Security Advisory

CVE-2024-7513: FactoryTalk View SE Project File Permissions

Last updated:
  • CVE-2024-7513

CVE-2024-7513 is a file permission flaw in Rockwell Automation FactoryTalk View Site Edition 13.0. The default permissions on the HMI projects folder let any user edit or replace project files that an account with elevated permissions later executes, which turns a low-privilege login into code execution. NVD and CISA both score it 8.8. Rockwell's fix is v15.0; folder permission changes mitigate it.

Vulnerability summary

CVSS base score

8.8

High severity

EPSS score (FIRST)

2.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2024-7513 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation FactoryTalk View Site Edition (SE)cpe:2.3:a:rockwellautomation:factorytalk_view:*:*:*:*:se:*:*:*13.0 (CISA ICSA-24-226-06 and Rockwell's record; NVD: 13.0 and later, no upper bound); Rockwell's record gives v15.0 as the fix

What does this mean for affected devices?

Rockwell Automation, the CNA, describes a code execution vulnerability that "occurs due to improper default file permissions allowing any user to edit or replace files, which are executed by account with elevated permissions." NVD's Primary score is 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) with CWE-732, incorrect permission assignment for a critical resource. CISA also gives 8.8, but with a local vector and changed scope (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H), and Rockwell scores it CVSS v4.0 8.5 (AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N). NVD's configuration matches FactoryTalk View SE from 13.0 with no upper bound (NVD, CVE record).

Which FactoryTalk View SE versions are affected?

CISA's ICSA-24-226-06 (CSAF), released on 2024-08-13 and updated (Update A) on 2024-08-29, lists FactoryTalk View SE 13.0, deployed worldwide in the Chemical, Commercial Facilities, Critical Manufacturing, Energy, Government Facilities and Water and Wastewater Systems sectors. Rockwell reported it to CISA and refers to its own advisory SD 1688. By default, CISA notes, all HMI server projects sit in C:\Users\Public\Documents\RSView Enterprise\SE\HMI projects on the HMI server, a public folder. A related View SE flaw, CVE-2024-37369, lets low-privilege users edit scripts in v12.0, and FactoryTalk View ME has the same public-folder problem as CVE-2024-37365.

How do you fix CVE-2024-7513?

Rockwell's record says to upgrade to v15.0. Where that has to wait, CISA lists Rockwell's folder hardening for the HMI server computer:

  • remove the INTERACTIVE group from the security properties of the HMI projects folder (Rockwell's record also says to remove the Everyone group's read and write rights);
  • add specific users or user groups and give them only the permissions they need; users with read-only permission can still test run and run the FactoryTalk View SE client;
  • in Version 14, the steps are in FactoryTalk View Studio under Help, FactoryTalk View SE Help, Security, "HMI projects folder".

The Rockwell FactoryTalk software guide lists this CVE with CVE-2023-46289 as open on an unpatched View SE 13.0 node with the default projects folder. Its EPSS percentile of 85.9 sits well above most FactoryTalk CVEs; see the KEV and EPSS prioritization guide for how to use that.

Is CVE-2024-7513 exploited?

CVE-2024-7513 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0257, a percentile of 85.9, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Analyzed; published 2024-08-14; [email protected] Primary CVSS 3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; Rockwell Secondary CVSS 4.0 8.5 AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N; CWE-732; CPE factorytalk_view se from 13.0, no upper bound. — NVD
  • CISA ICSA-24-226-06 CSAF (read 2026-11-28): released 2024-08-13, Update A 2024-08-29; FactoryTalk View SE 13.0; CWE-732; CVSS 3.1 8.8 AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H; default projects folder C:\Users\Public\Documents\RSView Enterprise\SE\HMI projects; remove INTERACTIVE group, add specific users; Version 14 help path; Rockwell SD 1688; reported by Rockwell. — CISA ICSA-24-226-06
  • CVE record (read 2026-11-28): PUBLISHED, assigner Rockwell, published 2024-08-14; FactoryTalk View Site Edition 13.0; CWE-732; CNA CVSS 4.0 8.5; solution upgrade to v15.0; workaround remove Everyone group read/write on the project folder; reference advisory SD 1688. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.02572, percentile 0.85913, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-24-226-06: Rockwell Automation FactoryTalk View Site Edition
  3. CISA ICSA-24-226-06 CSAF (machine-readable advisory)
  4. CVE record CVE-2024-7513 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which FactoryTalk View SE versions are affected by CVE-2024-7513?

Version 13.0, per CISA ICSA-24-226-06 and Rockwell's record. NVD's configuration starts at 13.0 with no upper bound; Rockwell names v15.0 as the fix.

How do I fix CVE-2024-7513 without upgrading?

On the HMI server, remove the INTERACTIVE group (and the Everyone group's write rights) from the HMI projects folder and grant access only to named users or groups. Read-only users can still run the View SE client.

Why does NVD use a network vector for CVE-2024-7513 when CISA says local?

NVD scores it AV:N, CISA AV:L with changed scope; both land on 8.8. Rockwell's CVSS v4.0 score, 8.5, also uses a local vector. The flaw needs a user account that can reach the projects folder either way.

Is CVE-2024-7513 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0257 (percentile 85.9) in the 2026-11-27 dataset.