalk View ME V15.00 and later on ASEM 6300 IPCs

What does this mean for affected devices?

Rockwell Automation, the CNA, describes it as "a path traversal security issue" that allows "unauthenticated attackers on the same network as the device to delete any file within the panels operating system," adding that exploitation "is dependent on the knowledge of filenames to be deleted." NVD's Primary score is 9.1 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H) with CWE-22. The scores differ: CISA gives CVSS v3.1 7.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, availability impact only), and Rockwell gives CVSS v4.0 8.7 and maps CWE-287, improper authentication, in its record. NVD's configuration covers FactoryTalk View ME up to and including 15.0 (NVD, CVE record).

Which products are affected?

CISA's ICSA-25-289-01 (CSAF), released on 2025-10-16, covers FactoryTalk View Machine Edition and PanelView Plus 7, deployed worldwide in the Critical Manufacturing sector. Its product list gives View ME before V15.00 and PanelView Plus 7 V14.100, while Rockwell's record says V15.00 and prior and the remediation includes a patch for V15.00 systems, so treat V15.00 as affected until patched. Rockwell's own advisory is SD1753. The same CISA advisory lists CVE-2025-9063, an improper authorization flaw (CISA 7.3) that the V14.103 firmware package also fixes.

How do you fix CVE-2025-9064?

Per CISA and Rockwell, there are two fixes, one for each platform:

  • PanelView Plus 7 Performance Series B: install the V14.103 firmware package, which fixes both CVE-2025-9063 and CVE-2025-9064;
  • FactoryTalk View ME V15.00 and later on ASEM 6300 IPCs: install patch BF31001.

Owners who cannot upgrade at once should follow Rockwell's security best practices: keep HMI panels on a segmented machine network that only controllers and engineering hosts can reach, and off the internet. Losing files on the panel can stop the operator interface, so plan the firmware update with a tested project backup.

The Rockwell FactoryTalk software guide lists the View ME flaws together, including the 2023 PanelView Plus code execution flaw CVE-2023-2071. The path traversal fix guide explains how vendors close this bug class.

Is CVE-2025-9064 exploited?

CVE-2025-9064 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.008, a percentile of 53.1, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Path traversal. Our practical guide covers how to detect, fix, verify and disclose it: How to fix path traversal in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Analyzed; published 2025-10-14; [email protected] Primary CVSS 3.1 9.1 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H; Rockwell Secondary CVSS 4.0 8.7; CWE-22 (NVD Primary), CWE-287 (Rockwell Secondary); CPE factorytalk_view (machine) up to and including 15.0. — NVD
  • CISA ICSA-25-289-01 CSAF (read 2026-11-28): released 2025-10-16; products FactoryTalk View ME < V15.00 and PanelView Plus 7 V14.100; CVE-2025-9064 CWE-22, CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; fixes: PanelView Plus 7 Performance Series B V14.103 firmware package (CVE-2025-9063 and CVE-2025-9064), patch BF31001 for View ME V15.00 and later on ASEM 6300 IPCs; sibling CVE-2025-9063 CWE-285, 7.3; sector Critical Manufacturing. — CISA ICSA-25-289-01
  • CVE record (read 2026-11-28): PUBLISHED, assigner Rockwell, published 2025-10-14; FactoryTalk View ME V15.00 and prior; CWE-287; CNA CVSS 4.0 8.7; solutions V14.103 firmware and patch BF31001; reference Rockwell advisory SD1753. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.00795, percentile 0.53104, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-25-289-01: Rockwell Automation FactoryTalk View Machine Edition and PanelView Plus 7
  3. CISA ICSA-25-289-01 CSAF (machine-readable advisory)
  4. CVE record CVE-2025-9064 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which FactoryTalk View ME systems are affected by CVE-2025-9064?

FactoryTalk View Machine Edition up to V15.00, on PanelView Plus 7 Performance Series B terminals and on ASEM 6300 industrial PCs. CISA's product list says before V15.00; Rockwell's record says V15.00 and prior, and NVD covers up to and including 15.0.

How do I fix CVE-2025-9064?

On PanelView Plus 7 Performance Series B, install the V14.103 firmware package. On ASEM 6300 IPCs running View ME V15.00 or later, install patch BF31001. Both come from Rockwell's download and support sites.

Why does NVD rate it 9.1 when CISA says 7.5?

CISA scored only the availability impact of deleted files (A:H). NVD also counted the integrity impact of deleting arbitrary files (I:H), which raises the CVSS 3.1 base score to 9.1. Rockwell's CVSS 4.0 score is 8.7.

Is CVE-2025-9064 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.008 (percentile 53.1) in the 2026-11-27 dataset.