Security Advisory

CVE-2024-37369: FactoryTalk View SE Script Permissions Flaw

Last updated:
  • CVE-2024-37369

CVE-2024-37369 is a file permission flaw in Rockwell Automation FactoryTalk View Site Edition v12.0, the distributed HMI that runs supervisory screens in many plants. Low-privilege users can edit scripts, bypass access control lists and potentially gain further access to the system. NVD scores it 8.8, CISA 7.8. Rockwell corrected it in FactoryTalk View SE V14.0 and later.

Vulnerability summary

CVSS base score

8.8

High severity

EPSS score (FIRST)

0.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2024-37369 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation FactoryTalk View Site Edition (SE)cpe:2.3:a:rockwellautomation:factorytalk_view:*:*:*:*:se:*:*:*v12.0 (CISA ICSA-24-165-17 and Rockwell's record; NVD: from 12.0 up to, not including, 14.0); corrected in V14.0 and later

What does this mean for affected devices?

Rockwell Automation, the CNA, describes it as "a privilege escalation vulnerability" that "allows low-privilege users to edit scripts, bypassing Access Control Lists, and potentially gaining further access within the system." NVD's Primary score is 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) with CWE-732, incorrect permission assignment for a critical resource. CISA scores it CVSS 3.1 7.8 (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) and Rockwell gives CVSS v4.0 8.5; both use a local attack vector where NVD uses network. NVD's configuration covers FactoryTalk View SE from 12.0 up to, but not including, 14.0 (NVD, CVE record).

Which FactoryTalk View SE versions are affected?

CISA's ICSA-24-165-17 (CSAF), released on 2024-06-13, lists FactoryTalk View SE v12.0, deployed worldwide in the Critical Manufacturing sector. Rockwell reported it to CISA. Rockwell's CVE record, which points to its advisory SD1674, gives V12.0 as the first known affected version and v14 as the corrected one. NVD's range also takes in releases between 12.0 and 14.0, such as 13.0. View SE scripts run on HMI servers and operator stations, so an edited script can change what operators see or what commands go to the controllers.

How do you fix CVE-2024-37369?

Upgrade to FactoryTalk View SE V14.0 or later, where Rockwell corrected the problem. Users who cannot upgrade should apply Rockwell's security best practices and use the Secure Install option when installing FactoryTalk Services Platform. Limit who can log on to View SE servers and operator stations, and review the permissions on project folders: CISA's later advisory ICSA-24-226-06 reports a related View SE 13.0 permissions flaw, CVE-2024-7513, and asks owners to remove the INTERACTIVE group from the HMI projects folder.

The Rockwell FactoryTalk software guide lists every View SE flaw with its fix, including the folder permission advice. The platform underneath View SE has its own token flaw, CVE-2024-21917, fixed in FTSP v6.40. For locking down HMI stations with a small team, see the OT/ICS security guide for small manufacturers.

Is CVE-2024-37369 exploited?

CVE-2024-37369 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0064, a percentile of 45.3, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS). CISA's advisory reported no known public exploitation when it was published.

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Analyzed; published 2024-06-14; [email protected] Primary CVSS 3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; Rockwell Secondary CVSS 4.0 8.5 (AV:L); CWE-732 (NVD Primary and Rockwell); CPE factorytalk_view (se) from 12.0 (including) to 14.0 (excluding). — NVD
  • CISA ICSA-24-165-17 CSAF (read 2026-11-28): released 2024-06-13; FactoryTalk View SE v12.0; CWE-732; CVSS 3.1 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; corrected in V14.0 and later; Secure Install option of FactoryTalk Services Platform; reported by Rockwell Automation. — CISA ICSA-24-165-17
  • CVE record (read 2026-11-28): PUBLISHED, assigner Rockwell, published 2024-06-14; FactoryTalk View SE 12.0; CWE-732; CNA CVSS 4.0 8.5; solution: first known V12.0, corrected v14; Secure Install option; reference Rockwell advisory SD1674. — CVE.org
  • CISA ICSA-24-226-06 CSAF (read 2026-11-28): CVE-2024-7513 in FactoryTalk View SE 13.0, CWE-732; mitigation removes the INTERACTIVE group from the HMI projects folder. — CISA ICSA-24-226-06
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.00640, percentile 0.45285, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-24-165-17: Rockwell Automation FactoryTalk View SE
  3. CISA ICSA-24-165-17 CSAF (machine-readable advisory)
  4. CVE record CVE-2024-37369 (CVE Services JSON)
  5. CISA ICSA-24-226-06 CSAF: Rockwell Automation FactoryTalk View Site Edition
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which FactoryTalk View SE versions are affected by CVE-2024-37369?

CISA and Rockwell list FactoryTalk View SE v12.0. NVD's configuration covers 12.0 up to, but not including, 14.0, which also takes in 13.0.

How do I fix CVE-2024-37369?

Upgrade to FactoryTalk View SE V14.0 or later. If you cannot upgrade yet, use the Secure Install option of FactoryTalk Services Platform, apply Rockwell's security best practices and restrict logons to View SE hosts.

Is CVE-2024-37369 remotely exploitable?

The scorers differ. CISA and Rockwell use a local attack vector by a low-privilege user; NVD scores it as network-reachable with low privileges (8.8). In every case the attacker needs an account, so limiting who can log on to View SE hosts reduces exposure.

Is CVE-2024-37369 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0064 (percentile 45.3) in the 2026-11-27 dataset.