Security Advisory

CVE-2023-2071: FactoryTalk View ME PanelView Plus RCE

Last updated:
  • CVE-2023-2071

CVE-2023-2071 is a remote code execution flaw in Rockwell Automation FactoryTalk View Machine Edition 13.0 and earlier on PanelView Plus operator terminals. A CIP function meant to call only approved library routines does not check its input well enough, so an unauthenticated attacker on the network could run code. NVD, Rockwell and CISA all score it 9.8. Rockwell fixes it with security patch BF29493.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-2071 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation FactoryTalk View Machine Edition (on PanelView Plus terminals)cpe:2.3:a:rockwellautomation:factorytalk_view:*:*:*:*:machine:*:*:*13.0 and earlier (NVD: up to and including 13.0, running on PanelView Plus; CISA ICSA-23-264-06: v13.0 and v12.0 and earlier); fixed by the v12.0 and v13.0 security patch BF29493

What does this mean for affected devices?

Rockwell Automation, the CNA, describes the flaw this way: FactoryTalk View Machine Edition on the PanelView Plus "improperly verifies user's input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets." The terminal can run exported functions from libraries through a CIP class, and a routine meant to limit that to two approved libraries can be bypassed. NVD's Primary score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), the same 9.8 that Rockwell published. Rockwell and CISA map CWE-20, improper input validation; NVD maps CWE-434, unrestricted upload of a file with a dangerous type. NVD's configuration covers FactoryTalk View ME up to and including 13.0 running on a PanelView Plus (NVD, CVE record).

Which FactoryTalk View ME versions are affected?

CISA's ICSA-23-264-06 (CSAF), released on 2023-09-21, lists FactoryTalk View Machine Edition v13.0 and v12.0 and earlier, deployed worldwide in the Critical Manufacturing sector. Rockwell credits Yuval Gordon, CPS Research and the Microsoft Threat Intelligence Community with reporting it. FactoryTalk View ME is the HMI runtime on PanelView Plus panels at the machine, so the vulnerable component sits on the plant floor network next to the controllers.

How do you fix CVE-2023-2071?

Install the security patch for your version. Rockwell's CVE record names it as BF29493, "Patch: FactoryTalk Linx CIP Vulnerability issue, FactoryTalk View ME 12.0, 13.0", on Rockwell's support site, which needs a login. CISA adds that Rockwell asks owners to move to corrected firmware revisions and to follow its security best practices. Until the patch is in, keep PanelView Plus terminals on a segmented cell network that only the controllers and engineering hosts can reach, and keep them off the internet. A month later CISA's ICSA-23-290-02 covered CVE-2023-29464, a memory leak and denial-of-service flaw in FactoryTalk Linx 6.20 and earlier on the same terminals, fixed by its own security patches.

The Rockwell FactoryTalk software guide lists the View ME flaws by version, including the 2025 path traversal CVE-2025-9064. For segmenting HMI panels with a small team, see the OT/ICS security guide for small manufacturers.

Is CVE-2023-2071 exploited?

CVE-2023-2071 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0127, a percentile of 69.8, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2023-09-12; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; Rockwell Secondary 9.8 same vector; CWE-434 (NVD Primary), CWE-20 (Rockwell Secondary); CPE factorytalk_view (machine) up to and including 13.0, running on panelview_plus. — NVD
  • CISA ICSA-23-264-06 CSAF (read 2026-11-28): released 2023-09-21; FactoryTalk View ME v13.0 and <= 12.0; CWE-20; CVSS v3 9.8; fix: v12.0 and v13.0 patch; reported by Yuval Gordon, CPS Research and the Microsoft Threat Intelligence Community; sector Critical Manufacturing. — CISA ICSA-23-264-06
  • CVE record (read 2026-11-28): PUBLISHED, assigner Rockwell, published 2023-09-12; affected <= 13.0; CWE-20; CNA CVSS 3.1 9.8; solution: patch BF29493 (FactoryTalk Linx CIP Vulnerability issue, FactoryTalk View ME 12.0, 13.0). — CVE.org
  • CISA ICSA-23-290-02 CSAF (read 2026-11-28): CVE-2023-29464, FactoryTalk Linx <= 6.20 on PanelView Plus, memory read and CIP denial of service, CISA 8.2; install the security patches for the respective versions. — CISA ICSA-23-290-02
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01266, percentile 0.69796, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-23-264-06: Rockwell Automation FactoryTalk View Machine Edition
  3. CISA ICSA-23-264-06 CSAF (machine-readable advisory)
  4. CVE record CVE-2023-2071 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which devices are affected by CVE-2023-2071?

PanelView Plus operator terminals running FactoryTalk View Machine Edition 13.0 or earlier. CISA lists v13.0 and v12.0 and earlier; NVD's configuration covers View ME up to and including 13.0 on a PanelView Plus.

How do I fix CVE-2023-2071?

Install Rockwell security patch BF29493 for FactoryTalk View ME 12.0 or 13.0 from the Rockwell support site, which needs a login. Keep the terminals on a segmented cell network until the patch is in.

Why do NVD and Rockwell list different CWEs?

Rockwell and CISA classify the root cause as improper input validation (CWE-20). NVD maps it to unrestricted upload of a file with a dangerous type (CWE-434), in line with the record's description of a self-made library uploaded to the device. The score is 9.8 either way.

Is CVE-2023-2071 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0127 (percentile 69.8) in the 2026-11-27 dataset.